# BTU/hr to kW Calculator

> Convert a US BTU per hour rating into kilowatts for sizing metric equipment and electrical supply.

Page: https://craftquantities.com/calculators/plumbing-hvac/btu-to-kw-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Equivalent output: 3.52 kW for Rated output 12000, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Rated output (BTU/hr) | `btuPerHour` | 12000 | 12000 | range 0–2000000 |

- **Rated output (BTU/hr)**: The rated output in BTU per hour, as printed on a US nameplate.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Equivalent output** | 3.52 kW |
| Conversion factor applied | 0 kW per BTU/hr |

### US customary

| Result | Value |
|---|---|
| **Equivalent output** | 3.52 kW |
| Conversion factor applied | 0 kW per BTU/hr |

## How it is worked out

Converted using an exact defined factor of 0.00029307107017222003 kW per BTU/hr. This is thermal output, not electrical consumption — do not size a circuit from it.

The working the page shows, in order: Conversion factor applied; then equivalent output.

The method, derived in full:

- [Unit Conversion, Exactness and Rounding](https://craftquantities.com/methodology/unit-conversion-and-rounding/): Why most conversion factors carry no uncertainty at all, which ones hide a material assumption, and why converting a measurement can never make it more precise than it was.

What this calculation does not cover:

- The kilowatt figure is heat moved or produced, not electricity drawn. This is not an electrical load calculation and it gives you no minimum circuit ampacity, breaker size or conductor rating — take those from the unit's stated running current and its MCA and maximum overcurrent protection figures.
- US gas appliance nameplates commonly carry both an input firing rate and an output capacity, both stated in BTU/h. The conversion cannot tell which one you entered, so converting an input rating and treating the kilowatts as delivered heat overstates the output by whatever the appliance's efficiency is.
- The arithmetic is exact; the rating you feed it is not. Nominal tonnage and catalogue BTU/h figures are rounded sales sizes, and any capacity rating only holds at the conditions it was tested at — heat pump and air conditioner output both move with outdoor temperature. Nothing here derates the figure to your design condition.
- On cooling equipment the BTU/h rating covers total capacity, sensible plus latent. Converting it gives a total in kilowatts and says nothing about how much is available to drop air temperature rather than remove moisture, which is what governs performance in a humid space.
- This converts a number, it does not size anything. There is no heat loss or heat gain calculation behind it, no check that the capacity suits the building, and no check that the emitters, ductwork or pipework can actually deliver it.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- 1 BTU/h = 0.29307107017222 W (International Table BTU), so 1000 BTU/h = 0.293071 kW

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Can I size the electrical supply from this kW figure?**

Only for direct resistive heating, where input and output are effectively the same. For a heat pump or air conditioner the converted figure is heat moved, not electricity consumed, and the running current on the nameplate is typically a third of it or less. For a gas appliance the electrical demand is only the fan and controls. Always size the circuit from the stated running current.

**My unit is quoted in tons. How does that relate?**

One ton of refrigeration is 12,000 BTU/hr, which is 3.517 kW. The term comes from the rate of cooling produced by melting one short ton of ice in 24 hours. Tonnage is always nominal, so a nameplate 'three ton' unit may test anywhere in a band around 36,000 BTU/hr.

**Does this work for heating output as well as cooling?**

Yes — BTU per hour is a rate of energy transfer and the conversion is direction-agnostic. Bear in mind that many units carry different heating and cooling ratings, and that heat pump output falls as outdoor temperature drops, so use the rating for the design condition rather than the headline figure.

## Related calculators

- [kW to BTU/hr Calculator](https://craftquantities.com/calculators/plumbing-hvac/kw-to-btu-calculator/)
- [BTU/hr to Watts Calculator](https://craftquantities.com/calculators/measurements-conversions/btu-to-watts-calculator/)
- [kW to Horsepower Calculator](https://craftquantities.com/calculators/measurements-conversions/kw-to-hp-calculator/)
- [Refrigeration Tons, BTU/h and kW Converter](https://craftquantities.com/calculators/plumbing-hvac/tons-btu-kw-conversion-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/btu-to-kw-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/btu-to-kw-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `btu-to-kw-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/btu-to-kw-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/btu-to-kw-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.