# Grease Trap Sizing Calculator (PDI-G101 Method)

> Calculate the required grease trap capacity for a commercial kitchen, based on flow rate, retention time, and storage factor.

Page: https://craftquantities.com/calculators/materials-quantities/grease-trap-sizing-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-06, 2 published test vectors.

Required grease trap capacity: 136 gal for Retention Time 2 and Storage Factor 1.7, the page's opening figures; on the metric page, 2 and 1.7 give 510 L. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Flow Rate | `flowRate` | 150 L/min | 40 gal/min | lpm, lps, gpm; range 20–800 L/min |
| Retention Time (minutes, Typically 2 per PDI-G101) | `retentionTime` | 2 | 2 | range 1–4 |
| Storage Factor (Typically 1.7 for Full-Service Restaurants) | `storageFactor` | 1.7 | 1.7 | range 1–2.5 |

- **Flow Rate**: The peak drainage flow rate from the fixtures connected to the grease interceptor.
- **Retention Time (minutes, Typically 2 per PDI-G101)**: The minimum time wastewater must be retained in the interceptor to allow grease to separate.
- **Storage Factor (Typically 1.7 for Full-Service Restaurants)**: A multiplier accounting for grease storage capacity needed between service intervals.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Required grease trap capacity** | 510 L |

### US customary

| Result | Value |
|---|---|
| **Required grease trap capacity** | 136 gal |

- Confidence: medium.

## How it is worked out

Flow rate and storage factor depend on the specific fixtures connected (per PDI-G101 fixture flow rate tables) and food service type — confirm against your local plumbing code's grease interceptor sizing requirements.

The method, derived in full:

- [Fixture Units, Diversity and Drainage Loads](https://craftquantities.com/methodology/fixture-units-demand-and-diversity/): Why a hundred fixtures do not need a hundred times one fixture's flow, why low-flow fittings turned an oversized water main into a health problem, and why a grease interceptor is sized on time rather than on flow.

What this calculation does not cover:

- A PDI-rated interceptor only performs at its rated flow, and reaching that takes a flow-control fitting this sizing never mentions. The fitting's orifice plus its vent throttles the surge from a pot sink dumping so the water is actually inside the unit for the retention time assumed above; without it the slug blows straight through a correctly sized trap and takes the grease with it. It is the cheapest item in the installation and the one most often omitted.
- What gets connected matters more than the capacity. Dishwasher discharge at 60-80°C re-emulsifies grease so it passes through as a solution and re-solidifies in the sewer downstream, which is why many jurisdictions bar a dishwasher from a small point-of-use interceptor or divert it to a large in-ground one; a food waste disposer fills the same unit with solids that eat the grease storage this factor was meant to buy. Sanitary drainage must never be connected at all.
- The storage factor extends the service interval only until the rule catches up with it. Most authorities require pumping once grease and settled solids reach a quarter of the wetted volume, and many set a maximum interval regardless of size — 90 days is common — so a generously sized unit does not buy an open-ended run between visits, and the manifest for those visits is usually what an inspector asks for first.
- The answer is a liquid volume, which is not how a point-of-use unit is bought. Hydromechanical interceptors are certified as a flow rating with a paired grease capacity in pounds and sold in fixed steps, so this figure has to land on a catalogue model rather than a tank size. A gravity interceptor buried outside is the one specified as a volume, and most codes size that one by a different method again.

A professional must decide:

- The storage factor extends the service interval only until the rule catches up with it. Most authorities require pumping once grease and settled solids reach a quarter of the wetted volume, and many set a maximum interval regardless of size — 90 days is common — so a generously sized unit does not buy an open-ended run between visits, and the manifest for those visits is usually what an inspector asks for first.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- PDI-G101 method: required grease trap capacity = flow rate × retention time × storage factor, the standard plumbing industry method for sizing hydromechanical grease interceptors for commercial kitchen fixtures

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What is the PDI-G101 method?**

PDI-G101 is the standard plumbing industry method for sizing hydromechanical grease interceptors for commercial kitchen fixtures, using the formula required capacity = flow rate × retention time × storage factor.

**Where does the flow rate value come from?**

Flow rate should come from the PDI-G101 fixture flow rate tables, totaled across the specific fixtures (sinks, dishwashers, etc.) connected to the interceptor — confirm the correct per-fixture values for your equipment.

**Can I rely on this result alone for a permit-ready grease interceptor size?**

No — flow rate and storage factor depend on the specific connected fixtures and food service type. Always confirm the required capacity against your local plumbing code's grease interceptor sizing requirements before selecting equipment.

## Related calculators

- [Trap Primer Flow Rate Calculator](https://craftquantities.com/calculators/materials-quantities/trap-primer-flow-calculator/)
- [Backflow Preventer Discharge Velocity Calculator](https://craftquantities.com/calculators/materials-quantities/backflow-preventer-velocity-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/grease-trap-sizing-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/grease-trap-sizing-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `grease-trap-sizing-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/grease-trap-sizing-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/grease-trap-sizing-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.