# Range Hood and Cooker Hood Airflow Calculator (CFM, L/s and Make-Up Air)

> The kitchen extract the 2021 IRC, NBC 2020 or England's rules ask of a range (cooker) hood, HVI's figure for the cooktop, and when make-up air is needed.

Page: https://craftquantities.com/calculators/plumbing-hvac/range-hood-airflow-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-10-31, 6 published test vectors.

Make-up air the code asks for: 600 CFM for Cooktop or Range Width 30 in and Hood's Rated Airflow at Its Top Setting 600 CFM, the page's opening figures, to compare with the limit shown with it; a comparison, not a check. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Code | `code` | United States: 2021 IRC (M1503.6, M1505.4.4) | United States: 2021 IRC (M1503.6, M1505.4.4) | `irc`, `nbc`, `adf` |
| Cooktop or Range Width | `cooktopWidth` | 60 cm | 30 in | mm, cm, m, in, ft, yd; range 0.2–3 m |
| Hood Position | `hoodPosition` | Against a wall | Against a wall | `wall`, `island` |
| Hood's Rated Airflow at Its Top Setting | `hoodRating` | 1000 m³/h | 600 CFM | lps, m3h, lpm, cfm; range 1–2000 L/s |
| Fuel-Burning Appliances in the Home | `appliance` | A natural-draft (open-flued) furnace, boiler or water heater elsewhere in the home | A natural-draft (open-flued) furnace, boiler or water heater elsewhere in the home | `none`, `heating`, `kitchen` |

- **Code**: The code whose kitchen extract and make-up air rules the page restates.
- **Cooktop or Range Width**: The width of the cooking surface the hood serves, which sets the trade guide's airflow.
- **Hood Position**: A hood over an island has no wall behind it to steer the plume, so the guide asks more of it.
- **Hood's Rated Airflow at Its Top Setting**: The most the hood is rated to move, from its label or data sheet; the codes judge what it is capable of, not the speed you use.
- **Fuel-Burning Appliances in the Home**: Whether a hood running hard could pull flue gases back down a natural-draft flue, which is what the make-up air rules guard against.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Make-up air the code asks for** | 278 L/s |
| Hood airflow as rated | 277.78 L/s |
| Code minimum for a kitchen extract | 47.19 L/s |
| HVI's recommended airflow for this cooktop | 92.9 L/s |
| HVI's minimum for this cooktop | 37.16 L/s |
| Airflow at which the code's combustion-air rule starts | 188.78 L/s |

### US customary

| Result | Value |
|---|---|
| **Make-up air the code asks for** | 600 CFM |
| Hood airflow as rated | 600 CFM |
| Code minimum for a kitchen extract | 100 CFM |
| HVI's recommended airflow for this cooktop | 250 CFM |
| HVI's minimum for this cooktop | 100 CFM |
| Airflow at which the code's combustion-air rule starts | 400 CFM |

- Confidence: medium.
- The figure is compared against a limit; that is a check of the number, not an approval.

## How it is worked out

The hood's rating is above the 400 CFM (189 L/s) line in M1503.6 of the 2021 IRC, and a natural-draft appliance shares the air barrier, so that section asks for make-up air at about the hood's own rate, mechanical or passive, with a damper that opens when the hood runs. This needs checking by a qualified person before you proceed. This restates a published requirement and compares it with what you entered. It is not an inspection and it is not a compliance determination — a competent person has to verify the installed work.

The working the page shows, in order: Hood airflow as rated; Code minimum for a kitchen extract; HVI's recommended airflow for this cooktop; HVI's minimum for this cooktop; Airflow at which the code's combustion-air rule starts; then make-up air the code asks for.

The method, derived in full:

- [Ventilation: Net Free Area, Air Change and the Openings That Deliver Them](https://craftquantities.com/methodology/ventilation-openings-and-air-change/): Why a wooden louvre delivers a quarter of the hole you cut and a metal one three-quarters, why intake and exhaust have to be balanced or the roof ventilates the house, and why doubling the pressure does not double the flow.

What this calculation does not cover:

- The codes are restated, not applied. Which edition a jurisdiction adopted, its amendments, and the exceptions each rule carries (the IRC's for space cooling, Canada's for a depressurization test, England's for a specification beyond its guidance) decide what is actually required, and an inspector or building control body decides whether it is met.
- Ratings are not delivered airflow. A hood rated at a stated static pressure moves less through a long, narrow or bent duct. The IRC asks for fans listed and labeled for their airflow and states its bathroom rate at 0.25 in. w.c. (62 Pa), but names no pressure for the kitchen rate; a recirculating hood, which filters and returns the air, extracts nothing and is not a kitchen extract under England's guidance.
- HVI's figures are a trade association's guide per foot of range, not a code; a high-output gas range or a commercial-style cooktop may call for more, and the hood's capture (its depth, its height above the cooktop and whether it overhangs the front burners) matters as much as its airflow.
- No duct, damper or make-up air path is sized. Where make-up air is required, where it enters, how it is tempered and how its damper is controlled are the designer's, and the codes' own subsections say more than the headline figure.
- Combustion safety is a property of the house, not of the hood. Even with no make-up air required on paper, a tight house with a natural-draft appliance can be depressurized by several fans at once, and a worst-case depressurization or spillage test is how that is found out.

A professional must decide:

- The codes are restated, not applied. Which edition a jurisdiction adopted, its amendments, and the exceptions each rule carries (the IRC's for space cooling, Canada's for a depressurization test, England's for a specification beyond its guidance) decide what is actually required, and an inspector or building control body decides whether it is met.

## Sources

As the calculator cites them (sources checked 2026-10-31):

- International Code Council, 2021 International Residential Code, as adopted without amendment in the Colorado Division of Fire Prevention and Control Residential Code 2021: M1503.6 makeup air for an exhaust system capable of more than 400 cfm (0.19 m³/s) where a fuel-burning appliance that is neither direct-vent nor mechanical-draft is inside the dwelling unit's air barrier, at a rate approximately equal to the exhaust rate, with the space-cooling exception; Table M1505.4.4, kitchens 100 cfm intermittent or 25 cfm continuous (its footnote a states the bathroom rate at 0.25 in. w.c., 62 Pa; the kitchen row names no static pressure); M1505.3, fans listed and labeled for their airflow to ANSI/AMCA 210-ANSI/ASHRAE 51. Ohio's Residential Code (Ohio Adm. Code 4101:8-15-01, effective 1 July 2019) and the 2024 IRC carry the same 1503.6 wording <https://up.codes/viewer/colorado/irc-2021/chapter/15/exhaust-systems>
- National Research Council of Canada, National Building Code of Canada 2020 (NBC 2020), Division B: 9.32.3.7.(1)–(3), a supplemental exhaust fan of not less than 50 L/s in each kitchen and its exceptions; 9.32.3.8, protection against depressurization: with a fuel-fired space- or water-heating appliance that is not direct- or mechanically vented, outdoor makeup air from a fan rated at not less than the exhausting device's capacity and not more than 10% above it, interlocked with it, tempered to at least 12 °C or delivered to an unoccupied area; exceptions for solid fuel only, a CAN/CGSB-51.71 depressurization test, and radon subfloor systems
- HM Government, Approved Document F Volume 1: Dwellings (2021 edition, in force 15 June 2022): Table 1.1, intermittent extract of 30 l/s from a kitchen with a cooker hood extracting to the outside and 60 l/s without one; Table 1.2, a continuous high rate of 13 l/s; paragraph 1.21, a cooker hood 650 to 750 mm above the hob unless the maker specifies; paragraphs 0.17–0.18, fans and open-flued appliances under Approved Document J <https://assets.publishing.service.gov.uk/government/uploads/system/uploads/attachment_data/file/1045918/ADF1.pdf>
- HM Government, Approved Document J (2010 edition incorporating 2010, 2013 and 2022 amendments), 1.20: where a kitchen contains an open-flued gas appliance, the kitchen extract fan's rate should not exceed 20 litres/second (72 m³/hour); 40 l/s for an oil appliance with a pressure-jet burner and 20 l/s with a vaporising burner; no extract in the same room as a solid fuel appliance; 1.21, a spillage test under the greatest depressurization <https://assets.publishing.service.gov.uk/media/6336e58be90e0772dc9651a2/ADJ_2022.pdf>
- Home Ventilating Institute, 'How Much Ventilation Do I Need?' (Home Ventilation Guide): range hoods against a wall 100 CFM recommended and 40 CFM minimum per linear foot of range; over an island 150 and 50; worked at 2.5 ft, 3 ft and 4 ft <https://www.hvi.org/resources/publications/home-ventilation-guide-articles/how-much-ventilation-do-i-need/>

The site's pages for the documents these name:

- [International Residential Code](https://craftquantities.com/standards/icc/irc/)
- [Approved Documents to the Building Regulations (England)](https://craftquantities.com/standards/uk-gov/uk-approved-documents/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**How many CFM does a range hood need?**

Two different answers. The US code minimum for a kitchen is 100 CFM (47.2 L/s) intermittent, which almost any hood meets. The Home Ventilating Institute's guide asks more for good capture: 100 CFM for each foot of range against a wall (155 L/s a metre) and 150 over an island (232 L/s a metre), so 250 CFM (118 L/s) for a 30 in (76 cm) range on a wall, with 40 and 50 CFM a foot (62 and 77 L/s a metre) as its minimums. A powerful gas range or a hood mounted high may need more than the guide, and more airflow than that brings the make-up air question.

**When does a range hood need make-up air?**

Under M1503.6 of the 2021 IRC, when the hood can exhaust more than 400 CFM (189 L/s) and the house has a fuel-burning appliance inside its air barrier that is neither direct-vent nor power-vented, such as a natural-draft water heater or furnace, or a fireplace. The make-up air must be about equal to the hood's rate. All-electric homes and homes with only sealed-combustion appliances are outside it in the 2021 text. Older editions and local amendments are worded differently, so check the code your jurisdiction adopted.

**How is this different in Canada?**

The National Building Code of Canada has no 400 CFM line. Where a home has a fuel-fired space- or water-heating appliance that is not direct-vented or mechanically vented, Article 9.32.3.8 asks for a make-up air fan for any exhaust device other than the principal ventilation fan, sized at no less than the device's capacity and no more than 10% above it, unless a depressurization test to CAN/CGSB-51.71 shows the appliances are safe. Each kitchen also needs a supplementary exhaust fan of at least 50 L/s (106 CFM), with exceptions where the principal fan serves the kitchen.

**What extract rate does a cooker hood need in England?**

Approved Document F (2021) asks 30 l/s (64 CFM, 108 m³/h) from a cooker hood that extracts to the outside, or 60 l/s (127 CFM, 216 m³/h) from a kitchen extract fan where there is no such hood; a recirculating hood does not count. Approved Document J then limits a kitchen extract fan to 20 l/s (42 CFM, 72 m³/h) where the kitchen contains an open-flued gas appliance, and asks for a spillage test wherever fans and open-flued appliances share a house. England's guidance has no make-up air requirement as such.

**Does a bigger hood always clear the kitchen better?**

Not by airflow alone. Capture depends on the hood being wide and deep enough, low enough over the cooktop and overhanging the front burners, and on air being able to come into the room to replace what leaves; a big fan in a tight house with no make-up air moves less than its rating and can pull flue gases back down a chimney. Size the hood to the cooktop, then deal with where its air comes from.

## Related calculators

- [Commercial Kitchen Ventilation Hood Exhaust CFM Calculator](https://craftquantities.com/calculators/materials-quantities/kitchen-hood-exhaust-cfm-calculator/)
- [Worst-Case Envelope Depressurisation Calculator](https://craftquantities.com/calculators/plumbing-hvac/worst-case-depressurisation-calculator/)
- [Bathroom Extract Fan Rate and Duct Resistance Calculator](https://craftquantities.com/calculators/plumbing-hvac/bathroom-extract-rate-calculator/)
- [CFM to Litres per Second Calculator](https://craftquantities.com/calculators/measurements-conversions/cfm-to-liters-per-second-calculator/)
- [Litres per Second to CFM Calculator](https://craftquantities.com/calculators/measurements-conversions/liters-per-second-to-cfm-calculator/)
- [Appliance Combustion Air Free Area Calculator (Indoor Air Method)](https://craftquantities.com/calculators/materials-quantities/combustion-air-free-area-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/range-hood-airflow-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/range-hood-airflow-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `range-hood-airflow-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/range-hood-airflow-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/range-hood-airflow-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.