# VAV Terminal Reheat Coil Sensible Heat Capacity Calculator

> Calculate the sensible heating capacity a VAV terminal's reheat coil must provide for a given airflow and target temperature rise.

Page: https://craftquantities.com/calculators/materials-quantities/vav-reheat-coil-capacity-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.2, sources checked 2026-10-31, 2 published test vectors.

Required reheat coil sensible capacity: 25,900 BTU/hr for Airflow 600 CFM and Target Temperature Rise ΔT 40 °F, the page's opening figures; on the metric page, 283.17 L/s and 22.22 °C give 7.6 kW. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Airflow | `airflow` | 283.168 L/s | 600 CFM | lps, m3h, lpm, cfm; range 23.5974–2359.74 L/s |
| Target Temperature Rise ΔT | `reheatRise` | 22.22 °C | 40 °F | c_delta, f_delta; range 3–45 °C |

- **Airflow**: The VAV terminal's airflow rate at the reheat condition.
- **Target Temperature Rise ΔT**: The desired air temperature increase across the reheat coil, from entering to leaving air.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Required reheat coil sensible capacity** | 7.6 kW |

### US customary

| Result | Value |
|---|---|
| **Required reheat coil sensible capacity** | 25,900 BTU/hr |

- Confidence: medium.

## How it is worked out

This is a simplified sensible-heat sizing check using the standard-air 1.08 factor — it is not a substitute for full manufacturer coil selection, which also accounts for entering water/electric element temperature, coil rows, fin spacing, and actual air density (the 1.08 factor itself shifts at high altitude).

The method, derived in full:

- [Sensible Heat and Flow](https://craftquantities.com/methodology/sensible-heat-and-flow/): The single equation behind water heater sizing, duct heating and every temperature-rise problem on the site.

What this calculation does not cover:

- The temperature rise is not a free choice, and nothing here stops you entering one the room cannot use. Air leaving a ceiling diffuser much more than about 15 °F (8 °C) above room temperature stops mixing and stratifies at the ceiling — ASHRAE 62.1 penalizes a zone's air distribution effectiveness for exactly that condition. A large rise on a small minimum airflow therefore buys a capacity that heats the plenum while the occupied zone stays cold, and the remedy is more airflow, not more rise.
- Nothing here sizes what feeds the coil. The same duty is either an electric element pulling a breaker and a feeder off a panel, or a hot-water coil demanding a flow rate through a control valve — and across a floor of thirty terminals the summed electrical demand, or the pump flow and pipe size to serve them, is a design quantity in its own right that a per-box capacity never adds up.

## Sources

As the calculator cites them (sources checked 2026-10-31):

- Q(Btu/hr) = 1.08 x CFM x deltaT, the standard ASHRAE sensible heat formula for air at standard conditions (60 min/hr x 0.075 lb/ft³ standard air density x 0.24 Btu/(lb\*F) specific heat of air is approximately 1.08). This is a simplified sizing/balance check; full VAV reheat coil selection also accounts for entering water temperature, coil rows, fin spacing, and actual air density at altitude.

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Where does the 1.08 factor come from?**

It combines standard air properties: 60 minutes per hour x 0.075 lb/ft³ standard air density x 0.24 Btu/(lb\*F) specific heat of air, which multiplies out to approximately 1.08 — the standard ASHRAE sensible heat formula for air at standard conditions.

**What airflow should I use for a VAV reheat calculation?**

Use the terminal's airflow rate at the reheat condition — typically its minimum (heating) airflow setpoint, since reheat is usually staged in at reduced airflow to avoid overcooling the space.

**Is this enough to select an actual reheat coil?**

No — this is a simplified sensible-heat sizing check using the standard-air 1.08 factor. Full manufacturer coil selection also accounts for entering water or electric element temperature, coil rows, fin spacing, and actual air density, which shifts the 1.08 factor itself at high altitude.

## Related calculators

- [HVAC Thermal Load (U-Value) Calculator](https://craftquantities.com/calculators/plumbing-hvac/hvac-thermal-load-calculator/)
- [HVAC Duct Size Calculator](https://craftquantities.com/calculators/plumbing-hvac/hvac-duct-cfm-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/vav-reheat-coil-capacity-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/vav-reheat-coil-capacity-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `vav-reheat-coil-capacity-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/vav-reheat-coil-capacity-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/vav-reheat-coil-capacity-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.