# Mini-Split/VRF Line Set Length Derating Calculator

> A mini-split or VRF system's derated capacity for line set length beyond the base allowance and for vertical rise, at the rates in the maker's manual.

Page: https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-06, 2 published test vectors.

Derated system capacity: 19,300 BTU/hr for Additional Horizontal Line Length Beyond Base Allowance 19.5 ft and Vertical Rise 10 ft, the page's opening figures; on the metric page, 6 m and 3 m give 5.65 kW. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Manufacturer's Rated Capacity | `ratedCapacity` | 7.03371 kW | 24000 BTU/hr | w, kw, btuh, ton_r; range 1758.43–17584.3 W |
| Additional Horizontal Line Length Beyond Base Allowance | `extraHorizontalLength` | 6 m | 19.5 ft | mm, cm, m, in, ft, yd; range 0–30 m |
| Manufacturer's Horizontal Derate Rate (% per ft) | `horizontalDerateRate` | 0.5 | 0.5 | range 0–3 |
| Vertical Rise | `verticalRise` | 3 m | 10 ft | mm, cm, m, in, ft, yd; range 0–15 m |
| Manufacturer's Vertical Derate Rate (% per ft) | `verticalDerateRate` | 1 | 1 | range 0–5 |

- **Manufacturer's Rated Capacity**: The system's nameplate cooling/heating capacity at the manufacturer's base (included) line length.
- **Additional Horizontal Line Length Beyond Base Allowance**: The horizontal refrigerant line run beyond the manufacturer's base length allowance.
- **Manufacturer's Horizontal Derate Rate (% per ft)**: The percentage of rated capacity lost per foot of horizontal line beyond the base allowance.
- **Vertical Rise**: The total vertical elevation change between indoor and outdoor units.
- **Manufacturer's Vertical Derate Rate (% per ft)**: The percentage of rated capacity lost per foot of vertical rise.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Derated system capacity** | 5.65 kW |
| Total capacity derate | 19.69 % |

### US customary

| Result | Value |
|---|---|
| **Derated system capacity** | 19,300 BTU/hr |
| Total capacity derate | 19.75 % |

- Confidence: medium.

## How it is worked out

The horizontal and vertical derate rates MUST come from the specific manufacturer's installation/engineering manual for your exact model — they vary significantly between manufacturers and are not standardized. This calculator only applies the rates you supply; it does not know or assume any specific product's actual derate schedule.

The working the page shows, in order: Total capacity derate; then derated system capacity.

The method, derived in full:

- [Sealed Circuits: Expansion, Makeup Water and Refrigerant Lines](https://craftquantities.com/methodology/hydronic-and-refrigerant-circuits/): Why an expansion vessel is two to three times bigger than the water it has to absorb, why makeup water is a fault report rather than a consumable, and why a refrigerant line that is too large starves its own compressor of oil.

What this calculation does not cover:

- A long line set needs more refrigerant, and that quantity is not computed here. Systems ship pre-charged to a stated line length, and past it charge is added at a published rate per unit of extra length — get that wrong and the capacity loss dwarfs the derate above, starving the evaporator when short and returning liquid to the compressor when long. The top-up is weighed in, not gauged in.
- A derate schedule has an end and this arithmetic does not. Manufacturers publish a maximum total line length and a maximum height difference, and beyond either the system is outside its listing no matter what percentage the rates would produce. Direction counts too: permitted lift is usually different with the outdoor unit above the indoor one than below it, and oil traps at intervals up a long riser belong to the same rule — the field above takes one rise with no sign on it.
- The nameplate being derated is a laboratory figure. Rated capacity is measured at standard test conditions, and on a design summer afternoon at a higher outdoor temperature — or in heating at a low one, where defrost cycles take their own share — the machine delivers less than its rating before line length is counted at all. Comparing a derated nameplate against a load computed at design conditions compares two numbers taken on different days.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Manufacturers of mini-split and VRF systems publish a base line length included at 100% rated capacity, then apply a percentage capacity derate per foot of additional horizontal run and per foot of vertical rise beyond that allowance — this calculator applies user-supplied derate rates (from the specific manufacturer's engineering/installation manual) rather than a universal constant, since these rates vary significantly by manufacturer and model.

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Where do the horizontal and vertical derate rates come from?**

They must come from the specific manufacturer's installation or engineering manual for the exact model being installed — these rates vary significantly between manufacturers and are not standardized. This calculator only applies whatever rates you supply; it doesn't assume any product's actual derate schedule.

**Why does vertical rise usually carry a steeper derate than horizontal length?**

Manufacturers publish separate horizontal and vertical derate rates because vertical rise adds oil-return and pressure-drop demands on the compressor beyond simple line friction, which is why the vertical rate is commonly higher than the horizontal rate for the same system.

**What counts as the horizontal length entered here?**

Only the horizontal run beyond the manufacturer's published base allowance included at 100% rated capacity — check the installation manual for that base length first, then enter only the additional length beyond it.

## Related calculators

- [Refrigerant Line Set Nominal Size Reference Calculator](https://craftquantities.com/calculators/materials-quantities/refrigerant-line-size-calculator/)
- [Generator Sizing Calculator](https://craftquantities.com/calculators/electrical/generator-sizing-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/mini-split-line-length-derating-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/mini-split-line-length-derating-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `mini-split-line-length-derating-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/mini-split-line-length-derating-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.