# Three-Phase Motor Full-Load Amperage Calculator

> Estimate a three-phase motor's full-load current draw from its horsepower, voltage, and efficiency.

Page: https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Estimated full-load amperage: 11.7 A for Motor Horsepower 10, Voltage 480 and Motor Efficiency 90, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Motor Horsepower (HP) | `horsepower` | 10 | 10 | range 0.5–500 |
| Voltage (V, Line-to-Line) | `voltage` | 480 | 480 | range 120–690 |
| Motor Efficiency (%) | `efficiency` | 90 | 90 | range 50–98 |
| Power Factor | `powerFactor` | 0.85 | 0.85 | range 0.5–1 |

- **Motor Horsepower (HP)**: The motor's rated output horsepower.
- **Voltage (V, Line-to-Line)**: The three-phase line-to-line supply voltage.
- **Motor Efficiency (%)**: The motor's rated efficiency at full load.
- **Power Factor**: The motor's rated power factor at full load.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Estimated full-load amperage** | 11.7 A |

### US customary

| Result | Value |
|---|---|
| **Estimated full-load amperage** | 11.7 A |

- Confidence: medium.

## How it is worked out

This is a calculated estimate — for actual motor circuit conductor and overcurrent protection sizing, NEC 430.250 REQUIRES using the tabulated FLA values from NEC Table 430.250, not the motor nameplate current or a calculated value, per code.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- This is RUNNING current, not starting current. A motor started across the line draws locked-rotor current of roughly five to eight times FLA for the first seconds, fixed by the NEMA code letter on the nameplate, and that inrush is what sets the starter size, the breaker's instantaneous trip point, and how far the voltage dips on everything else in the panel when the motor kicks in. A generator, a soft start or a trip curve chosen from the number on this page will trip on every start.
- Efficiency and power factor are FULL-LOAD figures, and current does not fall in proportion to load. A motor running at half its rated horsepower still carries most of its magnetizing current, so its power factor collapses - 0.85 at full load can be 0.6 or worse at part load - and the measured amps sit well above half of what is computed here. An oversized motor is the usual reason a clamp reading and a calculated figure refuse to agree.
- Assumes rated voltage actually arrives at the motor terminals. On a long feeder the voltage at the motor is lower than the voltage at the panel, and a motor asked for the same torque at lower voltage answers by drawing MORE current, which heats the windings and shortens insulation life. Long runs have to be checked for voltage drop separately; this formula takes whatever voltage you type as arriving intact.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Standard three-phase motor FLA formula: FLA = (HP × 746) ÷ (√3 × voltage × efficiency × power factor), derived from the electrical power relationship P = √3 × V × I × PF applied to motor output power converted to input electrical power via efficiency

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**How is three-phase motor full-load amperage calculated?**

FLA = (HP × 746) ÷ (√3 × voltage × efficiency × power factor). This converts the motor's rated mechanical output power (horsepower, converted to watts) into the electrical input current drawn at the given line-to-line voltage, efficiency, and power factor.

**Can I use this calculated value to size conductors or breakers?**

No — this is a calculated estimate only. For actual motor circuit conductor and overcurrent protection sizing, NEC 430.250 REQUIRES using the tabulated FLA values from NEC Table 430.250, not the motor nameplate current or a calculated value, per code.

**Why do efficiency and power factor both appear in the formula?**

Because both are needed to relate the motor's rated horsepower output back to its actual electrical current draw. Efficiency accounts for losses converting electrical input power to mechanical output power, and power factor for the phase difference between voltage and current in an AC circuit.

## Related calculators

- [Single-Phase Motor Full-Load Current Calculator (Amps from hp or kW)](https://craftquantities.com/calculators/electrical/single-phase-motor-full-load-current-calculator/)
- [Electrical Circuit Load Calculator](https://craftquantities.com/calculators/electrical/electrical-load-calculator/)
- [Busbar Ampacity Calculator (Current Density Method)](https://craftquantities.com/calculators/materials-quantities/busbar-ampacity-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/motor-full-load-amps-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/motor-full-load-amps-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `motor-full-load-amps-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/motor-full-load-amps-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/