# ACI 347 Wall Formwork Rate-of-Placement Pressure Calculator

> Calculate the maximum lateral pressure on wall formwork from ordinary (non-SCC) concrete, using the ACI 347R rate-of-placement formula.

Page: https://craftquantities.com/calculators/materials-quantities/wall-formwork-pressure-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.2.2, sources checked 2026-10-31, 2 published test vectors.

Maximum lateral formwork pressure: 970 psf for Concrete Unit Weight 150 pcf, Concrete Temperature 70 °F and Total Wall Pour Height 10 ft, the page's opening figures; on the metric page, 2402.77 kg/m³, 21.1 °C and 3 m give 46.5 kPa. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Concrete Unit Weight | `freshDensity` | 2402.77 kg/m³ | 150 pcf | kgm3, pcf, lbyd3; range 1602–3204 kg/m³ |
| Rate of Placement R (ft/hr, Vertical Rise at This Form Location, Max 15) | `pourRate` | 5 | 5 | range 1–15 |
| Concrete Temperature | `concreteTemperature` | 21.1 °C | 70 °F | c, f, k; range 4–38 °C |
| Cement/Admixture Coefficient Cc (1.0 = Ordinary Cement No Retarder; 1.2 = With Retarder OR High Slag/Fly-Ash No Retarder; 1.4 = High Slag/Fly-Ash WITH Retarder) | `cementCoefficient` | 1.0 — Ordinary Cement, No Retarder | 1.0 — Ordinary Cement, No Retarder | `1.0`, `1.2`, `1.4` |
| Total Wall Pour Height | `wallHeight` | 3 m | 10 ft | mm, cm, m, in, ft, yd; range 0.01–16 m |

- **Concrete Unit Weight**: The fresh concrete's unit weight.
- **Rate of Placement R (ft/hr, Vertical Rise at This Form Location, Max 15)**: How fast the concrete surface rises at this form location, in feet per hour.
- **Concrete Temperature**: The temperature of the fresh concrete at placement, in °F.
- **Cement/Admixture Coefficient Cc (1.0 = Ordinary Cement No Retarder; 1.2 = With Retarder OR High Slag/Fly-Ash No Retarder; 1.4 = High Slag/Fly-Ash WITH Retarder)**: ACI 347R Table 2.2 chemistry coefficient for the cement/admixture combination used.
- **Total Wall Pour Height**: The total vertical height of the wall being poured.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Maximum lateral formwork pressure** | 46.5 kPa |
| Unit weight coefficient Cw | 1 (dimensionless) |
| Full hydrostatic ceiling | 70.69 kPa |

### US customary

| Result | Value |
|---|---|
| **Maximum lateral formwork pressure** | 970 psf |
| Unit weight coefficient Cw | 1 (dimensionless) |
| Full hydrostatic ceiling | 1,500 psf |

- Confidence: medium.

## How it is worked out

Wall pressure is rate-limited rather than height-limited. Because a wall is filled over a long period, the concrete at the base normally stiffens before the top arrives, and the pressure envelope caps out well below full hydrostatic.

The working the page shows, in order: Unit weight coefficient Cw; Full hydrostatic ceiling; then maximum lateral formwork pressure.

The method, derived in full:

- [Formwork Pressure](https://craftquantities.com/methodology/formwork-pressure/): Why a column form sees full hydrostatic pressure and a wall form usually does not, and why temperature belongs in the equation.

What this calculation does not cover:

- The rate-based reduction depends on the concrete stiffening as expected. Retarders, cold weather and high cement replacement all delay that and raise the pressure.
- Excludes wind load on the form face, which on a tall free-standing wall form can govern the bracing even though it does not affect the ties.
- Does not address the uplift and lateral load at a construction joint, or the loads from the placing equipment resting on or against the form.

## Sources

As the calculator cites them (sources checked 2026-10-31):

- ACI 347R-14(21) Guide to Formwork for Concrete, Section 2.2.2, Eq. 2.4 (used across its full 0-15 ft/hr rate range as a single conservative envelope formula, since Eq. 2.3 and 2.4 are continuous and equal at R=7 ft/hr and Eq. 2.4 is always ≥ Eq. 2.3 below that): Pmax = Cw×Cc×\[150 + 43400/T + 2800R/T\] psf, with a floor of 600×Cw psf and a ceiling of full hydrostatic pressure (w×h). Cw (unit weight coefficient, Table 2.1) = 1.0 for 140-150 pcf concrete. Cc (chemistry coefficient, Table 2.2) = 1.0 for ordinary Type I/II/III cement with no retarder, rising to 1.2-1.4 for retarders or high slag/fly-ash content. This formula ONLY applies when slump ≤ 7 in, placement uses normal internal vibration to a depth ≤4ft, and R≤15 ft/hr — this is DISTINCT from this site's existing SCC formwork pressure calculator, which correctly uses full hydrostatic pressure (ACI 347R Eq. 2.1a) for self-consolidating concrete, since SCC and high-slump/retarded mixes fall outside this reduced formula's applicability and ACI 347R itself directs using full hydrostatic pressure for those cases.

The site's pages for the documents these name:

- [ACI 347R](https://craftquantities.com/standards/aci/aci-347r/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is wall pressure lower than the full height of concrete suggests?**

Because not all of it is still fluid. By the time the top of a wall is being placed, the concrete at the bottom has begun to set and is carrying its own weight rather than pushing outward. The pressure envelope rises with depth to a point and then stops — that point depends on how fast you are filling and how fast the mix stiffens.

**What happens if the pour is faster than planned?**

The pressure rises toward hydrostatic, and formwork designed for a slower rate can be overloaded. It is a genuine site risk rather than a theoretical one — a pour that is going well is tempting to accelerate, and the formwork design assumed a rate that nobody on the pour necessarily knows. The design rate belongs on the pour card.

**Does temperature really matter that much?**

It does. Concrete stiffens far more slowly at 5 °C than at 25 °C, so a winter pour keeps more of its height fluid and generates higher pressure at the same rate. Pressure formulas include temperature explicitly for this reason, and a summer design used unchanged in winter is not conservative.

**Do ties and bracing resist the same thing?**

No, and conflating them is a common error. Ties resist the concrete's lateral pressure pushing the two faces apart. Bracing resists everything else — wind on the face, the pour crew, placing equipment, and any accidental impact — and it keeps the form plumb and stable before and during the pour. A form can be adequately tied and still be blown over.

## Related calculators

- [SCC Formwork Lateral Pressure Calculator](https://craftquantities.com/calculators/materials-quantities/scc-formwork-pressure-calculator/)
- [ACI 347 Column Formwork Pressure Calculator](https://craftquantities.com/calculators/materials-quantities/column-formwork-pressure-calculator/)
- [Concrete Formwork Tie Spacing Calculator](https://craftquantities.com/calculators/materials-quantities/formwork-tie-spacing-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/wall-formwork-pressure-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/wall-formwork-pressure-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `wall-formwork-pressure-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/wall-formwork-pressure-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/wall-formwork-pressure-calculator/