# Domestic Water Pipe Sizing by Fixture Unit Calculator

> Size a domestic water pipe from its fixture unit load against both limits that govern it: the velocity ceiling and the pressure at the furthest fixture.

Page: https://craftquantities.com/calculators/materials-quantities/domestic-water-pipe-sizing-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.0, sources checked 2026-09-11, 4 published test vectors.

Minimum pipe diameter: 0.862 in for Total Water Supply Fixture Units 20, Demand Factor 3.2 and Fitting allowance 50, the page's opening figures; on the metric page, 20, 3.2 and 50 give 21.9 mm. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Total Water Supply Fixture Units (WSFU) | `totalFixtureUnits` | 20 | 20 | range 2–500 |
| Demand Factor (Calibration Constant for Your Fixture Mix) | `demandFactor` | 3.2 | 3.2 | range 2–5 |
| Maximum velocity | `maxVelocity` | 2.4 m/s | 7.87402 ft/s | ms, fpm, fps; range 1.2–3 m/s |
| Pressure available at the point of supply | `supplyPressure` | 413.685 kPa | 59.9999 psi | pa, kpa, mpa, psi, psf, in_wc; range 100000–1000000 Pa |
| Developed length to the furthest fixture | `developedLength` | 30 m | 98 ft | mm, cm, m, in, ft, yd; range 1–300 m |
| Fitting allowance (% added to the length) | `fittingAllowance` | 50 | 50 | range 0–200 |
| Height of the highest fixture above the supply | `staticLift` | 6 m | 19.5 ft | mm, cm, m, in, ft, yd; range 0–60 m |
| Pressure lost across the water meter | `meterLoss` | 34.474 kPa | 5.00003 psi | pa, kpa, mpa, psi, psf, in_wc; range 0–200000 Pa |
| Pressure needed at the furthest fixture | `requiredResidual` | 103.421 kPa | 14.9999 psi | pa, kpa, mpa, psi, psf, in_wc; range 20000–400000 Pa |
| Pipe material | `pipeMaterial` | Plastic — PEX, PB, PVC (C = 150) | Plastic — PEX, PB, PVC (C = 150) | `plastic`, `copper`, `galvanised` |

- **Total Water Supply Fixture Units (WSFU)**: The sum of water supply fixture unit values for every fixture served by this pipe segment.
- **Demand Factor (Calibration Constant for Your Fixture Mix)**: A calibration constant that scales the square-root approximation to your building's fixture mix.
- **Maximum velocity**: The maximum velocity allowed in the pipe to limit noise and water hammer risk.
- **Pressure available at the point of supply**: The pressure available where the supply enters the building.
- **Developed length to the furthest fixture**: The length of pipe from the point of supply to the furthest fixture, following the run.
- **Fitting allowance (% added to the length)**: How much extra length is added to represent the elbows, tees and valves in the run.
- **Height of the highest fixture above the supply**: The height of the highest fixture above the point of supply.
- **Pressure lost across the water meter**: The pressure the metering assembly loses at your design flow.
- **Pressure needed at the furthest fixture**: The flow pressure the furthest fixture needs at its inlet to work properly.
- **Pipe material**: Which Hazen-Williams roughness coefficient the friction calculation uses.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Minimum pipe diameter** | 21.9 mm |
| Estimated peak demand | 54.17 L/min |
| Diameter set by the velocity ceiling | 21.89 mm |
| Diameter set by the pressure budget | 19.47 mm |
| Pressure lost to static lift | 58,839.9 Pa |
| Pressure lost to friction at this diameter | 122,650.21 Pa |
| Pressure left at the furthest fixture | 197,720.89 Pa |
| Equivalent length used for friction | 45 m |

### US customary

| Result | Value |
|---|---|
| **Minimum pipe diameter** | 0.862 in |
| Estimated peak demand | 14.31 GPM |
| Diameter set by the velocity ceiling | 0.86 in |
| Diameter set by the pressure budget | 0.77 in |
| Pressure lost to static lift | 58,286.8 Pa |
| Pressure lost to friction at this diameter | 122,120.36 Pa |
| Pressure left at the furthest fixture | 198,803.83 Pa |
| Equivalent length used for friction | 147 ft |

- Confidence: medium.

## How it is worked out

Velocity governs this run. The diversified demand would fit through a smaller bore on pressure alone, but sustained velocity above the ceiling erodes the pipe and is audible through the building, so the velocity limit is the binding one and the pressure budget has room to spare.

The working the page shows, in order: Estimated peak demand; Diameter set by the velocity ceiling; Diameter set by the pressure budget; Pressure lost to static lift; Pressure lost to friction at this diameter; Pressure left at the furthest fixture; Equivalent length used for friction; then minimum pipe diameter.

The method, derived in full:

- [Flow, Velocity and Sizing a Duct or Pipe](https://craftquantities.com/methodology/flow-velocity-and-duct-or-pipe-sizing/): Why sizing a conduit is really choosing a velocity — capped above by noise and wear, held up from below by settlement — and then solving for the area.

What this calculation does not cover:

- Fixture-unit methods work because fixtures are used intermittently and rarely together. That diversity is the whole basis of the sizing, and it is why the pipe is far smaller than the sum of the fixture flows would suggest.
- Hunter's curve is old, and its age biases this in one direction. It was derived in the 1940s from fixtures using several times the water modern ones do, and it is well documented as oversizing systems built with low-flow fittings — the demand factor is the handle for that, and lowering it is a judgement with consequences rather than a correction.
- Excludes continuous-demand loads such as irrigation and hose bibs, which do not benefit from diversity and are added at their full flow.
- The friction calculation assumes one diameter for the whole run. A real system steps down as branches leave it, so the true loss is somewhere between this figure and the loss of a system sized entirely at the smallest branch — this is the screening answer, and a segment-by-segment calculation is the design one.
- Fitting losses are an allowance, not a count. Each elbow, tee and valve has its own equivalent length and a push-fit insert reduces the bore as well, so the percentage is a stand-in for a takeoff nobody has done. On a run with many tight bends it will understate the loss.
- The meter figure is yours to supply and this page cannot check it. Meter loss rises steeply as flow approaches the meter's rating and a backflow preventer or pressure-reducing valve often costs more than the meter itself; entering a nominal figure where the real assembly loses far more is the quiet way this calculation goes wrong.
- Velocity limits govern independently of flow: sustained velocities above roughly 2.4 m/s (8 ft/s) cause erosion and noise regardless of what the fixture units allow.
- The result is an internal diameter, not a pipe size. Nominal designations are not bores — copper, PEX and CPVC of the same nominal size have materially different internal diameters, and a push-fit system loses more at every joint — so take the next size up whose actual bore meets this figure in the material you are using.

A professional must decide:

- Water: supply and drainage design, and work on them, are for a licensed plumber under the local plumbing rules.

## Sources

As the calculator cites them (sources checked 2026-09-11):

- Estimated demand from fixture units (simplified Hunter's curve approximation) is converted to a minimum pipe diameter via the pipe flow area equation, keeping velocity within a safe range (commonly under ~2.4 m/s / 8 ft/s) to limit noise and water hammer risk
- Hazen-Williams equation (SI units): hf = 10.67 × L × Q^1.852 ÷ (C^1.852 × D^4.8704), used here to find the bore at which friction loss consumes the available pressure
- Static pressure loss = ρgh, at 1000 kg/m³ and 9.80665 m/s² — about 9.81 kPa, or 0.433 psi, per metre of lift
- Water supply fixture unit values are taken from the fixture unit table of the code in force — IPC Table E103.3(2) and UPC Table 610.3 differ, and this page does not reproduce either

The site's pages for the documents these name:

- [International Plumbing Code](https://craftquantities.com/standards/icc/ipc/)
- [Uniform Plumbing Code](https://craftquantities.com/standards/iapmo/upc/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is the pipe so much smaller than the total fixture flow?**

Because of diversity. Every fixture in a house adding up to well over 100 litres a minute is a real number, and it never happens — a WC fills for a minute, a tap runs for thirty seconds, and the probability that all of them coincide is vanishingly small. Fixture-unit methods encode that statistically, which is why a house with fifteen fixtures runs on a 25 mm supply rather than a 75 mm one.

**What does not get diversity applied to it?**

Anything that runs continuously. Irrigation, a hose bib left on, a filling tank — these have no intermittency to average out, so they are added at full flow on top of the diversified fixture demand. Missing this is the usual reason a system sized correctly on paper drops pressure whenever the garden is watered.

**Which of the two limits is actually deciding my size?**

The result says so, and it is worth reading before changing anything. If velocity governs, the pressure budget has room and a longer run or a higher fixture would not immediately hurt. If pressure governs, the bore is being driven by friction over the developed length — and shortening the run, cutting the fitting count or reducing the residual requirement will move the answer more than changing the pipe material will.

**Is Hunter's curve still appropriate?**

It is what the codes are built on and it is demonstrably conservative for modern fixtures. It was derived in the 1940s from fixtures that used several times the water a low-flow fitting does now, and the documented consequence is oversized services — which cost more, hold water longer and can raise stagnation concerns. The demand factor on this page is the honest handle for that: lower it if every fixture is genuinely low-flow, and understand you are departing from the table the inspector will check.

**How much pressure does height cost?**

About 9.81 kPa, or 0.433 psi, for every metre climbed, and it is unavoidable — it does not depend on the pipe, the flow or the material. A second-floor shower six metres above the service entry has already spent nearly 60 kPa before a single fitting has been passed, which is why the top floor is where a marginal system fails first.

**Why does my meter matter so much?**

Because its loss rises steeply as the flow approaches its rating, and it sits in series with everything else. A meter comfortably sized at average demand can cost a large share of the whole pressure budget at peak, and a backflow preventer or pressure-reducing valve in the same assembly commonly costs more again. On a system that fails only when several fixtures run together, the assembly is the first place to look.

**Does pipe material change the size?**

It can, through two different routes. Roughness changes friction loss, which this page models — though smoother pipe rarely buys a whole size. The bigger effect is bore: nominal designations are not internal diameters, and plastic systems with insert fittings lose significant bore at every joint, so a nominally equivalent size delivers less than copper of the same designation. Take the answer here as an internal diameter and find the size that actually provides it in your material.

## Related calculators

- [Water Meter Sizing Calculator (Fixture Units)](https://craftquantities.com/calculators/materials-quantities/water-meter-sizing-calculator/)
- [Domestic Water Pipe Friction Loss Calculator (Hazen-Williams)](https://craftquantities.com/calculators/materials-quantities/hazen-williams-friction-loss-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/domestic-water-pipe-sizing-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/domestic-water-pipe-sizing-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `domestic-water-pipe-sizing-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/domestic-water-pipe-sizing-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/domestic-water-pipe-sizing-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.