# Dehumidifier Water Removal Calculator

> The water held in a room's air between its current and target humidity, in gallons or litres, and the pull-down time at your unit's real extraction rate.

Page: https://craftquantities.com/calculators/plumbing-hvac/dehumidifier-pulldown-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 3 published test vectors.

Water to remove from the air: 0.0666 gal for Floor area 430 sq ft, Ceiling height 8 ft and Room temperature 68 °F, the page's opening figures; on the metric page, 40 m², 2.5 m and 20 °C give 0.259 L. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Floor area | `area` | 40 m² | 430 sq ft | m2, ft2, mm2, in2; range 0.01–2000 m² |
| Ceiling height | `height` | 2.5 m | 8 ft | mm, cm, m, in, ft, yd; range 0.01–10 m |
| Room temperature | `temp` | 20 °C | 68 °F | c, f, k; range 5–35 °C |
| Current relative humidity (%) | `rhStart` | 70 | 70 | range 20–100 |
| Target relative humidity (%) | `rhTarget` | 55 | 55 | range 20–90 |
| Dehumidifier rated capacity (L/day) | `ratedCapacity` | 20 | 20 | range 0.5–100 |
| Real-conditions extraction (% of rated) | `deratePercent` | 70 | 70 | range 10–100 |

- **Floor area**: The floor area of the space being dried.
- **Ceiling height**: Average ceiling height — area × height is the air volume that holds the water.
- **Room temperature**: Air temperature in the space. Warmer air holds more water at the same relative humidity.
- **Current relative humidity (%)**: What the hygrometer reads now, in %.
- **Target relative humidity (%)**: Where you want to hold the space — 50–55% is the usual comfort and mould-control band.
- **Dehumidifier rated capacity (L/day)**: The litres-per-day figure on the unit's plate or box.
- **Real-conditions extraction (% of rated)**: How much of the rated capacity your room's conditions actually deliver.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Water to remove from the air** | 0.259 L |
| Room air volume | 100 m³ |
| Water in the air now | 1.21 L |
| Water in the air at the target | 0.95 L |
| Pull-down time at derated capacity | 0.44 hours |
| Effective extraction rate | 14 L/day |

### US customary

| Result | Value |
|---|---|
| **Water to remove from the air** | 0.0666 gal |
| Room air volume | 127.41 yd³ |
| Water in the air now | 0.31 gal |
| Water in the air at the target | 0.24 gal |
| Pull-down time at derated capacity | 0.43 hours |
| Effective extraction rate | 3.7 gal/day |

- Confidence: medium.

## How it is worked out

This is the water in the AIR alone. Wet walls, wet contents and the continuous load from infiltration and occupants add far more over a day than the air itself holds — the pull-down being quick does not mean the job is small.

The working the page shows, in order: Room air volume; Water in the air now; Water in the air at the target; Pull-down time at derated capacity; Effective extraction rate; then water to remove from the air.

The method, derived in full:

- [Airtightness, Infiltration and Moisture](https://craftquantities.com/methodology/airtightness-and-infiltration/): Why a blower-door result is not an air change rate, why a leak at the top of a house matters far more than the same leak halfway up, and why sealing without ventilating moves the problem rather than solving it.

What this calculation does not cover:

- Only the water suspended in the air is counted. Moisture soaked into plaster, timber, screed, carpet and stored contents is excluded, and so is the continuous load — air leaking in from outside, ground moisture through a slab or crawlspace, showers, cooking and occupants. That continuous load, not the air's own water content, is what fills the tank day after day and what sizes the machine.
- This is not a drying-out calculation. Reaching the target room humidity does not mean a wet subfloor, wall cavity or plaster is dry; only a moisture meter in the material tells you that, and water still held in the fabric will push the room back up as soon as the unit stops.
- The pull-down time assumes a closed space with nothing adding moisture while the unit runs and a single extraction rate held constant throughout. It does not model infiltration during the run, doors opening, extraction falling as the room dries and cools, coil defrost cycles, or the unit's own humidistat cutting out short of the target.
- One temperature and one humidity are applied to the whole volume. Real spaces stratify — cold corners, outside walls, the space behind furniture and under a floor sit colder and wetter than the meter in the middle of the room, and reach the target long after it does.
- Not a condensation or mould-risk assessment. Mould grows at the surface humidity against a cold wall, window reveal or uninsulated slab, which can stay high while the room air sits comfortably at 55%. Judging that needs the surface temperature and a dew-point check, not a room average.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- Magnus saturation-vapour-pressure approximation, e_s = 6.112·exp(17.62·T/(243.12+T)) hPa — WMO-recommended coefficients
- Vapour mass from the ideal gas law on the vapour's own partial pressure, m = e·V/(R_v·T), with R_v = 461.5 J/(kg·K) — so no fixed air density enters and the figure stays exact across the whole temperature range
- Humidity ratio W = 0.622·e/(P−e) at standard sea-level pressure — psychrometric relations per ASHRAE Handbook — Fundamentals
- Rated dehumidifier capacity is defined at a standard test condition; the US DOE test procedure (10 CFR 430) moved from 80°F/60% RH to 65°F/60% RH, roughly halving printed ratings for the same hardware — the unit's own documentation governs its real extraction

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is the amount of water so small? My dehumidifier fills its tank daily.**

Because the air itself holds surprisingly little — a whole living room's air carries a few hundred millilitres between 70% and 55%. What fills the tank day after day is the CONTINUOUS load: outside air leaking in, cooking, showers, people breathing, and moisture evaporating out of walls and contents. The pull-down is the sprint; holding the target is the job.

**Why does the same unit print different capacities in different markets?**

The test chambers differ. The older US test ran at 80°F/60% RH, the current DOE test at 65°F/60% — roughly halving the printed number for identical hardware — and European ratings usually quote 30°C/80%, the most generous condition of all. Compare units only within one standard.

**What should I enter for real-conditions extraction?**

Your unit's own capacity table, if it publishes one, at your room's temperature and humidity. Extraction falls as the room gets cooler and drier than the test chamber; refrigerant units in cool basements can drop under half their rating, which is why desiccant units are often preferred below about 15°C. The 70% default is a placeholder, not a measurement.

**Does lowering the temperature help dry the room?**

It does the opposite for a refrigerant dehumidifier — cooler air gives the coil less to condense, and extraction falls. If anything, gentle heat plus dehumidification dries a space faster than either alone.

## Related calculators

- [Vapor Barrier Dew-Point Condensation Risk Calculator](https://craftquantities.com/calculators/materials-quantities/vapor-barrier-dewpoint-calculator/)
- [ERV/HRV Sizing Calculator](https://craftquantities.com/calculators/insulation-efficiency/erv-hrv-sizing-calculator/)
- [CFM Ventilation Calculator](https://craftquantities.com/calculators/plumbing-hvac/cfm-ventilation-calculator/)
- [Crawlspace Encapsulation Liner Calculator](https://craftquantities.com/calculators/materials-quantities/crawlspace-liner-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/dehumidifier-pulldown-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/dehumidifier-pulldown-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `dehumidifier-pulldown-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/dehumidifier-pulldown-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/dehumidifier-pulldown-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.