# Backflow Preventer Relief Valve Discharge Calculator

> Calculate the discharge flow rate from a reduced-pressure backflow preventer's relief valve, for air gap/drain sizing.

Page: https://craftquantities.com/calculators/materials-quantities/relief-valve-discharge-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Relief valve discharge flow: 36.8 gal/min for Relief Valve Orifice Area 0.78 in², the page's opening figures; on the metric page, 500 mm² gives 138 L/min. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Relief Valve Orifice Area | `orificeArea` | 500 mm² | 0.775002 in² | m2, ft2, mm2, in2; range 0.00005–0.003 m² |
| Discharge Coefficient (Typically ~0.6 for a Sharp-Edged Orifice) | `dischargeCoefficient` | 0.6 | 0.6 | range 0.4–0.8 |
| Available Pressure Head | `head` | 3 m | 10 ft | mm, cm, m, in, ft, yd; range 0.01–60 m |

- **Relief Valve Orifice Area**: The open cross-sectional area of the relief valve's discharge orifice.
- **Discharge Coefficient (Typically ~0.6 for a Sharp-Edged Orifice)**: An empirical factor accounting for orifice flow contraction and friction losses.
- **Available Pressure Head**: The pressure head driving flow through the relief valve orifice, expressed as a water column height.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Relief valve discharge flow** | 138 L/min |
| Discharge velocity | 4.6 m/s |

### US customary

| Result | Value |
|---|---|
| **Relief valve discharge flow** | 36.8 gal/min |
| Discharge velocity | 913.37 ft/min |

- Confidence: medium.

## How it is worked out

Confirm the actual relief valve orifice area and discharge coefficient from the specific backflow preventer manufacturer's data — this is a general orifice-flow estimate, not a substitute for the manufacturer's rated relief capacity.

The working the page shows, in order: Discharge velocity; then relief valve discharge flow.

The method, derived in full:

- [Head Loss, Falls and Surge: Resistance in Pipes, Ducts and Drains](https://craftquantities.com/methodology/head-loss-falls-and-surge/): Why one pipe size up cuts the friction to a third, why a compressed flex duct can cost four times its rated loss, why a drain can be too steep, and why a fast-closing valve produces a pressure the pump never could.

What this calculation does not cover:

- Takes the head as given and does not derive it. During a genuine relief event the driving head is the supply-side pressure at that instant, not a static column — a 70 psi (483 kPa) main is about 50 m (164 ft) of water, not the 3 m (10 ft) the field opens on — and because flow goes with the square root of head, an assumed head that low understates the discharge by roughly a factor of four.
- Says nothing about how the discharge is piped. Relief from a reduced-pressure assembly must reach the drain through an air gap and never a direct connection — hard-piping it into the waste system rebuilds the exact cross-connection the assembly was installed to prevent, and it also means a relief event pushes into the drain instead of showing itself on the floor where someone notices it.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Discharge flow = orifice area × discharge coefficient × √(2×g×head), the standard orifice discharge equation applied to a relief valve opening, used to size the air gap fitting or floor drain that must handle the preventer's full relief discharge

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does this matter for air gap or drain sizing?**

A reduced-pressure backflow preventer's relief valve can discharge its full rated flow instantaneously if the assembly senses a pressure fault. The air gap fitting or floor drain receiving that discharge must be able to handle this flow rate without flooding, so this figure is used to size that drainage path.

**How accurate is the 0.6 discharge coefficient?**

0.6 is a commonly used approximation for a sharp-edged orifice, but actual relief valve geometry varies by manufacturer and model. Confirm the manufacturer's actual orifice area and discharge coefficient (or a directly rated relief flow) rather than relying solely on this generic estimate.

**Is this the same as the backflow preventer's rated flow capacity?**

No — this estimates the relief valve's discharge flow during a relief event, which is a separate figure from the assembly's normal supply flow capacity. Always verify against the manufacturer's published relief discharge data for the specific model before final drain sizing.

## Related calculators

- [Backflow Preventer Discharge Velocity Calculator](https://craftquantities.com/calculators/materials-quantities/backflow-preventer-velocity-calculator/)
- [Closed-Loop Hydronic Water Hammer Surge Pressure Calculator](https://craftquantities.com/calculators/materials-quantities/water-hammer-surge-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/relief-valve-discharge-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/relief-valve-discharge-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `relief-valve-discharge-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/relief-valve-discharge-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/relief-valve-discharge-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.