# Structural Glazing Mullion Wind Load Deflection Calculator

> Check a window/curtain wall mullion's calculated wind-load deflection against the standard L/175 glazing deflection limit.

Page: https://craftquantities.com/calculators/materials-quantities/mullion-deflection-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.2.0, sources checked 2026-09-22, 3 published test vectors.

Calculated mullion deflection: 0.19 in for Wind Line Load on Mullion 102.78 lbf/ft, Mullion Span 10 ft and Modulus of Elasticity E 10152641.64 psi, the page's opening figures, to compare with the limit shown with it; a comparison, not a check. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Wind Line Load on Mullion | `lineLoad` | 1.5 kN/m | 102.783 lbf/ft | n_per_m, kn_per_m, lbf_per_ft, kip_per_ft; range 100–10000 N/m |
| Mullion Span | `span` | 3 m | 10 ft | mm, cm, m, in, ft, yd; range 0.01–8 m |
| Modulus of Elasticity E | `elasticModulus` | 70000 MPa | 10152600 psi | pa, kpa, mpa, psi, psf, in_wc; range 60000000000–210000000000 Pa |
| Moment of Inertia I (×10⁶ mm⁴) | `momentOfInertia` | 5 | 5 | range 0.1–100 |

- **Wind Line Load on Mullion**: The uniform wind load applied along the mullion's length, from the tributary area of glass it supports.
- **Mullion Span**: The unsupported span of the mullion between its structural supports.
- **Modulus of Elasticity E**: The mullion material's modulus of elasticity.
- **Moment of Inertia I (×10⁶ mm⁴)**: The mullion cross-section's moment of inertia about the axis resisting the wind load.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Calculated mullion deflection** | 4.52 mm |
| L/175 allowable limit | 17.14 mm |

### US customary

| Result | Value |
|---|---|
| **Calculated mullion deflection** | 0.19 in |
| L/175 allowable limit | 0.69 in |

- Confidence: medium.
- The figure is compared against a limit; that is a check of the number, not an approval.

## How it is worked out

The deflection this mullion works out to is below the L/175 limit shown with it — The AAMA convention this page applies gives it. Being under one limit is not a design. Nothing else is checked here — not the other limit states, not the connections, not the member the load arrives from.

The working the page shows, in order: L/175 allowable limit; then calculated mullion deflection.

The method, derived in full:

- [Glass, Insulating Units and the Curtain Wall](https://craftquantities.com/methodology/glazing-and-curtain-wall/): Why glass has no strength until you say how long the load lasts, why the edge of a sealed unit leaks more heat than the middle, and why a mullion's deflection limit protects the seal rather than the glass.

What this calculation does not cover:

- Passing L/175 is a serviceability check only and says nothing about strength. The bending stress at midspan, local buckling of the extrusion's thin walls, and the shear carried by screw splines and anchor fixings are separate checks that must pass independently, and a slender aluminium section can sit comfortably inside the deflection limit while over-stressing under the same wind load.
- The formula treats the mullion as a single simply-supported span carrying a uniform load, so it does not represent a member continuous over several floors, a stack joint with an expansion sleeve, a cantilevered head, or the rotation and slip of slotted anchor brackets at the slab edge. Anchor flexibility in particular adds end movement that 5wL⁴/(384EI) cannot see, so the real mullion can move further than the figure shown.
- Only the L/175 ratio is applied. Many specifications also cap framing deflection normal to the glass at an absolute figure, commonly 19 mm (3/4 in), with the smaller of the two governing; L/175 first exceeds 19 mm at a span of about 3.33 m, so beyond that span this page can report a pass that the absolute cap would refuse.
- The wind line load is taken as given and is not derived here. The tributary width of glass either side of the mullion must already be built into the line load, no allowance is made for the higher corner, edge or parapet components-and-cladding zones, and because deflection is a serviceability check the load should be the unfactored service wind pressure rather than the factored pressure used for the strength design.
- The moment of inertia is entered as a single published figure about the axis resisting wind, so a split or captured mullion pair only behaves as stiffly as a combined value implies when its two halves genuinely transfer shear between them. This field does not follow the unit selector, as the span, the wind line load and E do, so a section quoted in in⁴ must be multiplied by 0.416 to reach ×10⁶ mm⁴.

## Sources

As the calculator cites them (sources checked 2026-09-22):

- AAMA TIR-11 / ASTM E1300: mullion deflection under uniform wind load, treated as a simply-supported beam, Δ = 5wL⁴/(384EI); standard allowable deflection limit for mullions supporting glass is L/175 (for spans up to about 4.1m/13'-6"), keeping frame deflection small enough that the glass doesn't lose edge support or over-stress

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is the deflection limit L/175 instead of a fixed number?**

The allowable deflection scales with the span so that longer mullions are allowed proportionally more movement — L/175 keeps the deflection-to-span ratio consistent, which is what actually protects the glass from losing edge bearing or being over-stressed, per AAMA TIR-11.

**What happens if the mullion fails this deflection check?**

Excess mullion deflection can reduce the glass's edge bearing in its pocket, transfer unintended stress into the glass, or affect weatherseal performance. The fix is typically a deeper/stiffer mullion section (higher moment of inertia) or a shorter span (added intermediate support).

**Does this deflection limit apply to all mullion spans?**

The L/175 limit given here applies to spans up to about 4.1 m (13'-6"); longer spans may be governed by a different code-specified limit or project-specific criteria, so verify against your applicable code and project specification for spans beyond that range.

## Related calculators

- [Structural Silicone Glazing (SSG) Bite Width Calculator](https://craftquantities.com/calculators/materials-quantities/ssg-bite-width-calculator/)
- [Curtain Wall Mullion Tributary Dead Load Calculator](https://craftquantities.com/calculators/materials-quantities/curtain-wall-mullion-load-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/mullion-deflection-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/mullion-deflection-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `mullion-deflection-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/mullion-deflection-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/mullion-deflection-calculator/