# Timber Post Bearing Area Calculator

> Calculate the minimum bearing area required where a timber post bears on a beam, based on allowable perpendicular-to-grain stress.

Page: https://craftquantities.com/calculators/materials-quantities/post-bearing-area-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Required bearing area: 20.7 in² for Axial Load 8.99 kip and Allowable Bearing Stress Fc-perp 435.11 psi, the page's opening figures; on the metric page, 40 kN and 3 MPa give 133 cm². Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Axial Load | `axialLoad` | 40 kN | 8.99236 kip | n, kn, lbf, kip; range 2000–300000 N |
| Allowable Bearing Stress Fc-perp | `allowableBearingStress` | 3 MPa | 435.113 psi | pa, kpa, mpa, psi, psf, in_wc; range 1000000–8000000 Pa |

- **Axial Load**: The compressive axial load the post transfers into the beam below it.
- **Allowable Bearing Stress Fc-perp**: The species/grade's allowable compression stress perpendicular to grain, from the NDS design values.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Required bearing area** | 133 cm² |

### US customary

| Result | Value |
|---|---|
| **Required bearing area** | 20.7 in² |

## How it is worked out

The method, derived in full:

- [Bearing Capacity, and How a Load Spreads Into What Carries It](https://craftquantities.com/methodology/bearing-and-load-spread/): Why the allowable pressure under a footing is usually set by settlement rather than by strength, why a wider footing settles more at the same pressure, and why timber bearing is limited by the weakest direction of the grain.

What this calculation does not cover:

- The Fc-perp figure is used exactly as typed and no NDS adjustment factors are applied to it. The bearing area factor Cb, which raises the allowable value in the form (bearing length + 9.5 mm) divided by bearing length for bearings under about 150 mm long set back at least about 75 mm from the end of the member, is not credited, and the wet service and temperature reductions are not taken off either. Enter a value already adjusted for the edition and service conditions you are designing to.
- Tabulated Fc-perp is governed by a deformation limit of roughly 1 mm (0.04 in) of indentation in the standard test, not by fibre rupture. Meeting the required area therefore controls how far the joint beds down, and exceeding it produces progressive crushing and a settling floor rather than a sudden collapse. Creep is not modelled at all, and perpendicular-to-grain deformation under sustained load keeps growing well beyond the initial value.
- The output is a single area, not a bearing length, a plate size or a post section, and it assumes that whole area is loaded uniformly. Area cannot be won by spreading past the edge of the supporting member, and a thin plate that cantilevers beyond the post face does not deliver uniform stress unless it is stiff enough in bending, which is a separate check. An out-of-plumb, cupped or partially seated bearing contacts over only part of the face and sees a peak stress well above load divided by area.
- Only crushing of the supporting member at one interface is checked. The post's own capacity in compression parallel to grain with the column stability factor CP, the supporting beam's bending and shear under the concentrated load, uplift and lateral restraint at the connection, and the same bearing check repeated at every interface further down the load path are all outside what this page computes.
- Fc-perp from the NDS supplement is an allowable stress, so the axial load entered must be an unfactored service load combination; putting a factored LRFD load such as 1.2D + 1.6L (0.42 gal) against it oversizes the bearing by roughly the load factor. Fc-perp is also one of the few timber design values the load duration factor does not adjust, so a short-duration wind or seismic case does not justify a higher allowable stress here.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- Required bearing area = axial load ÷ allowable compression stress perpendicular to grain (Fc-perp), the standard NDS timber bearing check

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is perpendicular-to-grain stress the governing check here, not parallel-to-grain?**

Because where a post bears on top of a beam (or a beam bears on a sill plate), the load crosses the grain of the supporting member, and wood is significantly weaker in compression perpendicular to grain than parallel to grain. So Fc-perp of the supporting member typically governs the required bearing area.

**What if the actual post cross-section is smaller than the required bearing area?**

Then a bearing plate, larger post, or a cap block with a wider footprint is needed to spread the load over enough area to keep bearing stress within the allowable Fc-perp. Bearing directly with an undersized post can crush the fibers of the supporting member over time.

**Does the supporting member's species affect the allowable bearing stress?**

Yes — Fc-perp values vary by wood species and grade and are published in the NDS supplement design value tables; always use the actual allowable value for the specific supporting member's species and grade rather than a generic assumption.

## Related calculators

- [Timber Column Euler Buckling Calculator](https://craftquantities.com/calculators/materials-quantities/timber-column-buckling-calculator/)
- [I-Joist Web Stiffener Bearing Length Calculator](https://craftquantities.com/calculators/materials-quantities/i-joist-bearing-length-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/post-bearing-area-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/post-bearing-area-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `post-bearing-area-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/post-bearing-area-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/post-bearing-area-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.