# Heat Pump Sizing Calculator

> Size a heat pump to a known heat loss, and find the balance point where supplementary heat starts to be needed.

Page: https://craftquantities.com/calculators/plumbing-hvac/heat-pump-sizing-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-03, 4 published test vectors.

Capacity required at design temperature: 8 kW at design for Design heat loss 27297.13 BTU/hr and Design outdoor temperature 26.6 °F, the page's opening figures; on the metric page, 8 kW and -3 °C give 8 kW at design. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Design heat loss | `designHeatLossKw` | 8 kW | 27297.1 BTU/hr | w, kw, btuh, ton_r; range 500–200000 W |
| Design outdoor temperature | `designOutdoorC` | -3 °C | 26.6 °F | c, f, k; range -40–20 °C |
| Rated capacity at 7 °C | `ratedCapacityKw` | 8 kW | 27297.1 BTU/hr | w, kw, btuh, ton_r; range 500–200000 W |
| Capacity loss per °C below rating point (%) | `capacityDeratePerDegree` | 2 | 2 | range 0–6 |

- **Design heat loss**: Whole-house heat loss at the design outdoor temperature.
- **Design outdoor temperature**: The external design condition for your location.
- **Rated capacity at 7 °C**: The heat pump's nameplate output at the standard rating point.
- **Capacity loss per °C below rating point (%)**: How fast output falls as it gets colder, per °C.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Capacity required at design temperature** | 8 kW at design |
| Nameplate capacity at 7 °C | 8 kW |
| Capacity at the design temperature | 6.4 kW |
| Shortfall needing supplementary heat | 1.6 kW |
| Balance point | 0 °C |
| Capacity retained at design | 80 % |

### US customary

| Result | Value |
|---|---|
| **Capacity required at design temperature** | 8 kW at design |
| Nameplate capacity at 7 °C | 8 kW |
| Capacity at the design temperature | 6.4 kW |
| Shortfall needing supplementary heat | 1.6 kW |
| Balance point | 32 °F |
| Capacity retained at design | 80 % |

- Confidence: medium.

## How it is worked out

The derate is a linear planning approximation. Use the manufacturer's published capacity table for the actual machine before committing.

The working the page shows, in order: Nameplate capacity at 7 °C; Capacity at the design temperature; Shortfall needing supplementary heat; Balance point; Capacity retained at design; then capacity required at design temperature.

The method, derived in full:

- [Sealed Circuits: Expansion, Makeup Water and Refrigerant Lines](https://craftquantities.com/methodology/hydronic-and-refrigerant-circuits/): Why an expansion vessel is two to three times bigger than the water it has to absorb, why makeup water is a fault report rather than a consumable, and why a refrigerant line that is too large starves its own compressor of oil.

What this calculation does not cover:

- Capacity derate is linear here; real machines follow a curve that varies with refrigerant, compressor type and defrost behaviour.
- Defrost cycles reduce delivered output in damp near-freezing conditions and are not modelled.
- Says nothing about whether the emitters — radiators or underfloor — can deliver the heat at the lower flow temperature a heat pump uses. That is usually the harder problem in a retrofit.

## Sources

As the calculator cites them (sources checked 2026-09-03):

- Heat pump capacity falls with outdoor temperature; manufacturers publish capacity tables at 47/17/5 °F (8/−8/−15 °C)
- ACCA Manual S — equipment selection against the calculated load, including balance-point analysis for heat pumps
- MCS 3005 (UK) requires sizing to the calculated design heat loss rather than to the existing boiler output

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why can I not size a heat pump like a boiler?**

Because a boiler's output does not change with the weather and a heat pump's does. A 24 kW boiler delivers 24 kW at −10 °C; an 8 kW heat pump delivers perhaps 5.5 kW there. Sizing from the old boiler also inherits its oversizing — boilers were routinely fitted at two or three times the actual heat loss, and copying that produces a heat pump that costs far more than it needs to and cycles badly.

**What is the balance point?**

The outdoor temperature at which the heat pump's falling capacity exactly meets the building's rising demand. Above it the heat pump covers everything; below it something else has to make up the difference. A balance point near the design temperature means very little supplementary running; one well above it means the immersion or backup heater carries a large share of the season.

**Is supplementary heat a failure?**

No, it is a design choice. Sizing for the coldest hour of the year leaves a machine badly oversized for the other 99%, cycling and running inefficiently. Accepting a few dozen hours of backup is usually cheaper both to install and to run. What matters is knowing how many hours, which is what the balance point tells you.

**Will my existing radiators work?**

Often not without change, and this calculator does not answer it. A heat pump runs at 35-50 °C flow against a boiler's 70-80 °C, and a radiator's output falls sharply at lower flow temperature — frequently to half. Emitter sizing is usually the binding constraint in a retrofit, and it is a room-by-room question.

## Related calculators

- [Heating & Cooling Load Screening Calculator](https://craftquantities.com/calculators/plumbing-hvac/manual-j-screening-calculator/)
- [Room Heat Loss and Radiator Size Calculator (Watts and BTU)](https://craftquantities.com/calculators/plumbing-hvac/room-heat-loss-calculator/)
- [Boiler Makeup Water Calculator](https://craftquantities.com/calculators/materials-quantities/boiler-makeup-water-calculator/)
- [Mini-Split/VRF Line Set Length Derating Calculator](https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/)
- [Air Conditioner Size Calculator](https://craftquantities.com/calculators/plumbing-hvac/ac-size-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/heat-pump-sizing-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/heat-pump-sizing-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `heat-pump-sizing-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/heat-pump-sizing-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/heat-pump-sizing-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.