# Mass Timber Char Depth & Residual Section Calculator

> What a fire period takes off an exposed timber member, notional char plus the zero-strength layer, and the residual section and sanding margin it leaves.

Page: https://craftquantities.com/calculators/materials-quantities/timber-char-depth-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-08-30, 2 published test vectors.

Residual section dimension: 5.69 in for Required Fire-Resistance Period 60, the page's opening figures; on the metric page, 60 gives 142 mm. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Required Fire-Resistance Period (minutes) | `fireResistancePeriod` | 60 | 60 | range 15–240 |
| Notional Charring Rate (mm/min) | `charringRate` | 0.7 | 0.7 | range 0.4–1.2 |
| Zero-Strength Layer Allowance | `zeroStrengthLayer` | 7 mm | 0.25 in | mm, cm, m, in, ft, yd; range 0–0.02 m |
| Original Section Dimension | `memberDimension` | 240 mm | 9.5 in | mm, cm, m, in, ft, yd; range 0.05–1.2 m |
| Faces Exposed Across This Dimension | `exposedFaces` | Two faces — the width of a beam, or a four-sided column | Two faces — the width of a beam, or a four-sided column | `1`, `2` |
| Minimum Residual Dimension Required | `requiredResidualDimension` | 120 mm | 4.75 in | mm, cm, m, in, ft, yd; range 0.01–1.2 m |

- **Required Fire-Resistance Period (minutes)**: The period the element has to survive under the standard fire, as consented.
- **Notional Charring Rate (mm/min)**: The notional rate tabulated for this product and density in the standard you are designing to.
- **Zero-Strength Layer Allowance**: Depth of heat-damaged timber just inside the char line that the reduced cross-section method discounts.
- **Original Section Dimension**: The width, depth or panel thickness being checked, before any fire loss.
- **Faces Exposed Across This Dimension**: How many opposite faces of this particular dimension the fire can reach.
- **Minimum Residual Dimension Required**: The smallest residual the engineer's fire check still passes at — from the design, not from this page.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Residual section dimension** | 142 mm |
| Notional char depth | 42 mm |
| Effective loss per exposed face | 49 mm |
| Surface removable before the residual reaches the required minimum | 22 mm |
| Proportion of the original dimension surviving | 59.17 % |

### US customary

| Result | Value |
|---|---|
| **Residual section dimension** | 5.69 in |
| Notional char depth | 1.65 in |
| Effective loss per exposed face | 1.9 in |
| Surface removable before the residual reaches the required minimum | 0.94 in |
| Proportion of the original dimension surviving | 59.93 % |

- Confidence: medium.

## How it is worked out

The headroom shown is the total that may come off this face across the life of the building, not per visit. Record what is removed at each remedial pass, because two light sandings a year apart are indistinguishable from one heavy one by the time it matters.

The working the page shows, in order: Notional char depth; Effective loss per exposed face; Surface removable before the residual reaches the required minimum; Proportion of the original dimension surviving; then residual section dimension.

The method, derived in full:

- [Timber: Load Duration, Notching, Char and Panel Action](https://craftquantities.com/methodology/timber-behaviour-and-member-checks/): Why the same joist is stronger against a wind gust than against a bookcase, why a notch is limited by geometry rather than by stress, and why a heavy timber beam can outlast an unprotected steel one in a fire.

What this calculation does not cover:

- One dimension at a time. A three-sided beam needs two runs — width at two faces, depth at one — and the residual capacity check uses both results together.
- Notional charring assumes the member keeps its shape and no layer falls away; products where a lamella can debond char faster and are covered by different provisions in the standards.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-08-30):

- EN 1995-1-2 (Eurocode 5, Part 1-2: Structural fire design) reduced cross-section method: char depth is the product's notional charring rate times the fire-resistance period, with a zero-strength layer deducted in addition. Both the rate and the layer are entered here from the standard governing your design — this page publishes neither
- The National Design Specification for Wood Construction, Chapter 16, gives the equivalent char provisions used in US practice; its charring model and its allowance differ from the Eurocode one, so take both figures from a single document rather than mixing the two
- Sanding removes material from the same surface the char depth is measured inward from, so any thickness taken off comes straight out of the residual section — the arithmetic on this page is that subtraction and nothing more

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is a zero-strength layer deducted on top of the char?**

Because the char line is not a clean boundary between ash and sound timber. Just inside it sits a band of wood hot enough to have lost most of its stiffness and strength without having burned, and the reduced cross-section method deals with that by discounting a further defined thickness. Ignoring it overstates the surviving section by roughly the same amount on every exposed face.

**Can I sand a water stain out of an exposed soffit?**

Only if the residual section has headroom over what the fire check needs, and that is a question for the engineer rather than the finisher. The sacrificial thickness is doing structural work in a fire; material removed from the visible face is subtracted from the residual section as surely as the char is, and a light finishing pass is a different proposition from sanding out a deep mark.

**Do the Eurocode and the NDS give the same answer?**

No, and they are not meant to be interchangeable. They model charring differently, tabulate different rates, and handle the heat-affected zone in different ways, so a rate lifted from one and an allowance lifted from the other produce a number that belongs to neither. Work from a single document throughout.

## Related calculators

- [CLT Floor Panel Grid Layer Calculator](https://craftquantities.com/calculators/materials-quantities/clt-floor-panel-calculator/)
- [Glulam Beam Deflection Checker](https://craftquantities.com/calculators/materials-quantities/glulam-beam-deflection-calculator/)
- [Timber Beam Bending Stress Calculator](https://craftquantities.com/calculators/materials-quantities/timber-beam-bending-stress-calculator/)
- [Multi-Layer Fire-Rated (Type X) Gypsum Sheet Calculator](https://craftquantities.com/calculators/materials-quantities/fire-rated-gypsum-layer-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/timber-char-depth-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/timber-char-depth-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `timber-char-depth-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/timber-char-depth-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/timber-char-depth-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.