# Lightning Rod (Air Terminal) Cone of Protection Calculator

> Calculate the protected radius at ground level from a lightning air terminal, using the classical cone-of-protection method.

Page: https://craftquantities.com/calculators/materials-quantities/lightning-rod-protection-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Protected radius: 33 ft for Air Terminal Height Above Protected Surface 33 ft, the page's opening figures; on the metric page, 10 m gives 10 m. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Air Terminal Height Above Protected Surface | `rodHeight` | 10 m | 33 ft | mm, cm, m, in, ft, yd; range 0.01–50 m |
| Protection Angle (°, Per NFPA 780 Class/Height Table) | `protectionAngle` | 45 | 45 | range 25–60 |

- **Air Terminal Height Above Protected Surface**: The lightning air terminal's height above the roof or surface it is protecting.
- **Protection Angle (°, Per NFPA 780 Class/Height Table)**: The half-angle of the protective cone, set by NFPA 780's protection class and terminal height tables.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Protected radius** | 10 m |

### US customary

| Result | Value |
|---|---|
| **Protected radius** | 33 ft |

- Confidence: medium.

## How it is worked out

The classical cone method's protection angle depends on the lightning protection class and terminal height per NFPA 780 tables, and this simplified single-cone method does not replace NFPA 780's more comprehensive rolling sphere method, which is required for a complete and code-compliant lightning protection system design by a certified LPI installer/designer.

The method, derived in full:

- [Earthing, Fault Current and Working Clearance](https://craftquantities.com/methodology/earthing-fault-current-and-clearance/): Why a ground rod cannot clear a fault, why doubling a rod's diameter achieves almost nothing, and why a LOWER available fault current can produce a more dangerous arc flash.

What this calculation does not cover:

- A protected zone is not a path to earth. The terminal only helps if the strike can get to ground down low-impedance conductors — at least two from each air terminal system, run down separate faces without tight bends, into grounding electrodes and bonded to the building's other earthing. A terminal sitting on a roof with one long lead full of sharp corners concentrates the strike rather than dispersing it.
- Being inside the cone does not protect metal — it puts metal in the way. Ductwork, handrails, pipework, roof plant and anything else conductive within the zone has to be bonded to the system or held beyond a computed separation distance, because the surge travelling down the conductor will jump sideways to any grounded metal closer than that distance. Side flash inside a roof void is what starts the fire.
- Most lightning damage never touches the roof at all. It arrives as a surge induced onto incoming power, telecoms and data lines by a strike some distance away, and a cone of protection does nothing whatsoever about it — that needs surge protective devices at the service entrance and again in front of sensitive equipment. Buildings with a textbook air terminal layout still lose every controller on site to it.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Classical cone-of-protection method: protected radius = rod height × tan(protection angle), where the protection angle depends on the terminal's height and the desired protection class per NFPA 780 (this simplified cone method is a traditional approach; NFPA 780 also provides the more comprehensive rolling sphere method for modern lightning protection system design)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What is the classical cone-of-protection method?**

It models the zone protected by a lightning air terminal as a cone extending outward and downward from the terminal's tip, with protected radius = rod height × tan(protection angle) — a traditional approach per NFPA 780.

**Where does the protection angle come from?**

The protection angle depends on the terminal's height and the desired protection class, set by NFPA 780's class/height tables — it is not a fixed universal value, so confirm the correct angle for your specific installation before relying on this calculator.

**Is the cone method sufficient for a complete lightning protection system design?**

No. NFPA 780 also provides the more comprehensive rolling sphere method for modern lightning protection system design, which better accounts for complex rooflines and multiple terminals. A complete, code-compliant design should be performed by a certified LPI installer/designer.

## Related calculators

- [Roof Fall Protection Anchor Spacing Calculator](https://craftquantities.com/calculators/materials-quantities/roof-fall-protection-anchor-calculator/)
- [Roof Vent Pipe Boot Count Calculator](https://craftquantities.com/calculators/materials-quantities/roof-vent-boot-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/lightning-rod-protection-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/lightning-rod-protection-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `lightning-rod-protection-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/lightning-rod-protection-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/lightning-rod-protection-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.