# Three-Phase Electrical Panel Load Balancing Calculator

> Check the load imbalance percentage across a three-phase panel's phases A, B, and C.

Page: https://craftquantities.com/calculators/materials-quantities/panel-phase-balance-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Phase load imbalance: 9.76 % for Phase A Load 40, Phase B Load 45 and Phase C Load 38, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Phase A Load (A) | `phaseALoad` | 40 | 40 | range 0–500 |
| Phase B Load (A) | `phaseBLoad` | 45 | 45 | range 0–500 |
| Phase C Load (A) | `phaseCLoad` | 38 | 38 | range 0–500 |

- **Phase A Load (A)**: The measured or calculated current draw on Phase A.
- **Phase B Load (A)**: The measured or calculated current draw on Phase B.
- **Phase C Load (A)**: The measured or calculated current draw on Phase C.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Phase load imbalance** | 9.76 % |
| Average phase load | 41 A |

### US customary

| Result | Value |
|---|---|
| **Phase load imbalance** | 9.76 % |
| Average phase load | 41 A |

## How it is worked out

The working the page shows, in order: Average phase load; then phase load imbalance.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- Current imbalance is not voltage imbalance, and motors care about the second. A small unbalance in supply VOLTAGE produces a far larger unbalance in a motor's phase currents, commonly six to ten times as large, which is why NEMA MG-1 caps voltage unbalance at 1% before a motor must be derated and treats 2% as already costing winding life in extra heat. A panel whose feeders are evenly loaded can still be delivering out-of-balance voltage; that check is made with a meter across the phases, not from this arithmetic.
- One reading is one moment. Circuits are balanced against loads that come and go - a kitchen at midday, chargers overnight, a chiller in August - so a panel reading 5% during the survey can be at 20% eight hours later, and shuffling breakers to flatten one snapshot can make the daily peak worse. What matters is the balance at the time of maximum demand, which comes from a logged reading over days rather than a single clamp.
- Balanced phases do not empty the neutral. On a four-wire wye panel feeding electronic single-phase loads - LED drivers, switch-mode supplies, small drives - the third harmonic and its multiples arrive in phase on all three legs and ADD in the neutral instead of cancelling, so a perfectly balanced panel can run its neutral hotter than any phase conductor. Nothing protects the neutral against that, and nothing on this page will show it; it takes a true-RMS measurement of the neutral itself.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Phase imbalance percentage = (maximum deviation from average phase load ÷ average phase load) × 100, the standard method for checking how evenly a three-phase panel's circuits are distributed across its phases

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does phase balance matter on a three-phase panel?**

Because an unevenly loaded panel wastes capacity on the lightest phase while pushing the heaviest phase closer to its limit, and can cause uneven voltage drop and neutral current issues. Spreading circuits evenly across phases A, B, and C keeps the system operating efficiently and within its rated capacity.

**How is the imbalance percentage calculated?**

It's the maximum deviation of any single phase from the average of all three phase loads, divided by that average, expressed as a percentage — the standard method for checking how evenly circuits are distributed across phases.

**What's considered an acceptable imbalance?**

Common guidance targets keeping phase imbalance under roughly 5-10%, though the acceptable threshold can vary by equipment and application — check your specific equipment manufacturer's requirements and local code for any applicable limit.

## Related calculators

- [Electrical Circuit Load Calculator](https://craftquantities.com/calculators/electrical/electrical-load-calculator/)
- [Home Electrical Service Panel Amperage Sizing Calculator](https://craftquantities.com/calculators/materials-quantities/service-panel-sizing-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/panel-phase-balance-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/panel-phase-balance-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `panel-phase-balance-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/panel-phase-balance-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/panel-phase-balance-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.