# Flexible Duct Friction Pressure Loss Calculator

> Estimate friction pressure loss through a flexible duct run from a curve-fit of the ASHRAE duct friction chart, times an installation-quality factor.

Page: https://craftquantities.com/calculators/materials-quantities/flex-duct-friction-loss-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Estimated total friction pressure loss: 0.059 in. w.g. for Airflow 150 CFM, Duct Diameter 8 in and Duct Run Length 39 ft, the page's opening figures; on the metric page, 70.79 L/s, 203.2 mm and 12 m give 15 Pa. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Airflow | `airflow` | 70.7921 L/s | 150 CFM | lps, m3h, lpm, cfm; range 9.4389–943.895 L/s |
| Duct Diameter | `ductDiameter` | 203.2 mm | 8 in | mm, cm, m, in, ft, yd; range 0.01–0.508 m |
| Duct Run Length | `runLength` | 12 m | 39 ft | mm, cm, m, in, ft, yd; range 0.01–60 m |
| Installation-Quality Friction Multiplier (1.5-2 Fully Extended, 3-4 Average Sag, 5-10+ Compressed/Kinked) | `installFactor` | 3.5 | 3.5 | range 1.5–10 |

- **Airflow**: The volumetric airflow moving through the duct run.
- **Duct Diameter**: The flex duct's nominal inside diameter.
- **Duct Run Length**: The total length of the flex duct run.
- **Installation-Quality Friction Multiplier (1.5-2 Fully Extended, 3-4 Average Sag, 5-10+ Compressed/Kinked)**: How much higher the flex duct's actual friction runs versus smooth rigid duct, based on how well it's installed.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Estimated total friction pressure loss** | 15 Pa |
| Base smooth-duct friction rate (per 100 ft) | 0.04 in. w.g./100 ft |

### US customary

| Result | Value |
|---|---|
| **Estimated total friction pressure loss** | 0.059 in. w.g. |
| Base smooth-duct friction rate (per 100 ft) | 0.04 in. w.g./100 ft |

- Confidence: low.

## How it is worked out

This uses a third-party curve-fit approximation of the ASHRAE Fundamentals duct friction chart, not an ASHRAE-published closed-form equation, plus a user-supplied installation-quality multiplier standing in for the actual flex-duct friction chart. For final duct design, use the specific flex duct manufacturer's published friction chart (required by ACCA Manual D Appendix 3) rather than this screening estimate — a compressed or sagging flex run can have far higher friction than the multiplier ranges shown here suggest.

The working the page shows, in order: Base smooth-duct friction rate (per 100 ft); then estimated total friction pressure loss.

The method, derived in full:

- [Head Loss, Falls and Surge: Resistance in Pipes, Ducts and Drains](https://craftquantities.com/methodology/head-loss-falls-and-surge/): Why one pipe size up cuts the friction to a third, why a compressed flex duct can cost four times its rated loss, why a drain can be too steep, and why a fast-closing valve produces a pressure the pump never could.

What this calculation does not cover:

- Fittings are not in this run. The number covers straight duct only, and on a flex branch the elbows, the boot at the ceiling, the takeoff collar at the trunk and the balancing damper are usually worth more pressure than the straight length is. Manual D handles them as equivalent length, and a single tight-radius bend in flex can be worth tens of feet of straight duct on its own — add those equivalent lengths into the run length above before treating this as the branch's loss.
- One branch is not the system. What the blower has to overcome is the whole path — return grille, filter, coil, supply trunk, this branch and the register at the end — and the fan's available external static is what all of it shares. A branch that reads a comfortable 0.06 in. w.g. can still be the one that starves, because the coil and the trunk ahead of it already spent the budget.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Base friction rate (in. w.g. per 100 ft) = 0.109136 × CFM^1.9 ÷ Diameter(in)^5.02, a widely-reproduced curve-fit approximation of the ASHRAE Fundamentals Ch. 21 smooth round galvanized duct friction chart. Flexible duct has significantly higher friction than smooth rigid duct of the same diameter — per ASHRAE-sponsored research (Culp, 'Compression Effects on Pressure Loss in Flexible HVAC Ducts'), a fully-extended flex duct runs roughly 1.5-3x smooth duct friction, while typical field installations with some sag/compression can run 3-4x or considerably higher; ACCA Manual D Appendix 3 and manufacturer-published flex-duct friction charts are the authoritative source for a specific product.

The site's pages for the documents these name:

- [ACCA Manual D](https://craftquantities.com/standards/acca/acca-manual-d/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does flexible duct have more friction loss than rigid duct of the same size?**

Because its inner wire-helix core creates a corrugated, ribbed inner surface, and any sag or compression along the run adds further disruption. Per ASHRAE-sponsored research, a fully-extended flex duct runs roughly 1.5-3x smooth rigid duct friction, and a typical field installation with some sag can run 3-4x or considerably higher.

**Which installation-quality multiplier should I use?**

Use 1.5-2 for flex duct that is fully extended with no sag, 3-4 for an average field installation with some sag, and 5-10+ if the run is visibly compressed or kinked. These are approximate ranges — the specific product's manufacturer friction chart is the authoritative source.

**Is this precise enough for final duct design?**

No. This calculator uses a third-party curve-fit approximation of the ASHRAE smooth-duct friction chart plus a user-supplied multiplier, not an ASHRAE-published closed-form equation or the actual flex-duct chart. For final design, ACCA Manual D Appendix 3 requires using the specific flex duct manufacturer's published friction chart — a compressed or sagging run can have far higher friction than these multiplier ranges suggest.

## Related calculators

- [HVAC Duct Size Calculator](https://craftquantities.com/calculators/plumbing-hvac/hvac-duct-cfm-calculator/)
- [Duct Insulation Wrap Area Calculator](https://craftquantities.com/calculators/materials-quantities/duct-insulation-wrap-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/flex-duct-friction-loss-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/flex-duct-friction-loss-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `flex-duct-friction-loss-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/flex-duct-friction-loss-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/flex-duct-friction-loss-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.