# Curtain Wall Mullion Tributary Dead Load Calculator

> Calculate the glass dead load carried by a curtain wall mullion from its tributary area.

Page: https://craftquantities.com/calculators/materials-quantities/curtain-wall-mullion-load-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-02, 2 published test vectors.

Mullion tributary dead load: 256 lb for Tributary Width 5 ft, Tributary Height 10 ft and Glass Weight per Area 5.12 lb/sq ft, the page's opening figures; on the metric page, 1.5 m, 3 m and 25 kg/m² give 113 kg. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Tributary Width | `tributaryWidth` | 1.5 m | 5 ft | mm, cm, m, in, ft, yd; range 0.01–3 m |
| Tributary Height | `tributaryHeight` | 3 m | 10 ft | mm, cm, m, in, ft, yd; range 0.01–6 m |
| Glass Weight per Area | `glassWeightPerArea` | 25 kg/m² | 5.1204 lb/sq ft | kgm2, lbft2; range 5–100 kg/m² |

- **Tributary Width**: The width of glass panel area that this mullion supports, typically half the spacing to each adjacent mullion.
- **Tributary Height**: The height of glass panel area that this mullion supports.
- **Glass Weight per Area**: About 25 kg/m² (5.1 lb/sq ft) for 10 mm glass. The glass makeup's surface density, including any laminated or insulated glass layers.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Mullion tributary dead load** | 113 kg |

### US customary

| Result | Value |
|---|---|
| **Mullion tributary dead load** | 256 lb |

## How it is worked out

The method, derived in full:

- [Glass, Insulating Units and the Curtain Wall](https://craftquantities.com/methodology/glazing-and-curtain-wall/): Why glass has no strength until you say how long the load lasts, why the edge of a sealed unit leaks more heat than the middle, and why a mullion's deflection limit protects the seal rather than the glass.

What this calculation does not cover:

- The answer is a mass — kilograms, or pounds once the imperial toggle is on — not a force. Convert it to a force before it enters any structural check, and do not paste it into the related mullion deflection calculator: that one asks for a horizontal wind line load per unit length, which is a different quantity from this vertical dead weight.
- Only the vertical dead weight of the glass is counted. Wind pressure, seismic and thermal movement, and any live or impact load sit outside this figure, and on most curtain wall mullions it is the wind bending case rather than the dead weight that sizes the section.
- The tributary-area split assumes equal panels centred on evenly spaced mullions and glazed on both sides. It does not hold at a building corner, at a jamb, or beside a door or opening where a mullion picks up glass on one side only, and it spreads the weight over an area when the glass actually lands on two setting blocks near the quarter points of the transom below.
- Nothing here checks where the weight goes once it reaches the mullion. The anchor, its bolts or embed, and the slab edge that receives it are a separate calculation, and whether the mullion is top-hung or bottom-bearing decides whether this dead load puts the section into tension or into compression, where buckling has to be checked as well.
- Tributary width is limited to 3 m (10 ft) and tributary height to 6 m (20 ft), capping the tributary area at 18 m² (194 sq ft). A mullion carrying glass through a two-storey atrium, or a module wider than 3 m, is outside those bounds — the field clamps the entry back to the limit and says so, and the load it then reports falls short of the real one in the same proportion.

A professional must decide:

- The answer is a mass — kilograms, or pounds once the imperial toggle is on — not a force. Convert it to a force before it enters any structural check, and do not paste it into the related mullion deflection calculator: that one asks for a horizontal wind line load per unit length, which is a different quantity from this vertical dead weight.
- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- Mullion tributary dead load = tributary width × tributary height × glass weight per unit area, the standard tributary-area method for assigning distributed load to a supporting structural member

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What is a mullion's tributary area?**

It's the portion of the surrounding glazed wall area that a given mullion is assumed to support — typically extending halfway to each neighboring mullion or support, using the standard tributary-area load-distribution method.

**Does this include the mullion's own self-weight?**

No — this calculates the glass dead load carried by the mullion from its tributary area only. The mullion's own weight and any additional attached components (gaskets, pressure plates, etc.) are separate and should be added if needed for a full dead load total.

**How do I find the glass weight per area for my makeup?**

Use the actual surface density of your specified glass makeup — for example, 10mm monolithic glass is roughly 25 kg/m². For laminated or insulated glass units, sum the surface densities of each pane and interlayer, or use the manufacturer's stated unit weight.

## Related calculators

- [Architectural Glass Weight Calculator](https://craftquantities.com/calculators/materials-quantities/architectural-glass-weight-calculator/)
- [Structural Glazing Mullion Wind Load Deflection Calculator](https://craftquantities.com/calculators/materials-quantities/mullion-deflection-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/curtain-wall-mullion-load-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/curtain-wall-mullion-load-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `curtain-wall-mullion-load-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/curtain-wall-mullion-load-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/curtain-wall-mullion-load-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.