# Bathroom Extract Fan Rate and Duct Resistance Calculator

> The extract rate a wet room needs, and the equivalent duct length that decides whether the fan you bought will actually deliver it.

Page: https://craftquantities.com/calculators/plumbing-hvac/bathroom-extract-rate-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-09-24, 3 published test vectors.

Extract rate required: 69.3 CFM for Room floor area 65 sq ft and Ceiling height 8 ft, the page's opening figures; on the metric page, 6 m² and 2.4 m give 32 L/s. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Room floor area | `floorArea` | 6 m² | 65 sq ft | m2, ft2, mm2, in2; range 1–60 m² |
| Ceiling height | `ceilingHeight` | 2.4 m | 8 ft | mm, cm, m, in, ft, yd; range 1.8–5 m |
| Air changes per hour | `airChanges` | 8 | 8 | range 1–30 |
| Straight duct run | `ductLength` | 3 m | 10 ft | mm, cm, m, in, ft, yd; range 0–30 m |
| Bends in the run | `bends` | 2 | 2 | range 0–12 |
| Duct type | `ductType` | Flexible (corrugated) | Flexible (corrugated) | `flexible`, `rigid` |

- **Room floor area**: The wet room's own floor, not the landing outside it.
- **Ceiling height**: Floor to ceiling, for the volume.
- **Air changes per hour**: How many times the room's whole volume is replaced each hour.
- **Straight duct run**: Measured along the duct, not across the room.
- **Bends in the run**: Every change of direction, including the one at the terminal.
- **Duct type**: Corrugated flexible costs far more per bend than rigid.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Extract rate required** | 32 L/s |
| Room volume | 14.4 m³ |
| Flow per hour | 115.2 m³/h |
| Equivalent duct length | 8 m |
| Each bend is worth | 2.5 m of duct |

### US customary

| Result | Value |
|---|---|
| **Extract rate required** | 69.3 CFM |
| Room volume | 520 ft³ |
| Equivalent duct length | 26.4 ft |
| Each bend is worth | 8.2 ft of duct |

- Confidence: medium.

## How it is worked out

63% of the run's resistance is the bends rather than the straight duct. Read the required flow against the fan's curve at that equivalent length, not against the figure on the box.

The working the page shows, in order: Room volume; Flow per hour; Equivalent duct length; Each bend is worth; then extract rate required.

The method, derived in full:

- [Ventilation: Net Free Area, Air Change and the Openings That Deliver Them](https://craftquantities.com/methodology/ventilation-openings-and-air-change/): Why a wooden louvre delivers a quarter of the hole you cut and a metal one three-quarters, why intake and exhaust have to be balanced or the roof ventilates the house, and why doubling the pressure does not double the flow.

What this calculation does not cover:

- THIS IS THE REQUIREMENT, NOT WHAT YOUR FAN WILL DELIVER. A fan's quoted flow is measured in free air with no duct attached. What it moves through the run described here depends on that fan's own pressure curve, which is a property of the fan and cannot be derived from anything on this page — so the page gives you the two numbers to read against the curve and deliberately invents no third one.
- The equivalent length prices the fittings, not the terminal. A louvred grille, an insect mesh or a backdraught shutter each add resistance of their own, and a mesh that has been in a coastal wall for five years adds a great deal more than a new one.
- Air has to get IN. An extract rate is only achievable if the same volume can enter — under the door, through a trickle vent, from the landing. A fan cannot move what cannot be replaced, so a well-sealed room with a tight door is one where the fan works against itself, and no duct calculation sees that.
- Nothing here covers the fan's noise, its run-on timer, humidity sensing, or whether the terminal position satisfies the separation distances a code asks for. A duct discharging under a soffit vent is putting the moisture back into the roof.
- An air change rate and a flat volume-per-second figure are different specifications, and codes use both. Where yours sets a flat figure, that figure governs; this page then tells you what air change rate it amounts to in your room.

## Sources

As the calculator cites them (sources checked 2026-09-24):

- Required extract flow is the room volume multiplied by the target air changes per hour, divided by 3.6 to convert cubic metres per hour into litres per second
- A fan's quoted flow is measured at zero static pressure — free air, with no duct attached — so it is an upper bound rather than a delivered rate, and the difference on a real run is substantial
- Duct fittings are costed as an equivalent length of the same straight duct; a bend in corrugated flexible duct is worth considerably more than the same bend in rigid, because the inner wall compresses as it turns

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does my new extractor not clear the mirror?**

Because the number on the box was measured with no duct attached. A fan is rated in free air at zero static pressure, and the moment you connect four metres of flexible duct and two bends it is working against a resistance the test never saw. Corrugated flexible duct is the usual culprit: its wall is rough along every straight metre and its bends compress on the inside. Swapping the same fan onto rigid duct with fewer turns often fixes a fan that seemed underpowered, because nothing was wrong with the fan.

**How many air changes does a bathroom need?**

Domestic guidance commonly sits between 8 and 15 an hour, with the higher end where there is a shower rather than only a bath — a shower puts far more moisture into the air in far less time. Some codes set a flat litres-per-second figure instead, and where yours does, that number governs and this page becomes a cross-check: it tells you what air change rate that flat figure amounts to in your particular room, which is often a surprise in a large bathroom.

**What is an equivalent length and why does it matter?**

It is the trick that makes a duct run comparable: a fitting is expressed as the length of straight duct that would cost the same in resistance. A 90-degree bend in rigid duct is worth about a metre; the same bend in corrugated flexible is worth considerably more, because the inner wall crushes as it turns. Add those to the straight run and you have one number to read against a fan's pressure curve. It is why a three-metre run with four bends can be harder work than a ten-metre straight one.

**Does the air have to get in from somewhere?**

Yes, and it is the most-missed half of ventilation. A fan cannot extract a litre that cannot be replaced, so a well-sealed room with a close-fitting door and no trickle vent is a room where the fan works against itself and the measured flow collapses. The usual provision is an undercut at the door or a vent in it. No duct calculation anywhere will show you this — the duct is fine, the fan is fine, and the room is simply not letting anything in.

## Related calculators

- [CFM Ventilation Calculator](https://craftquantities.com/calculators/plumbing-hvac/cfm-ventilation-calculator/)
- [HVAC Duct Fitting Equivalent Length Calculator](https://craftquantities.com/calculators/materials-quantities/duct-fitting-equivalent-length-calculator/)
- [Rectangular-to-Round Equivalent Duct Diameter Calculator](https://craftquantities.com/calculators/materials-quantities/equivalent-round-duct-diameter-calculator/)
- [Wet Room Tanking and Waterproof Membrane Calculator](https://craftquantities.com/calculators/materials-quantities/wet-room-tanking-calculator/)
- [Range Hood and Cooker Hood Airflow Calculator (CFM, L/s and Make-Up Air)](https://craftquantities.com/calculators/plumbing-hvac/range-hood-airflow-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/bathroom-extract-rate-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/bathroom-extract-rate-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `bathroom-extract-rate-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/bathroom-extract-rate-calculator.json

---
Source: https://craftquantities.com/calculators/plumbing-hvac/bathroom-extract-rate-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.