# Mixed Air (Economizer) Temperature Calculator

> Calculate the resulting mixed-air temperature when outdoor air and return air combine in an air handling unit.

Page: https://craftquantities.com/calculators/materials-quantities/mixed-air-temperature-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.2, sources checked 2026-10-31, 2 published test vectors.

Resulting mixed air temperature: 62.8 °F for Outdoor Air Flow 500 CFM, Outdoor Air Temperature 35 °F and Return Air Flow 1500 CFM, the page's opening figures; on the metric page, 235.97 L/s, 1.7 °C and 707.92 L/s give 17.1 °C. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Outdoor Air Flow | `outdoorAirCfm` | 235.974 L/s | 500 CFM | lps, m3h, lpm, cfm; range 0–4719.47 L/s |
| Outdoor Air Temperature | `outdoorTemp` | 1.7 °C | 35 °F | c, f, k; range -29–49 °C |
| Return Air Flow | `returnAirCfm` | 707.921 L/s | 1500 CFM | lps, m3h, lpm, cfm; range 0–9438.95 L/s |
| Return Air Temperature | `returnTemp` | 22.2 °C | 72 °F | c, f, k; range 4–32 °C |

- **Outdoor Air Flow**: The volume of outdoor air being introduced through the economizer/damper.
- **Outdoor Air Temperature**: The dry-bulb temperature of the incoming outdoor air.
- **Return Air Flow**: The volume of return air being recirculated from the conditioned space.
- **Return Air Temperature**: The dry-bulb temperature of the return air stream.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Resulting mixed air temperature** | 17.1 °C |
| Total combined airflow | 943.89 L/s |

### US customary

| Result | Value |
|---|---|
| **Resulting mixed air temperature** | 62.8 °F |
| Total combined airflow | 2,000 CFM |

## How it is worked out

The working the page shows, in order: Total combined airflow; then resulting mixed air temperature.

The method, derived in full:

- [Sensible Heat and Flow](https://craftquantities.com/methodology/sensible-heat-and-flow/): The single equation behind water heater sizing, duct heating and every temperature-rise problem on the site.

What this calculation does not cover:

- Returns the fully-mixed average, and a mixing box rarely mixes. Cold outdoor air crossing the damper does not blend with the return in the short distance before the coil — it arrives as a cold layer across part of the face, ten degrees or more below the average reported here — so a freeze stat trips on the coldest foot of its element and a hydronic coil bursts at its coldest tubes, not at the mean. Blenders, opposed-blade dampers and the geometry of the plenum are what close that gap, and none of them are inputs.

## Sources

As the calculator cites them (sources checked 2026-10-31):

- Mixed air temperature = (Outdoor Air CFM × Outdoor Air Temp + Return Air CFM × Return Air Temp) ÷ (Outdoor Air CFM + Return Air CFM), the standard air-stream mass-balance (weighted average) formula used in HVAC economizer and mixed-air control design.

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**How is mixed air temperature calculated?**

It's a CFM-weighted average of the two air streams: (Outdoor Air CFM × Outdoor Air Temp + Return Air CFM × Return Air Temp) ÷ (Outdoor Air CFM + Return Air CFM). This is the standard air-stream mass-balance formula used in HVAC economizer and mixed-air control design.

**Why does return air usually dominate the mixed air temperature?**

Because the result is CFM-weighted, whichever air stream has the larger airflow volume pulls the mixed temperature closer to its own temperature — a return air stream with more CFM than the outdoor air stream will have more influence on the final mixed temperature.

**What happens if both CFM values are zero?**

With no airflow in either stream there is nothing to mix, so this calculator returns 0°F for that edge case rather than dividing by zero.

## Related calculators

- [HVAC Thermal Load (U-Value) Calculator](https://craftquantities.com/calculators/plumbing-hvac/hvac-thermal-load-calculator/)
- [CFM Ventilation Calculator](https://craftquantities.com/calculators/plumbing-hvac/cfm-ventilation-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/mixed-air-temperature-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/mixed-air-temperature-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `mixed-air-temperature-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/mixed-air-temperature-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/mixed-air-temperature-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.