# HVAC Duct Size Calculator

> Find the recommended round duct diameter for a given airflow (CFM or L/s) and target air velocity.

Page: https://craftquantities.com/calculators/plumbing-hvac/hvac-duct-cfm-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Recommended round duct diameter: 10.2 in (round duct diameter) for Airflow 400 CFM and Target air velocity 700 ft/min, the page's opening figures; on the metric page, 188.78 L/s and 3.56 m/s give 260 mm. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Airflow | `cfm` | 188.779 L/s | 400 CFM | lps, m3h, lpm, cfm; range 9.4389–2359.74 L/s |
| Target air velocity | `targetVelocityFpm` | 3.556 m/s | 700 ft/min | ms, fpm, fps; range 1.524–7.62 m/s |

- **Airflow**: The required airflow for this duct run.
- **Target air velocity**: The design airflow speed through the duct.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Recommended round duct diameter** | 260 mm |
| Required cross-sectional area | 0.05 m² |

### US customary

| Result | Value |
|---|---|
| **Recommended round duct diameter** | 10.2 in (round duct diameter) |
| Required cross-sectional area | 0.57 sq ft |

- Confidence: medium.

## How it is worked out

This sizes for velocity only — a full duct design also accounts for static pressure and total system friction loss (duct length, fittings, filters) using manufacturer duct-sizing charts.

The working the page shows, in order: Required cross-sectional area; then recommended round duct diameter.

The method, derived in full:

- [Flow, Velocity and Sizing a Duct or Pipe](https://craftquantities.com/methodology/flow-velocity-and-duct-or-pipe-sizing/): Why sizing a conduit is really choosing a velocity — capped above by noise and wear, held up from below by settlement — and then solving for the area.

What this calculation does not cover:

- Velocity is the entire model. The diameter comes from airflow divided by the speed you type, with no friction rate, no duct length, no elbows or takeoffs and no filter or coil resistance in it, so a run sized here can still be one the blower cannot push its rated air through.
- This sizes one duct run; it is not a duct system design and not an ACCA Manual D. It produces no total effective length, no available static pressure and no friction rate, so where a permit, an energy-code compliance path or an equipment warranty calls for a documented duct design, this does not stand in for one.
- The answer is a theoretical diameter, not a size you can buy. Round pipe and flex come in fixed increments and nothing here steps the result onto one — take the next size up, because dropping to the size below raises velocity, noise and pressure loss at the same time.
- Duct material and condition are not part of the calculation. Flexible duct is rougher than smooth galvanised pipe at the same nominal diameter, and rougher again where it is left compressed, sagging or coiled between supports, so the same figure on this page does not deliver the same air in every material.
- Nothing checks the velocity you entered against a noise limit. The number is taken as a design choice, and whether the run will be audible in the room depends on the fittings, the register and how close the duct passes to occupied space — none of which this calculation sees.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- Standard duct sizing formula: cross-sectional area (sq ft) = CFM / velocity (ft/min); round duct diameter = sqrt(4 x area / pi)
- Common design velocity for residential supply ducts is roughly 700-900 ft/min; return ducts are often designed slightly lower

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**How do I convert this to a rectangular duct size?**

Use a duct equivalent-diameter conversion chart or calculator to find a rectangular duct (e.g. for tight spaces above a ceiling) with the same effective cross-sectional airflow capacity as this round diameter.

**Why does velocity choice matter beyond just fitting the duct?**

Higher velocities let you use smaller, cheaper ducts but increase both noise and static pressure (which taxes the blower motor) — main trunk lines and long branch runs are often designed toward the lower end of the velocity range for this reason.

**Does this replace a Manual D duct design?**

No — this estimates one duct run's size from velocity alone. A full residential duct system design (ACCA Manual D) also balances total system static pressure, fitting losses, and blower capability across all runs together.

## Related calculators

- [CFM Ventilation Calculator](https://craftquantities.com/calculators/plumbing-hvac/cfm-ventilation-calculator/)
- [BTU Cooling / AC Sizing Calculator](https://craftquantities.com/calculators/plumbing-hvac/btu-cooling-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/hvac-duct-cfm-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/hvac-duct-cfm-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `hvac-duct-cfm-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/hvac-duct-cfm-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/hvac-duct-cfm-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.