# Roof Uplift Zone Pressure and Zone Width Calculator

> Velocity pressure at roof height, the net uplift for the coefficient your code figure gives, and how far in from each edge the corner and edge zones reach.

Page: https://craftquantities.com/calculators/materials-quantities/roof-uplift-zone-pressure-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 3 published test vectors.

Design uplift pressure in the selected zone: 30.5 psf for Basic Wind Speed V 115, Roof Slope 5 and External Pressure Coefficient Magnitude |GCp| for the Zone Being Checked 1, the page's opening figures; on the metric page, 115, 5 and 1 give 1.46 kPa. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Basic Wind Speed V (mph, 3-second gust) | `basicWindSpeed` | 115 | 115 | range 85–200 |
| Exposure Category | `exposureCategory` | C — open terrain with scattered obstructions | C — open terrain with scattered obstructions | `B`, `C`, `D` |
| Mean Roof Height | `meanRoofHeight` | 6 m | 19.5 ft | mm, cm, m, in, ft, yd; range 3–18 m |
| Least Horizontal Building Dimension | `leastHorizontalDimension` | 12 m | 39 ft | mm, cm, m, in, ft, yd; range 3–120 m |
| Roof Slope (degrees from horizontal) | `roofSlope` | 5 | 5 | range 0–45 |
| External Pressure Coefficient Magnitude \|GCp\| for the Zone Being Checked | `pressureCoefficient` | 1 | 1 | range 0.3–5 |

- **Basic Wind Speed V (mph, 3-second gust)**: The mapped basic wind speed for the site, at the risk category of the building.
- **Exposure Category**: The terrain roughness upwind of the building, over the distances the code specifies.
- **Mean Roof Height**: Average of eave height and ridge height, measured from grade.
- **Least Horizontal Building Dimension**: The shorter of the building's two plan dimensions.
- **Roof Slope (degrees from horizontal)**: The pitch of the roof plane being checked, in degrees.
- **External Pressure Coefficient Magnitude |GCp| for the Zone Being Checked**: Read from the components-and-cladding figure in your adopted code, for this zone and effective area.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Design uplift pressure in the selected zone** | 1.46 kPa |
| Velocity pressure at mean roof height | 1.24 kPa |
| Velocity pressure exposure coefficient | 0.9 (Kz) |
| Internal pressure component included | 0.22 kPa |
| Corner and edge zone width, measured in from each roof edge | 1.2 m |
| Corner zone plan area at each corner | 1.44 m² |

### US customary

| Result | Value |
|---|---|
| **Design uplift pressure in the selected zone** | 30.5 psf |
| Velocity pressure at mean roof height | 25.82 psf |
| Velocity pressure exposure coefficient | 0.9 (Kz) |
| Internal pressure component included | 4.65 psf |
| Corner and edge zone width, measured in from each roof edge | 3.9 ft |
| Corner zone plan area at each corner | 15.21 sq ft |

- Confidence: medium.

## How it is worked out

The external pressure coefficient is the value you entered, not one this page supplies, so the answer is only as good as the figure you read off. This is a low-slope roof, so the low-slope coefficient figure applies and the corner zone wraps the full perimeter corner. The topographic factor is taken as 1.0, which is wrong on a hill, a ridge or an escarpment.

The working the page shows, in order: Velocity pressure at mean roof height; Velocity pressure exposure coefficient; Internal pressure component included; Corner and edge zone width, measured in from each roof edge; Corner zone plan area at each corner; then design uplift pressure in the selected zone.

The method, derived in full:

- [Snow, Uplift and the Roof's Load Path](https://craftquantities.com/methodology/roof-loads-and-the-load-path/): Why a warm sheltered roof carries more snow than an exposed cold one, why building next to an existing low roof can overload it without touching it, and why a collar tie and a rafter tie are not the same member.

What this calculation does not cover:

- Enclosed building assumed. A partially enclosed building carries a much larger internal pressure coefficient and a building with a large dominant opening larger still.
- Kzt = 1.0 assumed. Speed-up over a hill or an escarpment can raise the pressure by half again, and that is a separate calculation.
- Gives pressure, not fastener spacing. Turning pressure into a clip or fastener layout needs the tested assembly's own rated resistance and its safety factor.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- ASCE 7, Minimum Design Loads and Associated Criteria for Buildings and Other Structures, components and cladding provisions as adopted locally — velocity pressure q = 0.00256 × Kz × Kzt × Kd × V² in psf with V in mph, and net pressure p = q × (GCp − GCpi)
- ASCE 7 terrain exposure constants used for Kz = 2.01 × (z / zg)^(2/α), held constant below zmin: Exposure B α = 7.0, zg = 1200 ft, zmin = 30 ft; Exposure C α = 9.5, zg = 900 ft, zmin = 15 ft; Exposure D α = 11.5, zg = 700 ft, zmin = 7 ft
- ASCE 7 directionality factor Kd = 0.85 for components and cladding of a building, and internal pressure coefficient GCpi = ±0.18 for an enclosed building. Topographic factor Kzt and ground elevation factor Ke are both taken as 1.0 here — Ke = 1.0 is always permitted, Kzt = 1.0 is only correct away from a hill, ridge or escarpment
- Zone width a = the smaller of 0.1 × the least horizontal dimension and 0.4 × the mean roof height, but never less than 0.04 × the least horizontal dimension nor less than 3 ft
- THE EXTERNAL PRESSURE COEFFICIENT IS NOT SUPPLIED HERE. GCp depends on roof form, slope, zone and effective wind area, and it is read from the components-and-cladding figure in the code edition your jurisdiction has adopted. The default in that field is a starting point to be replaced with the value your own figure gives, and is not itself a published coefficient

The site's pages for the documents these name:

- [ASCE 7](https://craftquantities.com/standards/asce/asce-7/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does this calculator ask me for the pressure coefficient instead of looking it up?**

Because the coefficient lives in a figure — a set of curves against effective wind area, drawn separately for each roof form and slope band — and reproducing a figure from memory is how a calculator ends up quietly wrong. Everything around the coefficient is arithmetic this page can do exactly, so it does that and leaves the one value that must be read to be read.

**Where exactly do the zone boundaries fall on my roof?**

The zone width in the breakdown is measured in from every roof edge. That strip is the edge zone; where two strips meet at a corner, that square is the corner zone; everything inside is the field. On a 12 m by 20 m building at 6 m mean roof height the strip is about 1.2 m, so the corners are 1.2 m squares.

**Why is the internal pressure added rather than subtracted?**

Because uplift is worst when the roof is being sucked from above and pushed from below at the same time. An enclosed building can pressurise internally by 0.18 times the velocity pressure, and that pushes up on the underside of the deck while the external suction pulls on the top. Adding the magnitudes is the governing combination.

**Do the corner and edge zones really need different fastening?**

Yes, and it is the single commonest cause of metal roof failures. Corner suctions run two to three times the field value, so a fastener pattern that is generous in the field can be badly short 1.2 m in from the edge. Panels blow off from the corners inward, and the tear-off starts where the spacing stopped matching the pressure.

## Related calculators

- [Standing Seam Metal Roof Clip Count Calculator](https://craftquantities.com/calculators/materials-quantities/standing-seam-clip-count-calculator/)
- [Standing Seam Roof Thermal Movement Calculator](https://craftquantities.com/calculators/materials-quantities/standing-seam-thermal-movement-calculator/)
- [Temporary Fence Wind Load Overturning Ballast Calculator](https://craftquantities.com/calculators/materials-quantities/temp-fence-wind-ballast-calculator/)
- [Collar Tie Wind Uplift Tension Calculator](https://craftquantities.com/calculators/materials-quantities/collar-tie-uplift-tension-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/roof-uplift-zone-pressure-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/roof-uplift-zone-pressure-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `roof-uplift-zone-pressure-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/roof-uplift-zone-pressure-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/roof-uplift-zone-pressure-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.