# Lighting Circuit Connected Load Calculator

> Calculate a lighting circuit's total connected load and check it against the standard 80% continuous-load derating limit.

Page: https://craftquantities.com/calculators/materials-quantities/lighting-circuit-load-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 4 published test vectors.

Total connected lighting load: 720 W for Number of Light Fixtures 12, Watts per Fixture 60 and Circuit Voltage 120, the page's opening figures, to compare with the limit shown with it; a comparison, not a check. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Number of Light Fixtures | `fixtureCount` | 12 | 12 | range 1–100 |
| Watts per Fixture | `wattsPerFixture` | 60 | 60 | range 1–500 |
| Circuit Voltage (V) | `circuitVoltage` | 120 | 120 | range 12–600 |
| Breaker Rating (A) | `breakerRating` | 20 | 20 | range 5–50 |

- **Number of Light Fixtures**: The total number of light fixtures on this circuit.
- **Watts per Fixture**: The rated wattage of each fixture (or lamp/driver combination).
- **Circuit Voltage (V)**: The nominal voltage supplying the circuit.
- **Breaker Rating (A)**: The rating of the protective device on this circuit.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Total connected lighting load** | 720 W |
| Circuit current draw | 6 A |
| Maximum continuous load (80% of breaker) | 16 A |

### US customary

| Result | Value |
|---|---|
| **Total connected lighting load** | 720 W |
| Circuit current draw | 6 A |
| Maximum continuous load (80% of breaker) | 16 A |

- Confidence: medium.
- The figure is compared against a limit; that is a check of the number, not an approval.

## How it is worked out

The circuit's current draw is 6.0 A, at or below 16.0 A — 80% of the breaker rating, which NEC 210.19 and 210.20 set for a continuously-loaded circuit. Under BS 7671 the design check is instead Ib ≤ In ≤ Iz — load under device, device under cable capacity — with no 80% derate for lighting, so this comparison is on the cautious side of the British rule rather than a statement of it. Being inside the rating on this one check settles nothing about the rest of the circuit — the conductors, the overcurrent device, and the work as installed are all outside it.

The working the page shows, in order: Circuit current draw; Maximum continuous load (80% of breaker); then total connected lighting load.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- Watts divided by volts is the current only at unity power factor, and lighting is not at unity. LED drivers and ballasts pull current out of phase with the voltage, so the real figure is watts divided by volts times power factor — at 0.9 that is 11% more current than shown here, and uncorrected budget drivers sit nearer 0.5, which roughly doubles it. The breaker responds to current, not to watts.
- Steady-state load says nothing about the moment of switch-on. Electronic drivers charge their input capacitors in the first milliseconds at many times running current, and enough drivers on one circuit will trip a B-curve MCB or a thermal-magnetic breaker every time the lights are turned on, on a circuit that clears this check with room to spare. That is a driver-count and breaker-curve question, and it is decided nowhere on this page.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.
- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Connected load = fixture count × watts per fixture; per NEC 210.19/210.20, a continuously-loaded branch circuit's total load must not exceed 80% of the breaker's rating (equivalently, the breaker must be rated at least load ÷ 0.8)

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is the 80% continuous-load rule applied?**

Because NEC 210.19/210.20 limits a branch circuit supplying a continuous load, one on for 3 hours or more as most lighting circuits are, to 80% of the breaker's rating. Equivalently, the breaker must be rated at least the load divided by 0.8. This calculator checks the circuit's actual current draw against that 80% threshold.

**How is the connected load calculated?**

Connected load in watts is simply the number of fixtures multiplied by the watts per fixture. Dividing that by the circuit voltage gives the circuit's current draw in amps, which is then compared to 80% of the breaker rating.

**What if my circuit fails the 80% check?**

A failing result means the connected load draws more current than the continuous-load limit allows for the breaker size entered. Reduce the number of fixtures or wattage per fixture on that circuit, or move to a higher-rated breaker and conductor sized to match.

## Related calculators

- [Electrical Circuit Load Calculator](https://craftquantities.com/calculators/electrical/electrical-load-calculator/)
- [Three-Phase Electrical Panel Load Balancing Calculator](https://craftquantities.com/calculators/materials-quantities/panel-phase-balance-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/lighting-circuit-load-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/lighting-circuit-load-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `lighting-circuit-load-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/lighting-circuit-load-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/lighting-circuit-load-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.