# Commercial Kitchen Ventilation Hood Exhaust CFM Calculator

> Calculate the minimum exhaust airflow for an unlisted Type I commercial kitchen hood, per International Mechanical Code duty-rate tables.

Page: https://craftquantities.com/calculators/materials-quantities/kitchen-hood-exhaust-cfm-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Minimum required exhaust airflow (CFM): 2,400 CFM for Hood Length 8 ft, the page's opening figures; on the metric page, 2.44 m gives 2,402 CFM. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Hood Length | `hoodLength` | 2.44 m | 8 ft | mm, cm, m, in, ft, yd; range 0.01–12 m |
| Hood Style | `hoodStyle` | Wall-Mounted Canopy | Wall-Mounted Canopy | `wall-canopy`, `single-island`, `double-island-per-side`, `eyebrow`, `backshelf` |
| Cooking Duty Classification (Heaviest Appliance Under Hood) | `dutyLevel` | Medium Duty | Medium Duty | `light`, `medium`, `heavy`, `extra-heavy` |

- **Hood Length**: The overall length of the hood measured along its front, in the direction the appliances line up.
- **Hood Style**: The hood's mounting configuration, which sets its IMC Table 507.5 CFM-per-linear-foot rate.
- **Cooking Duty Classification (Heaviest Appliance Under Hood)**: The duty classification of the heaviest-duty appliance located anywhere under the hood.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Minimum required exhaust airflow (CFM)** | 2,402 CFM |
| Hood length | 2.44 m |
| CFM per linear foot rate used | 300 CFM/ft |
| Same airflow in L/s | 1,133.42 L/s |

### US customary

| Result | Value |
|---|---|
| **Minimum required exhaust airflow (CFM)** | 2,400 CFM |
| Hood length | 8 ft |
| CFM per linear foot rate used | 300 CFM/ft |
| Same airflow in L/s | 1,132.67 L/s |

## How it is worked out

This is the IMC Table 507.5 code-minimum rate for UNLISTED, field-fabricated Type I hoods. A listed hood tested per UL 710 may qualify for a lower manufacturer-published exhaust rate — check the specific hood's listing and manufacturer data before finalizing exhaust fan selection.

The working the page shows, in order: Hood length; CFM per linear foot rate used; Same airflow in L/s; then minimum required exhaust airflow (CFM).

The method, derived in full:

- [Containment, Capture and Process Airflow](https://craftquantities.com/methodology/containment-and-process-airflow/): Why a leaky asbestos enclosure needs more air rather than less, why an island cooker hood needs far more than a wall one, and why a powered attic fan can pull conditioned air out of the house it is cooling.

What this calculation does not cover:

- Every CFM exhausted has to come back in, and none of that is in this number. Code requires makeup air for a commercial hood, tempered in a cold climate, and without it the kitchen goes negative: doors drag, gas appliances backdraft, and the hood loses capture at exactly the edge its rate was set on. The makeup air unit is frequently the larger half of the mechanical package.
- The rate assumes a hood physically positioned to catch the plume. Table 507.5's CFM per linear foot is written for a canopy that overhangs the cooking surface on every open side and hangs at the listed height above it. A canopy cut back flush with the appliance line, or hung high to clear a head, spills grease-laden vapour into the room at the full code airflow.
- Extra-heavy duty means solid fuel, and solid-fuel appliances are generally required to have their OWN hood and their own duct, separate from everything else on the line. Selecting that duty level here to cover a wood-fired oven or a charcoal grill returns an airflow for a hood the code will not let it share, and brings spark arrestors and its own grease removal with it.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- CFM = hood length (linear ft) x CFM-per-linear-foot rate, selected by hood style and cooking-duty classification, per International Mechanical Code (IMC) Table 507.5 (the code-minimum method for unlisted/field-fabricated Type I hoods; NFPA 96 references the same duty classifications). Listed hoods tested per UL 710 may use lower manufacturer-published rates instead — this table is the code-minimum for unlisted hood construction. When a hood covers mixed-duty appliances, code requires using the rate for the heaviest-duty appliance under the entire hood length.

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does hood style change the required CFM?**

Island hoods are exposed to cross-drafts on all sides and pull air less efficiently than a wall-mounted canopy hood set against a wall, so IMC Table 507.5 assigns island hoods a higher CFM-per-linear-foot rate than a wall-mounted canopy hood of the same duty level.

**What happens if a hood covers appliances of different duty levels?**

Code requires using the rate for the heaviest-duty appliance located anywhere under the hood across its entire length — you cannot use a lower rate for the portion of the hood over lighter-duty appliances.

**Can a listed hood use a lower exhaust rate than this calculator shows?**

Yes — this calculator applies the IMC Table 507.5 code-minimum rate for unlisted, field-fabricated Type I hoods. A hood listed and tested per UL 710 may qualify for a lower manufacturer-published exhaust rate, so check the specific hood's listing and manufacturer data before finalizing exhaust fan selection.

## Related calculators

- [HVAC Duct Size Calculator](https://craftquantities.com/calculators/plumbing-hvac/hvac-duct-cfm-calculator/)
- [Grease Trap Sizing Calculator (PDI-G101 Method)](https://craftquantities.com/calculators/materials-quantities/grease-trap-sizing-calculator/)
- [Range Hood and Cooker Hood Airflow Calculator (CFM, L/s and Make-Up Air)](https://craftquantities.com/calculators/plumbing-hvac/range-hood-airflow-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/kitchen-hood-exhaust-cfm-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/kitchen-hood-exhaust-cfm-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `kitchen-hood-exhaust-cfm-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/kitchen-hood-exhaust-cfm-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/kitchen-hood-exhaust-cfm-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.