# Electrical Equipment Working Clearance Space Calculator

> Calculate the required clear floor space in front of electrical equipment per NEC 110.26 working clearance rules.

Page: https://craftquantities.com/calculators/materials-quantities/electrical-working-clearance-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Required minimum working clearance area: 7.38 sq ft for Equipment Width 2 ft and Required Clearance Depth (Per NEC 110.26(A) Table 3 ft, the page's opening figures; on the metric page, 0.6 m and 900 mm give 0.675 m². Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Equipment Width | `equipmentWidth` | 0.6 m | 2 ft | mm, cm, m, in, ft, yd; range 0.01–3 m |
| Required Clearance Depth (Per NEC 110.26(A) Table — 900 mm/1.07 m/1.22 m or 3/3.5/4 ft by Voltage & Condition) | `requiredDepth` | 900 mm | 3 ft | mm, cm, m, in, ft, yd; range 0.75–1.5 m |

- **Equipment Width**: The width of the electrical equipment (panel, switchboard, etc.) requiring working clearance in front of it.
- **Required Clearance Depth (Per NEC 110.26(A) Table — 900 mm/1.07 m/1.22 m or 3/3.5/4 ft by Voltage & Condition)**: The minimum clear depth required in front of the equipment, from NEC Table 110.26(A)(1) based on nominal voltage-to-ground and installation condition.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Required minimum working clearance area** | 0.675 m² |
| Clear width used (NEC 110.26(A)(2) floor: 750 mm / 30 in) | 750 mm |

### US customary

| Result | Value |
|---|---|
| **Required minimum working clearance area** | 7.38 sq ft |
| Clear width used (NEC 110.26(A)(2) floor: 750 mm / 30 in) | 30 in |

- Confidence: medium.

## How it is worked out

Required depth depends on the equipment's nominal voltage-to-ground and the installation condition (1/2/3, based on what's opposite the equipment) per NEC Table 110.26(A)(1) — look up the correct depth for your specific installation rather than assuming a default. The width floor is stated by NEC 110.26(A)(2) as 750mm (30in) — two code figures, not a conversion of one another, since 30in is 762mm; the area here is worked from the 750mm figure, so if you are building to the imperial column allow the full 30in of width. Height clearance (2.0m/6.5ft minimum) is a separate NEC 110.26(E) requirement not covered by this floor-area calculation.

The working the page shows, in order: Clear width used (NEC 110.26(A)(2) floor: 750 mm / 30 in); then required minimum working clearance area.

The method, derived in full:

- [Earthing, Fault Current and Working Clearance](https://craftquantities.com/methodology/earthing-fault-current-and-clearance/): Why a ground rod cannot clear a fault, why doubling a rod's diameter achieves almost nothing, and why a LOWER available fault current can produce a more dangerous arc flash.

What this calculation does not cover:

- Gives a floor area, not the volume that has to stay clear. Above a switchboard or panelboard, NEC 110.26(E) keeps that same footprint dedicated to electrical use up to 1.8 m (6 ft) above the equipment or to the structural ceiling — no piping, no ducts, nothing foreign to the installation. A duct routed over the panel fails the room after the clearance in front of it was got right.
- Ignores what swings into the space. NEC 110.26(A)(2) requires the width to allow equipment doors and hinged panels to open at least 90 degrees, and a room door that swings back across the working space eats it. This is a clear floor area, not a strip that people, doors and storage may share.

A professional must decide:

- Gives a floor area, not the volume that has to stay clear. Above a switchboard or panelboard, NEC 110.26(E) keeps that same footprint dedicated to electrical use up to 1.8 m (6 ft) above the equipment or to the structural ceiling — no piping, no ducts, nothing foreign to the installation.
- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- NEC 110.26(A) requires a minimum clear working space in front of electrical equipment, with depth determined by voltage-to-ground and condition (typically 900 mm/3 ft, 1.07 m/3.5 ft, or 1.22 m/4 ft, which are the table's own paired figures rather than conversions of each other), and width the greater of the equipment width or 750mm/2.5ft

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is the clear width sometimes larger than the equipment itself?**

NEC 110.26(A) sets the required working space width as the greater of the equipment's own width or 750mm (2.5ft). For equipment narrower than 750mm, the code still requires the full 750mm of clear width in front of it.

**How do I know which required depth to use?**

From NEC Table 110.26(A)(1), by the equipment's nominal voltage-to-ground and the installation condition: 900 mm (3 ft), 1.07 m (3.5 ft) or 1.22 m (4 ft). The condition is 1, 2 or 3, based on what's opposite the equipment. This calculator does not look that value up for you, so enter the depth that applies to your specific installation.

**Does this calculator cover the required height clearance too?**

No — this only calculates the required clear floor area (width × depth) in front of the equipment. NEC 110.26(E) separately requires a minimum headroom clearance of 2.0m (6.5ft) above the working space, which is not part of this floor-area calculation.

## Related calculators

- [Home Electrical Service Panel Amperage Sizing Calculator](https://craftquantities.com/calculators/materials-quantities/service-panel-sizing-calculator/)
- [Electrical Room Transformer Heat Load Calculator](https://craftquantities.com/calculators/materials-quantities/electrical-room-heat-load-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/electrical-working-clearance-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/electrical-working-clearance-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `electrical-working-clearance-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/electrical-working-clearance-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/electrical-working-clearance-calculator/