# Shaftwall C-H Stud Limiting Height Calculator

> How high a C-H shaftwall stud runs unsupported at a given spacing and pressure before its deflection limit, and the share of it a proposed height uses.

Page: https://craftquantities.com/calculators/materials-quantities/shaftwall-limiting-height-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-08-30, 3 published test vectors.

Maximum unsupported height: 18.9 ft for Design Transverse Pressure 5.22 psf and Stud Spacing 24 in, the page's opening figures; on the metric page, 250 Pa and 609.6 mm give 5.77 m. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Design Transverse Pressure | `designPressure` | 250 Pa | 5.22136 psf | pa, kpa, mpa, psi, psf, in_wc; range 50–2500 Pa |
| Stud Spacing | `studSpacing` | 609.6 mm | 24 in | mm, cm, m, in, ft, yd; range 0.2–1.25 m |
| Effective Moment of Inertia I_eff (×10⁶ mm⁴) | `momentOfInertia` | 0.45 | 0.45 | range 0.05–5 |
| Permitted Deflection Ratio | `deflectionRatio` | L/240 | L/240 | `120`, `180`, `240`, `360` |
| Proposed Unsupported Height | `proposedHeight` | 4 m | 13 ft | mm, cm, m, in, ft, yd; range 1–15 m |

- **Design Transverse Pressure**: The lateral pressure the shaft enclosure is designed to resist.
- **Stud Spacing**: Centre-to-centre spacing of the C-H studs along the wall.
- **Effective Moment of Inertia I_eff (×10⁶ mm⁴)**: The stud's effective moment of inertia, from the manufacturer's table.
- **Permitted Deflection Ratio**: The deflection limit the specification applies to this wall.
- **Proposed Unsupported Height**: The floor-to-floor height you want to run this stud through.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Maximum unsupported height** | 5.77 m |
| Line load carried by one stud | 152.4 N/m |
| Deflection at the proposed height | 5.55 mm |
| Allowable deflection at the proposed height | 16.67 mm |
| Deflection allowance used at that height | 33.3 % |

### US customary

| Result | Value |
|---|---|
| **Maximum unsupported height** | 18.9 ft |
| Line load carried by one stud | 10.44 lbf/ft |
| Deflection at the proposed height | 0.21 in |
| Allowable deflection at the proposed height | 0.65 in |
| Deflection allowance used at that height | 32.37 % |

- Confidence: medium.

## How it is worked out

The proposed height uses 33% of the deflection allowance. This is the deflection-governed limit only — the manufacturer's tabulated limiting height is the lesser of this and a bending strength check, and for heavier gauges and higher pressures it is often strength that governs.

The working the page shows, in order: Line load carried by one stud; Deflection at the proposed height; Allowable deflection at the proposed height; Deflection allowance used at that height; then maximum unsupported height.

The method, derived in full:

- [Slenderness, Effective Length and the Ratio That Decides Buckling](https://craftquantities.com/methodology/slenderness-and-buckling/): Why the ends of a column matter more than its material, why a flat arch thrusts so much harder than a deep one, and why height-to-thickness rules exist at all.

What this calculation does not cover:

- Deflection only. Bending strength requires the effective section modulus and yield strength for the same stud, which are published alongside the moment of inertia and are not derivable from it.
- Treats the stud as a simply supported span between tracks. Slip track details, deflection heads and intermediate bracing all change the end conditions and the tabulated heights that go with them.
- The liner panel is not counted as contributing stiffness. Shaftwall liner is friction-fitted between the studs and is not composite with them, which is why manufacturers publish limiting heights against the stud alone.

## Sources

As the calculator cites them (sources checked 2026-08-30):

- ASTM C645 (non-structural steel framing members) and ASTM C754 (installation of steel framing to receive gypsum panel products), which is where the practice of selecting studs from a published limiting-height table originates
- AISI S100 takes the modulus of elasticity of cold-formed sheet steel as 29,500,000 psi (203,400 MPa); the effective moment of inertia for a given C-H stud depth and gauge comes from the system manufacturer's own limiting height table
- Deflection-governed limiting height from elastic beam theory for a uniformly loaded simple span: setting 5wL⁴/(384EI) equal to L divided by the deflection ratio gives L = cube root of 384EI/(5wR)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does the calculator ask for a moment of inertia instead of a stud depth and gauge?**

Because the stiffness of a cold-formed section is not a geometric property you can look up from its outside dimensions. Parts of a thin section buckle locally well before the member as a whole is in trouble, and the effective stiffness that remains depends on the stress level. Manufacturers publish the resulting figure per depth and per gauge, and reproducing those tables from a formula would be inventing them.

**My manufacturer's table gives a lower height than this. Which do I use?**

The manufacturer's, always. A tabulated limiting height is the lesser of a deflection check and a bending strength check, and it is tied to a tested assembly with a specific track, fastening pattern and liner. This page computes only the deflection half, so where it reads higher than the table, strength is governing and the table is telling you so.

**Does adding a second layer of board to the corridor face raise the limiting height?**

Not in the way the tables are written. The published heights are for the stud alone, because the board is not connected to the stud in a way that lets the two act as one member, and the liner panel is only friction-fitted between the C-H flanges. Extra board adds weight and fire resistance, not stiffness you may count on.

**What transverse pressure should a shaft be designed for?**

That is a project decision rather than a property of the wall. Lift shafts see piston effect from car movement, tall shafts see stack pressure that grows with building height, and a smoke control system imposes a pressure difference by design. The figure comes from the mechanical design or the specification, and a perimeter shaftwall must also be checked against wind.

## Related calculators

- [Shaftwall Stud Framework Calculator](https://craftquantities.com/calculators/materials-quantities/shaftwall-stud-framework-calculator/)
- [Fire-Rated Shaftwall Liner Panel Count Calculator](https://craftquantities.com/calculators/materials-quantities/shaftwall-liner-panel-calculator/)
- [Cold-Formed Steel (CFS) C-Stud Deflection Checker](https://craftquantities.com/calculators/materials-quantities/cfs-stud-deflection-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/shaftwall-limiting-height-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/shaftwall-limiting-height-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `shaftwall-limiting-height-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/shaftwall-limiting-height-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/shaftwall-limiting-height-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.