# Foundation Frost-Protection Insulation Depth Calculator

> Calculate the rigid insulation thickness needed to achieve a target R-value for frost-protected shallow foundations.

Page: https://craftquantities.com/calculators/materials-quantities/foundation-frost-insulation-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Required insulation thickness: 2 in for Target R-Value 10 and Board R-Value per Inch 5, the page's opening figures; on the metric page, 10 and 5 give 50.8 mm. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Target R-Value (Per Frost-Protection Design) | `targetRValue` | 10 | 10 | range 2–25 |
| Board R-Value per Inch | `rValuePerInch` | 5 | 5 | range 3.5–6.5 |

- **Target R-Value (Per Frost-Protection Design)**: The total R-value required by your frost-protected shallow foundation design.
- **Board R-Value per Inch**: The rated thermal resistance per inch of thickness for the specific rigid insulation board.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Required insulation thickness** | 50.8 mm |

### US customary

| Result | Value |
|---|---|
| **Required insulation thickness** | 2 in |

- Confidence: medium.

## How it is worked out

Target R-value for frost-protected shallow foundations (FPSF) depends on your local frost depth/climate zone per IRC Appendix AF or local code — confirm the required R-value for your specific location before sizing insulation thickness.

The method, derived in full:

- [Thermal Resistance in Series](https://craftquantities.com/methodology/thermal-resistance-in-series/): Why R-values add but U-values do not, and why the assembly you build never performs like the assembly you specified.

What this calculation does not cover:

- The rated R per inch is a dry laboratory figure at a mean temperature around 75°F, and buried foam is neither dry nor at 75°F. Boards in wet ground take up water and lose resistance as they do, extruded polystyrene sheds blowing agent over decades toward a lower aged value, and polyiso — which is what the top of this input's range describes — absorbs water badly and is generally not accepted below grade at all. Choose a product the FPSF detail permits underground first, then read its R per inch off that product's sheet.
- The answer is a raw division, not a stock thickness. Foam comes in fixed thicknesses, so 3.33 in (85 mm) means two layers, and two layers only deliver the calculated figure if their joints are offset — aligned seams leave a straight thermal path through the whole assembly at every one. The portion above grade also needs a protective covering against sunlight and impact, which adds thickness the trench width and the finish detail have to accommodate.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Required thickness = target R-value ÷ the insulation board's rated R-value per inch, the same relationship used for any rigid foam insulation thickness sizing

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Where does the target R-value come from?**

From IRC Appendix AF (Frost-Protected Shallow Foundations) or your local building code, which set it by your local frost depth and climate zone. It is not a single fixed value, so confirm the required target for your specific site before sizing insulation.

**Why does board R-value per inch vary between products?**

Rigid foam insulation types (EPS, XPS, polyiso, etc.) have different rated thermal resistance per inch — always use the specific rated R-value per inch from your chosen board's manufacturer data sheet, not a generic assumption.

**Does this account for insulation placed vertically versus horizontally (wings)?**

No — this only converts a target R-value into a required thickness for a single insulation layer. FPSF designs typically also require horizontal wing insulation extending outward from the foundation; size that separately per your code table.

## Related calculators

- [EIFS Insulation Board Thickness Calculator](https://craftquantities.com/calculators/materials-quantities/eifs-insulation-thickness-calculator/)
- [Under-Slab Perimeter Rigid Foam Board Calculator](https://craftquantities.com/calculators/materials-quantities/under-slab-perimeter-foam-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/foundation-frost-insulation-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/foundation-frost-insulation-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `foundation-frost-insulation-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/foundation-frost-insulation-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/foundation-frost-insulation-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.