# Formwork Brace & Kicker Force Calculator

> The axial load in a wall-form brace (kicker) from the lateral pressure on its tributary strip, and the horizontal and vertical reactions at its anchor.

Page: https://craftquantities.com/calculators/materials-quantities/formwork-brace-force-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-08-30, 2 published test vectors.

Axial force in the brace: 1.13 kips for Form Height 10 ft, Brace Spacing Along the Form 6 ft and Design Lateral Load on the Form Face 15.04 psf, the page's opening figures; on the metric page, 3 m, 1.8 m and 0.72 kPa give 4.86 kN. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Form Height | `formHeight` | 3 m | 10 ft | mm, cm, m, in, ft, yd; range 0.6–8 m |
| Brace Spacing Along the Form | `braceSpacing` | 1.8 m | 6 ft | mm, cm, m, in, ft, yd; range 0.3–6 m |
| Design Lateral Load on the Form Face | `lateralPressure` | 0.72 kPa | 15.0375 psf | pa, kpa, mpa, psi, psf, in_wc; range 100–5000 Pa |
| Brace Angle to Horizontal (degrees) | `braceAngle` | 60 | 60 | range 15–75 |
| Brace Attachment Height | `attachmentHeight` | 2.4 m | 8 ft | mm, cm, m, in, ft, yd; range 0.3–8 m |

- **Form Height**: Full height of the form panel that the lateral pressure acts against.
- **Brace Spacing Along the Form**: Centre-to-centre spacing of the kickers, which is also the width of form tributary to one of them.
- **Design Lateral Load on the Form Face**: Lateral load per unit of form face, taken from the governing construction-loads document.
- **Brace Angle to Horizontal (degrees)**: Angle the kicker makes with the slab it bears on, measured at the anchorage.
- **Brace Attachment Height**: Height above the base of the form at which the kicker connects to it.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Axial force in the brace** | 4.86 kN |
| Total lateral force on the braced strip | 3.89 kN |
| Horizontal reaction at the anchorage | 2.43 kN |
| Vertical reaction at the anchorage | 4.21 kN |
| Lateral force per unit length of form | 2.16 kN/m |

### US customary

| Result | Value |
|---|---|
| **Axial force in the brace** | 1.13 kips |
| Total lateral force on the braced strip | 0.9 kips |
| Horizontal reaction at the anchorage | 0.56 kips |
| Vertical reaction at the anchorage | 0.98 kips |
| Lateral force per unit length of form | 150.38 lbf/ft |

- Confidence: medium.

## How it is worked out

This is one brace resolved by statics. Whether the slab can take it is a separate anchor check against the concrete's age and strength on the day, the embedment available, and the edge distance at the fixing — a young slab is the usual weak link, not the kicker.

The working the page shows, in order: Total lateral force on the braced strip; Horizontal reaction at the anchorage; Vertical reaction at the anchorage; Lateral force per unit length of form; then axial force in the brace.

The method, derived in full:

- [Formwork Pressure](https://craftquantities.com/methodology/formwork-pressure/): Why a column form sees full hydrostatic pressure and a wall form usually does not, and why temperature belongs in the equation.

What this calculation does not cover:

- Single-sided bracing on a form pinned at its base; a form braced from both faces, or one restrained at the base by a kicker plate, distributes the load differently.
- Does not check the brace member itself for buckling, nor its end connections — a compression kicker at this angle is often governed by slenderness rather than by axial capacity.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-08-30):

- ACI 347R, Guide to Formwork for Concrete, is the document that sets the minimum lateral force wall-form bracing must be designed for; the pressure used here is the one you enter from it, not a figure this page supplies
- ASCE/SEI 37, Design Loads on Structures During Construction, governs the construction-stage wind and lateral load cases that produce that pressure
- OSHA 29 CFR 1926 Subpart Q requires formwork to be designed, erected, supported, braced and maintained so that it supports all vertical and lateral loads applied to it
- Statics only: uniform lateral pressure over the tributary strip, the form taken as pinned at its base, and the resultant resolved along a kicker at the angle entered

The site's pages for the documents these name:

- [ACI 347R](https://craftquantities.com/standards/aci/aci-347r/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Is the concrete's lateral pressure the load I should enter here?**

Usually not. The concrete's pressure is what sizes the sheathing, studs, walers and ties — it acts inward on the form face and is largely balanced by the ties. What the kicker resists is the load that would push the whole assembly over: wind on the exposed face, workers and plant leaning on it, and the code minimum that applies when neither is large.

**Why does attaching the brace lower down make the force so much worse?**

Because the overturning moment stays the same while the lever arm resisting it gets shorter. The wind or code load acts at mid-height of the panel whatever you do; halving the height at which the kicker connects doubles the horizontal reaction it has to develop, and the axial force follows straight along with it.

**What does the vertical reaction actually do to the slab?**

It presses down where a compression kicker bears and lifts where a tension brace pulls, and at 60 degrees it is nearly twice the horizontal component rather than a small side effect. On a young slab or a thin topping, that vertical component is frequently what governs the anchor rather than the shear.

**Does this cover a form braced from both sides?**

No. Two-sided bracing shares the lateral load between the two systems and changes the base condition assumed here, so running this once per side would overstate both. Treat the result as the single-sided case, which is the arrangement most site kickers actually are.

## Related calculators

- [ACI 347 Wall Formwork Rate-of-Placement Pressure Calculator](https://craftquantities.com/calculators/materials-quantities/wall-formwork-pressure-calculator/)
- [Concrete Formwork Tie Spacing Calculator](https://craftquantities.com/calculators/materials-quantities/formwork-tie-spacing-calculator/)
- [Concrete Formwork Calculator](https://craftquantities.com/calculators/materials-quantities/concrete-formwork-calculator/)
- [Concrete Anchor Bolt Breakout Capacity Calculator (ACI 318)](https://craftquantities.com/calculators/materials-quantities/anchor-bolt-breakout-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/formwork-brace-force-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/formwork-brace-force-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `formwork-brace-force-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/formwork-brace-force-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/formwork-brace-force-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.