# Feet of Head to PSI Calculator

> Convert a vertical water column in feet into pressure in psi, for pump selection and system pressure checks.

Page: https://craftquantities.com/calculators/plumbing-hvac/feet-of-head-to-psi-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 4 published test vectors.

Static pressure: 43.4 psi for Head 100, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Head (ft) | `feetOfHead` | 100 | 100 | range 0–2000 |

- **Head (ft)**: The vertical height of the water column, in feet.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Static pressure** | 43.4 psi |
| Head entered | 30.48 m |
| Pressure | 298.91 kPa |
| Metric equivalent | 298.91 kPa |
| Bar | 2.99 bar |

### US customary

| Result | Value |
|---|---|
| **Static pressure** | 43.4 psi |
| Head entered | 100 ft |
| Pressure | 43.35 psi |
| Metric equivalent | 43.35 psi |
| Bar | 2.99 bar |

## How it is worked out

1 ft of water at 4 °C = 62.428 lb/ft³ ÷ 144 in²/ft² ≈ 0.4335 psi. Equivalently, 2.31 ft per psi. Assumes clean water at 4 °C. For any other fluid, multiply by its specific gravity.

The working the page shows, in order: Head entered; Pressure; Metric equivalent; Bar; then static pressure.

The method, derived in full:

- [Unit Conversion, Exactness and Rounding](https://craftquantities.com/methodology/unit-conversion-and-rounding/): Why most conversion factors carry no uncertainty at all, which ones hide a material assumption, and why converting a measurement can never make it more precise than it was.

What this calculation does not cover:

- This is static head only. Friction loss through pipe, fittings, valves and the meter, and the residual pressure a fixture, shower or sprinkler head needs to work, are all excluded. Total dynamic head is static head plus those two, and sizing a pump on this figure alone is how a system ends up short at the top outlet.
- The factor assumes clean water at 4 °C and the result does not scale for any other fluid. Glycol, brine, fuel oil and hot circulating water all differ in density, so multiply by specific gravity yourself — a strong glycol charge reads low here, hot heating water reads high.
- It describes a column at rest. Velocity head, a pump running near shut-off, thermal expansion in a closed circuit and water hammer on valve closure can all push real system pressure well above this figure, and it is the peak, not the static value, that splits a fitting or lifts a relief valve.
- Only the water column's own pressure is counted. Fill pressure in a sealed heating circuit, an expansion vessel's charge, a booster set's outlet pressure or gas pressure above the water in a closed tank all add on top of this number and none of them are in it.
- This is not a pressure rating check and not a pump selection. It says nothing about the pressure class of the pipe, fittings, cylinder or appliance at the bottom of the lift, and nothing about NPSH available at a pump suction — cavitation is governed by suction conditions, not by the discharge head being converted here.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- Water density 62.428 lb/ft³ at 4 °C — NIST/CRC standard reference
- Hydrostatic pressure p = ρgh; 1 psi ≈ 2.31 ft of water column

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why 2.31 feet per psi and not 2.3?**

2.31 comes from water at 4 °C, where it is densest. The rounder 2.3 is a jobsite shorthand. Over a 300 ft lift the difference is about 2 psi — immaterial for a domestic pump, and worth carrying properly on a tall building or a long rising main.

**Does the pipe diameter change the pressure?**

Not the static pressure. A column of water exerts pressure by its height alone, so a 1 in pipe and a 12 in pipe at the same height read the same. Diameter matters for flow and friction loss, which is a separate and often larger part of the pump's duty.

**What about a liquid that is not water?**

Scale by specific gravity. Glycol at 1.04 gives 4% more pressure per foot; diesel at about 0.85 gives 15% less. This calculator assumes water — using it for a heating system with a strong glycol charge will under-read.

**Is this the pressure my pump needs to produce?**

It is one part of it. Total dynamic head is static head plus friction loss through pipe, fittings and valves, plus any pressure required at the outlet. Sizing on static head alone is a common way to end up with a pump that will not deliver at the top of the building.

## Related calculators

- [PSI to Feet of Head Calculator](https://craftquantities.com/calculators/measurements-conversions/psi-to-feet-of-head-calculator/)
- [Hydronic Circulator Pump Head Loss Calculator](https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/)
- [Domestic Water Pipe Friction Loss Calculator (Hazen-Williams)](https://craftquantities.com/calculators/materials-quantities/hazen-williams-friction-loss-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/feet-of-head-to-psi-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/feet-of-head-to-psi-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `feet-of-head-to-psi-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/feet-of-head-to-psi-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/feet-of-head-to-psi-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.