# Ground-to-Roof Snow Load Calculator

> Convert ground snow load to flat-roof design snow load per ASCE 7.

Page: https://craftquantities.com/calculators/materials-quantities/roof-snow-load-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-02, 2 published test vectors.

Flat-roof design snow load: 21.9 psf for Ground Snow Load pg 31.33 psf, the page's opening figures; on the metric page, 1.5 kPa gives 1.05 kN/m². Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Ground Snow Load pg | `groundSnowLoad` | 1.5 kPa | 31.3282 psf | pa, kpa, mpa, psi, psf, in_wc; range 200–15000 Pa |
| Exposure Factor Ce | `exposureFactor` | 1 | 1 | range 0.7–1.3 |
| Thermal Factor Ct | `thermalFactor` | 1 | 1 | range 0.85–1.3 |
| Importance Factor Is | `importanceFactor` | 1 | 1 | range 0.8–1.2 |

- **Ground Snow Load pg**: The site's ground snow load, from your local building code's ground snow load map.
- **Exposure Factor Ce**: Accounts for wind exposure and terrain, which affects how much snow accumulates on the roof versus blows off.
- **Thermal Factor Ct**: Accounts for heat loss through the roof that can melt accumulated snow.
- **Importance Factor Is**: Based on the building's risk category, per ASCE 7.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Flat-roof design snow load** | 1.05 kN/m² |

### US customary

| Result | Value |
|---|---|
| **Flat-roof design snow load** | 21.9 psf |

## How it is worked out

The method, derived in full:

- [Snow, Uplift and the Roof's Load Path](https://craftquantities.com/methodology/roof-loads-and-the-load-path/): Why a warm sheltered roof carries more snow than an exposed cold one, why building next to an existing low roof can overload it without touching it, and why a collar tie and a rafter tie are not the same member.

What this calculation does not cover:

- The page returns pf from the equation alone, and ASCE 7 also sets a minimum roof snow load pm that governs instead on low-slope roofs: where the ground snow load is 20 psf (about 0.96 kPa) or less, pm is Is times pg, and above that it is 20 psf times Is. No floor is applied here, so the page's default pg of 1.5 kPa with an exposure factor of 0.9 returns 0.945 kPa, which is 19.7 psf and already below that 20 psf minimum.
- This is the balanced load spread evenly over the whole roof. Drift against a parapet, a roof step or a rooftop unit is a separate ASCE 7 calculation that puts a triangular surcharge over a limited width and can reach several times pf, so a rafter or beam sized on this figure can still be badly under-designed where the snow actually piles up. Sliding snow off an upper roof, and the rain-on-snow surcharge of about 5 psf (0.24 kPa) that applies to low-slope roofs where the ground snow load is 20 psf or less, are added on top of pf rather than contained in it.
- pf is a pressure on the horizontal projection of the roof, not on the sloped surface. Applying it to the true roof area counts the pitch twice: at 6:12 the sloped surface is 11.8 per cent larger than the plan area, so the snow total comes out that much high. Dead loads run the other way and do act on the sloped area, which is why the two are never taken over the same area.
- Ce, Ct and Is are multiplied exactly as typed and are never checked against the tables they come from. Entering Ce as 0.7 rather than 1.0 removes 30 per cent of the load on the strength of a wind exposure that has to hold for the life of the building, and conifers grow, a taller neighbour goes up, a screen wall gets added. The field also accepts Ce up to 1.3, beyond the 1.2 top of the ASCE 7 exposure table that its own help text describes, without objecting.
- The form used here, with a separate importance factor, is the pre-2022 one. ASCE 7-22 rebuilt the snow chapter around reliability-targeted ground snow loads mapped for each risk category and dropped Is from the flat-roof equation, so a pg read off those newer maps and then multiplied by Is of 1.2 applies the risk category twice and overstates pf by 20 per cent. Which edition your jurisdiction has adopted decides which of the two pg values belongs in the box.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- ASCE 7 flat-roof snow load: pf = 0.7 × Ce × Ct × Is × pg, where Ce is exposure factor, Ct is thermal factor, Is is importance factor, and pg is ground snow load

The site's pages for the documents these name:

- [ASCE 7](https://craftquantities.com/standards/asce/asce-7/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What do Ce, Ct, and Is represent?**

The ASCE 7 exposure, thermal and importance factors: Ce for wind exposure and terrain, Ct for heat loss through the roof, and Is for the building's risk category. Wind exposure and terrain affect snow drifting off the roof, and heat loss through the roof melts snow.

**Why does the formula start with a 0.7 factor?**

ASCE 7 applies a 0.7 base factor to the ground snow load as a general reduction, reflecting that flat roofs typically retain somewhat less snow than open ground, before the exposure, thermal, and importance factors are layered on.

**Is this the final design snow load for my roof?**

This calculates the base flat-roof snow load (pf) only — sloped-roof reduction factors, unbalanced or drift loading, and rain-on-snow surcharge (also part of ASCE 7) are separate checks not included here.

## Related calculators

- [Wood Load Duration Factor (CD) Adjustment Calculator](https://craftquantities.com/calculators/materials-quantities/wood-load-duration-factor-calculator/)
- [Collar Tie Wind Uplift Tension Calculator](https://craftquantities.com/calculators/materials-quantities/collar-tie-uplift-tension-calculator/)
- [Snow Weight Calculator — What the Snow on a Roof Weighs](https://craftquantities.com/calculators/materials-quantities/snow-weight-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/roof-snow-load-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/roof-snow-load-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `roof-snow-load-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/roof-snow-load-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/roof-snow-load-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.