# Concrete-Filled HSS Composite Column Capacity Calculator

> Estimate the cross-sectional compressive capacity of a concrete-filled HSS composite column.

Page: https://craftquantities.com/calculators/materials-quantities/hss-composite-column-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Cross-sectional compressive capacity Pno: 617 kips for Steel Yield Strength Fy 50038.02 psi, Steel HSS Cross-Sectional Area As 7.75 in² and Concrete Strength f'c 4351.13 psi, the page's opening figures; on the metric page, 345 MPa, 5000 mm² and 30 MPa give 2,750 kN. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Steel Yield Strength Fy | `steelYieldStrength` | 345 MPa | 50038 psi | pa, kpa, mpa, psi, psf, in_wc; range 200000000–700000000 Pa |
| Steel HSS Cross-Sectional Area As | `steelArea` | 5000 mm² | 7.75002 in² | m2, ft2, mm2, in2; range 0.0002–0.05 m² |
| HSS Shape | `shapeType` | Rectangular/Square HSS (C2 = 0.85) | Rectangular/Square HSS (C2 = 0.85) | `0.85`, `0.95` |
| Concrete Strength f'c | `concreteStrength` | 30 MPa | 4351.13 psi | pa, kpa, mpa, psi, psf, in_wc; range 15000000–70000000 Pa |
| Concrete Infill Area Ac | `concreteArea` | 40000 mm² | 62.0001 in² | m2, ft2, mm2, in2; range 0.001–0.5 m² |

- **Steel Yield Strength Fy**: The HSS steel's specified minimum yield strength.
- **Steel HSS Cross-Sectional Area As**: The hollow steel section's own cross-sectional (wall) area, from the manufacturer's tables.
- **HSS Shape**: The HSS shape, which sets the concrete confinement coefficient C2.
- **Concrete Strength f'c**: The specified compressive strength of the concrete infill.
- **Concrete Infill Area Ac**: The cross-sectional area of the concrete infill (inside the HSS wall).

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Cross-sectional compressive capacity Pno** | 2,750 kN |
| phi_c x Pno (phi_c = 0.75, still before slenderness) | 2,058.75 kN |

### US customary

| Result | Value |
|---|---|
| **Cross-sectional compressive capacity Pno** | 617 kips |
| phi_c x Pno (phi_c = 0.75, still before slenderness) | 462.83 kips |

- Confidence: medium.

## How it is worked out

This is the zero-length NOMINAL cross-sectional capacity (Pno) for a compact section. TWO steps stand between it and a design strength you may compare against a factored load: the AISC slenderness reduction (Pn = Pno x 0.658^(Pno/Pe), from the effective stiffness and unbraced length), and the resistance factor phi_c = 0.75 from AISC 360 I2.2b. Neither is applied above. A short, well-braced column is the dangerous case here, because the slenderness step barely moves it and the missing phi alone leaves a third more capacity than the code allows. Consult a structural engineer for final column design.

The working the page shows, in order: phi_c x Pno (phi_c = 0.75, still before slenderness); then cross-sectional compressive capacity Pno.

The method, derived in full:

- [Section Capacity: Bending, Axial, Shear, and Which One Gives First](https://craftquantities.com/methodology/section-capacity/): Why depth is worth four times what width is in bending, why reinforced concrete is deliberately designed to fail in the steel rather than the concrete, and why a notch removes far more strength than material.

What this calculation does not cover:

- The equation above is the compact-section case only. AISC classifies a filled section by wall slenderness — b/t against 2.26√(E/Fy) for rectangular HSS, D/t against 0.15E/Fy for round — and a noncompact or slender wall buckles locally before the steel ever reaches Fy, so Pno then comes from a different and lower expression. Fy × As applied to a thin-walled tube overstates the steel's contribution, not the concrete's, and nothing on this page checks the wall.
- The concrete only carries its share if the load is actually put into it. Where a beam or cap plate delivers load to the steel tube alone, AISC Chapter I6 governs the transfer into the core — direct bearing, limited to 1.7 f'c on the bearing area, or shear connectors inside the tube — and it has to occur within the load introduction length either side of the connection. A column detailed to bear on the tube wall alone never develops the Ac term counted above.
- This is the room-temperature capacity. A concrete-filled HSS is often chosen for its fire performance, where the tube weakens first and the core carries the column — which usually means reinforcing bar or fiber in the fill, and always means vent holes drilled through the tube wall at each floor, because steam trapped in a heated sealed tube can burst it. None of that follows from Pno.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- AISC 360 Chapter I (§I1.2a, §I2.2b): Pno = Fy×As + C2×f'c×Ac, where C2 = 0.85 for rectangular HSS and 0.95 for round HSS (confinement effect)

The site's pages for the documents these name:

- [AISC 360](https://craftquantities.com/standards/aisc/aisc-360/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does round HSS get a higher confinement coefficient (C2) than rectangular HSS?**

A round tube confines its concrete infill more uniformly under compression than a rectangular or square tube does, so AISC 360 assigns round HSS a higher C2 value (0.95) than rectangular/square HSS (0.85) to reflect that added confinement contribution to the concrete's strength.

**Is this the final usable capacity of the column?**

No — Pno is only the cross-sectional (zero-length) compressive capacity. For any column with meaningful unbraced length, AISC 360 requires a slenderness reduction (Pn = Pno·0.658^(Pno/Pe)) that lowers the usable capacity below Pno. This calculator does not perform that reduction.

**What areas should I use for As and Ac?**

As is the steel HSS wall's own cross-sectional area (from the manufacturer's or AISC shape tables), and Ac is the area of the concrete infill inside the HSS — the two must be measured separately and not double-counted.

## Related calculators

- [Timber Column Euler Buckling Calculator](https://craftquantities.com/calculators/materials-quantities/timber-column-buckling-calculator/)
- [Timber Post Bearing Area Calculator](https://craftquantities.com/calculators/materials-quantities/post-bearing-area-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/hss-composite-column-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/hss-composite-column-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `hss-composite-column-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/hss-composite-column-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/hss-composite-column-calculator/