# Heating Circuit Flow Rate Calculator (Heat Output, ΔT and Pipe Velocity)

> The water flow a radiator, circuit or heating system needs to carry its heat at a design temperature drop, and its velocity in the pipe feeding it.

Page: https://craftquantities.com/calculators/plumbing-hvac/heating-circuit-flow-rate-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-09-22, 3 published test vectors.

Design flow rate: 1.89 gal/min for Heat Output to Carry 34121.42 BTU/hr, Design Temperature Drop 36 °F and Internal Bore of the Pipe 0.5 in, the page's opening figures; on the metric page, 10 kW, 20 °C and 13.6 mm give 7.17 L/min. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Heat Output to Carry | `heatOutput` | 10 kW | 34121.4 BTU/hr | w, kw, btuh, ton_r; range 100–10000000 W |
| Design Temperature Drop (Flow to Return) | `deltaT` | 20 °C | 36 °F | c_delta, f_delta; range 1–60 °C |
| Internal Bore of the Pipe | `bore` | 13.6 mm | 0.5 in | mm, cm, m, in, ft, yd; range 0.005–0.5 m |

- **Heat Output to Carry**: The emitter's output at the design water temperature, or the whole circuit's load.
- **Design Temperature Drop (Flow to Return)**: The difference between flow and return water temperatures the system is designed for.
- **Internal Bore of the Pipe**: The inside diameter of the pipe carrying this flow, not its nominal size.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Design flow rate** | 7.17 L/min |
| The same flow in litres per second | 0.12 L/s |
| Water velocity in the pipe | 0.82 m/s |
| Mass of water per second | 0.12 kg/s |

### US customary

| Result | Value |
|---|---|
| **Design flow rate** | 1.89 gal/min |
| Water velocity in the pipe | 3.09 ft/s |
| Mass of water per second | 0.26 lb/s |

## How it is worked out

Flow = heat ÷ (the specific heat of water × the temperature drop). Halve the drop and the flow doubles; a quarter of it, as a heat pump runs, is four times the water through the same emitter and the same pipe.

The working the page shows, in order: The same flow in litres per second; Water velocity in the pipe; Mass of water per second; then design flow rate.

The method, derived in full:

- [Sensible Heat and Flow](https://craftquantities.com/methodology/sensible-heat-and-flow/): The single equation behind water heater sizing, duct heating and every temperature-rise problem on the site.

What this calculation does not cover:

- Water is taken at a kilogram a litre — 8.34 lb a US gallon. Hot water is slightly lighter — about 2 per cent at 70 °C (158 °F) — so the volume flow at working temperature is that much higher than shown.
- Glycol mixtures carry less heat per degree than water and are more viscous; a system with antifreeze needs the fluid maker's specific heat and a larger flow.
- The velocity is reported, not judged. Noise, erosion and the pump's duty set the limits for a given pipe, and the pressure loss that comes with the velocity is a separate calculation.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-22):

- Heat carried by water: Q = ṁ × c × ΔT, so the flow is the heat output ÷ (4.186 kJ/kg·K × the design temperature drop), with a litre of water taken as a kilogram
- CIBSE Guide C, Reference data — the properties of water; BS EN 12828, Heating systems in buildings — Design for water-based heating systems
- Velocity in the pipe = the volume flow ÷ the bore's cross-sectional area, π × d² ÷ 4

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does a heat pump need so much more water?**

Because the flow is the heat divided by the temperature drop, and a heat pump is designed on a drop around a quarter of a boiler's. Four times the water through the same emitter and pipe means much higher velocity and, with friction rising with roughly the square of the flow, far more pressure loss — which is why heat pump retrofits often need pipework, not just radiators.

**Where does 4.186 come from?**

It is the specific heat of water, 4.186 kilojoules to warm a kilogram by one kelvin. In US units the same fact is one BTU per pound per degree Fahrenheit, which is why the US rule of thumb is gpm = BTU/hr ÷ (500 × ΔT°F).

**What flow should each radiator get when balancing?**

Its own output divided by the specific heat and the design drop — which is this calculation run for each emitter. Write the figures on a schedule before touching a valve; balancing to a target flow is the only way to know it is done.

## Related calculators

- [Radiator Output at Lower Flow Temperature (ΔT Correction) Calculator](https://craftquantities.com/calculators/plumbing-hvac/radiator-output-delta-t-calculator/)
- [Hydronic Circulator Pump Head Loss Calculator](https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/)
- [Hydronic Closed-Loop Expansion Tank Sizing Calculator](https://craftquantities.com/calculators/materials-quantities/hydronic-expansion-tank-calculator/)
- [Hydronic Air/Dirt Separator Sizing Calculator](https://craftquantities.com/calculators/materials-quantities/air-dirt-separator-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/heating-circuit-flow-rate-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/heating-circuit-flow-rate-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `heating-circuit-flow-rate-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/heating-circuit-flow-rate-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/heating-circuit-flow-rate-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.