# Isolated Ground Rod Earth Resistance Calculator (Dwight's Formula)

> Calculate a single driven ground rod's earth resistance using Dwight's formula.

Page: https://craftquantities.com/calculators/materials-quantities/ground-rod-resistance-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Estimated ground rod resistance: 39.9 Ω for Soil Resistivity ρ 100 and Rod Diameter d 0.02, the page's opening figures; on the metric page, 100 and 0.02 give 40.4 Ω. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Soil Resistivity ρ (Ω·m) | `soilResistivity` | 100 | 100 | range 10–1000 |
| Rod driven length | `rodLength` | 2.4 m | 8 ft | mm, cm, m, in, ft, yd; range 0.01–6 m |
| Rod Diameter d (m, e.g. 0.0159 for 5/8 in) | `rodDiameter` | 0.0159 | 0.0159 | range 0.0127–0.025 |

- **Soil Resistivity ρ (Ω·m)**: How strongly the surrounding soil resists electrical current flow.
- **Rod driven length**: The length of the ground rod actually driven into the earth.
- **Rod Diameter d (m, e.g. 0.0159 for 5/8 in)**: The rod's outer diameter.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Estimated ground rod resistance** | 40.4 Ω |

### US customary

| Result | Value |
|---|---|
| **Estimated ground rod resistance** | 39.9 Ω |

- Confidence: medium.

## How it is worked out

Soil resistivity varies significantly with moisture, temperature, and composition — use a field-measured value (e.g. Wenner four-pin test) for your actual site rather than an assumed value. NEC 250.53(A)(2) requires a single rod to test at 25Ω or less, or a second rod must be added; this calculator estimates the resistance, it does not replace an actual field measurement.

The method, derived in full:

- [Earthing, Fault Current and Working Clearance](https://craftquantities.com/methodology/earthing-fault-current-and-clearance/): Why a ground rod cannot clear a fault, why doubling a rod's diameter achieves almost nothing, and why a LOWER available fault current can produce a more dangerous arc flash.

What this calculation does not cover:

- Dwight's formula assumes one uniform soil for the full depth of the rod, and real ground is layered. A wet clay skin over dry sand, or two feet of topsoil over rock, cannot be reduced to a single resistivity — and if the rod refuses on rock at 1.2 m then the length in the formula is 1.2 m, not the 2.4 m of steel that was bought. A Wenner traverse at several pin spacings reveals the profile; one number conceals it, and the error runs to a factor rather than a percentage.
- Resistivity is seasonal, and the shallow soil moves the most. It climbs steeply as ground dries and again as it freezes, where it can rise by an order of magnitude, so the upper metre — the part that dries and freezes — contributes least at exactly the times it is needed. A rod that measures 20 Ω after spring rain can be well past the 25 Ω threshold in February or in a drought, which is why driving below the frost line does far more than diameter ever will.
- One isolated rod. Add a second and the resistance does not halve, because the two current fields overlap — set them closer than the driven length apart and the pair behaves more like a single larger electrode than like two in parallel, which is the reason a minimum separation exists at all. Nor does this see the rest of the electrode system: a concrete-encased electrode, a metal water service or bonded building steel sits in parallel with the rod and usually dominates whatever a fall-of-potential or clamp-on test actually reads.
- A low rod resistance does not clear a fault. On a grounded AC system the fault current returns to the source along the equipment grounding conductor, and the earth is explicitly not permitted to serve as that path — a flawless 5 Ω rod will not operate a breaker. The rod is there for lightning, for static and for holding the system's voltage reference, so ohms in the ground are no substitute for a continuous low-impedance bonded return.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Dwight's formula for a single driven ground rod: R = (ρ ÷ (2×π×L)) × (ln(8L÷d) − 1), where ρ is soil resistivity, L is the rod's driven length, and d is the rod diameter — a well-established, widely-cited formula for estimating single ground rod resistance (IEEE Std 142)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What does Dwight's formula calculate?**

It estimates the earth resistance of a single driven ground rod: R = (ρ ÷ (2×π×L)) × (ln(8L÷d) − 1), where ρ is soil resistivity, L is the rod's driven length, and d is the rod's diameter. It's a well-established, widely-cited formula (per IEEE Std 142) for single ground rod resistance.

**Why does rod diameter matter so little compared to rod length?**

Because diameter only appears inside the logarithm term (ln(8L/d)), while rod length appears both inside the logarithm and as a direct divisor: driving a longer rod lowers resistance far more effectively than using a thicker one. Doubling the diameter has a small effect on the result.

**Is this calculated value good enough for a code compliance test?**

No — this is an estimate only. Soil resistivity varies significantly with moisture, temperature, and composition, so it should be field-measured (e.g. via a Wenner four-pin test) for your actual site. NEC 250.53(A)(2) requires a single rod to test at 25Ω or less (or a second rod must be added), and that determination must come from an actual field measurement, not a calculated estimate.

## Related calculators

- [Server Room Grounding Grid Resistance Calculator](https://craftquantities.com/calculators/materials-quantities/grounding-grid-resistance-calculator/)
- [Busbar Ampacity Calculator (Current Density Method)](https://craftquantities.com/calculators/materials-quantities/busbar-ampacity-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/ground-rod-resistance-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/ground-rod-resistance-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `ground-rod-resistance-calculator`.