# Domestic Water Pipe Friction Loss Calculator (Hazen-Williams)

> Calculate the friction head loss in a domestic water supply pipe run using the Hazen-Williams formula.

Page: https://craftquantities.com/calculators/materials-quantities/hazen-williams-friction-loss-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-06, 2 published test vectors.

Friction head loss: 18 ft for Pipe Length 165 ft, the page's opening figures; on the metric page, 50 m gives 5.92 m. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Pipe Length | `pipeLength` | 50 m | 165 ft | mm, cm, m, in, ft, yd; range 0.01–500 m |
| Flow Rate | `flowRate` | 5 L/s | 79 gal/min | lpm, lps, gpm; range 0.1–3000 L/min |
| Hazen-Williams Coefficient C (150 for New Copper/Plastic, 140 for New Steel) | `roughnessCoefficient` | 150 | 150 | range 100–160 |
| Internal Pipe Diameter | `pipeDiameter` | 50 mm | 2 in | mm, cm, m, in, ft, yd; range 0.01–0.3 m |

- **Pipe Length**: The total length of the pipe run.
- **Flow Rate**: The design flow rate through the pipe.
- **Hazen-Williams Coefficient C (150 for New Copper/Plastic, 140 for New Steel)**: The pipe material's Hazen-Williams roughness coefficient.
- **Internal Pipe Diameter**: The pipe's actual internal (bore) diameter.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Friction head loss** | 5.92 m |

### US customary

| Result | Value |
|---|---|
| **Friction head loss** | 18 ft |

## How it is worked out

The method, derived in full:

- [Head Loss, Falls and Surge: Resistance in Pipes, Ducts and Drains](https://craftquantities.com/methodology/head-loss-falls-and-surge/): Why one pipe size up cuts the friction to a third, why a compressed flex duct can cost four times its rated loss, why a drain can be too steep, and why a fast-closing valve produces a pressure the pump never could.

What this calculation does not cover:

- Hazen-Williams is an empirical fit to cold water in turbulent flow, roughly 40 to 75 °F (4 to 24 °C) at velocities in the 2 to 10 ft/s (0.6 to 3 m/s) band. Outside that it drifts: glycol-charged loops, hot recirculating mains and low-flow trickles are Darcy-Weisbach problems, where viscosity enters the calculation instead of being absorbed into a single C value. The formula still returns a number for any of them; it is just not the loss you will measure.
- Head loss is one term of the pressure the fixture actually sees. What is available is the incoming main, less the static lift to the outlet, less this friction, less the fittings, and less every device in the line — a meter, a backflow preventer, a filter and a softener can take 20 to 30 psi (207 kPa) between them. A run whose friction loss looks comfortable here can still open at a shower with nothing left.
- Velocity is not reported, and velocity is often what sizes the pipe rather than head loss. Copper is normally held near 8 ft/s cold and 5 ft/s or less on hot recirculating lines, because water moving faster erodes the inside of elbows and tees over the years and makes the pipe audible in the wall. A small pipe on a short run can pass a friction check comfortably and still be the wrong size.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Hazen-Williams equation (SI units): hf = 10.67 × L × Q^1.852 ÷ (C^1.852 × D^4.8704), where L is pipe length (m), Q is flow rate (m³/s), C is the Hazen-Williams roughness coefficient, and D is the pipe's internal diameter (m)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What does the Hazen-Williams C coefficient represent?**

It's an empirical roughness coefficient for the pipe material and condition — smoother pipes like new copper or plastic use a higher C (around 150), while older or rougher steel pipe uses a lower C (around 140), which increases the calculated friction loss.

**Why does pipe diameter have such a large effect on the result?**

The Hazen-Williams equation raises diameter to the power of 4.8704 in the denominator, so even a modest reduction in internal diameter causes a much larger increase in friction head loss for the same flow rate.

**Does this calculator include losses from fittings and valves?**

No — this calculates straight-pipe friction loss only, based on the Hazen-Williams equation. Fitting and valve losses should be added separately, typically by converting them to an equivalent length of straight pipe.

## Related calculators

- [Pipe Volume Calculator](https://craftquantities.com/calculators/plumbing-hvac/pipe-volume-calculator/)
- [Domestic Water Pipe Sizing by Fixture Unit Calculator](https://craftquantities.com/calculators/materials-quantities/domestic-water-pipe-sizing-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/hazen-williams-friction-loss-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/hazen-williams-friction-loss-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `hazen-williams-friction-loss-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/hazen-williams-friction-loss-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/hazen-williams-friction-loss-calculator/