# Curtain Wall Spandrel Condensation Risk Checker

> Check whether a curtain wall spandrel's interior glass surface temperature stays above the dew point under winter design conditions.

Page: https://craftquantities.com/calculators/materials-quantities/curtain-wall-condensation-checker/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-06, 2 published test vectors.

Interior glass surface temperature: 57.2 °F for Interior Design Temperature 69.8 °F and Exterior Winter Design Temperature 14 °F, the page's opening figures, to compare with the limit shown with it; a comparison, not a check. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Interior Design Temperature | `interiorTemp` | 21 °C | 69.8 °F | c, f, k; range 15–25 °C |
| Exterior Winter Design Temperature | `exteriorTemp` | -10 °C | 14 °F | c, f, k; range -40–5 °C |
| Assembly U-Factor (W/m²K) | `uFactor` | 1.8 | 1.8 | range 0.8–4 |
| Interior Film Coefficient (W/m²K, commonly 8) | `interiorFilmCoefficient` | 8 | 8 | range 5–12 |
| Interior Air Dew Point | `dewPoint` | 10 °C | 50 °F | c, f, k; range -5–20 °C |

- **Interior Design Temperature**: The interior air design temperature used for the winter condensation check.
- **Exterior Winter Design Temperature**: The exterior winter design temperature for the project location, typically a 97.5% or 99% design condition.
- **Assembly U-Factor (W/m²K)**: The overall U-factor of the spandrel/vision glass assembly being checked.
- **Interior Film Coefficient (W/m²K, commonly 8)**: The interior air film coefficient, commonly taken as 8 W/m²K per standard convention.
- **Interior Air Dew Point**: The dew point of the interior air, based on its temperature and relative humidity.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Interior glass surface temperature** | 14 °C |
| Interior air dew point | 10 °C |

### US customary

| Result | Value |
|---|---|
| **Interior glass surface temperature** | 57.2 °F |
| Interior air dew point | 50 °F |

- Confidence: medium.
- The figure is compared against a limit; that is a check of the number, not an approval.

## How it is worked out

The calculated interior glass surface temperature stays above the interior air's dew point shown below, so condensation is not predicted under these steady-state design conditions. This checks room-side vision/spandrel glass surface condensation risk only, per NFRC 500/AAMA 1503 steady-state methodology. Shadowbox CAVITY condensation — a distinct, common failure mode driven by trapped cavity moisture and solar vapor drive behind the spandrel panel — is NOT covered here and needs separate ventilation/vapor analysis per GANA/NGA guidance. No risk predicted under these conditions is not the same as none. The conditions are the ones you entered, and one surface is not the assembly.

The working the page shows, in order: Interior air dew point; then interior glass surface temperature.

The method, derived in full:

- [Glass, Insulating Units and the Curtain Wall](https://craftquantities.com/methodology/glazing-and-curtain-wall/): Why glass has no strength until you say how long the load lasts, why the edge of a sealed unit leaks more heat than the middle, and why a mullion's deflection limit protects the seal rather than the glass.

What this calculation does not cover:

- Models conduction only. Warm indoor air pushed out through an imperfect air seal — a splice joint, an anchor pocket, a gasket that has taken a set — carries far more moisture into the assembly than diffusion does, and it condenses wherever it cools rather than on the face being checked. A wall that passes on paper can still run with water, or ice, inside the mullion, and the first sign of it is usually a stain at the head of the panel below.
- Uses the exterior air temperature, and the outer surface does not sit at it. On a clear, calm night the glass radiates to the sky and settles several degrees below the surrounding air, which drags the interior surface down with it — and those are exactly the nights condensation forms. A result that clears the dew point by a degree or two at the design air temperature has no margin left for the sky.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Steady-state condensation risk check per AAMA 1503/NFRC 500 methodology: interior surface temperature Ts = Ti − U×(Ti−To)/hi, where Ti/To are interior/exterior design temperatures, U is the assembly's overall U-factor, and hi is the interior air film coefficient (commonly 8 W/m²K); condensation risk exists if Ts falls below the interior air's dew point

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What does this calculator actually check?**

It estimates the steady-state interior glass surface temperature of a curtain wall spandrel or vision glass assembly under winter design conditions, using the NFRC 500/AAMA 1503 methodology, and compares it against the interior air's dew point. If the surface temperature falls below the dew point, condensation is predicted on the room-side glass surface.

**Does passing this check mean the spandrel panel is free of condensation risk everywhere?**

No. This checks room-side vision glass surface risk only. Shadowbox cavity condensation — moisture trapped behind the spandrel panel, often driven by solar vapor drive — is a separate and common failure mode that this tool does not evaluate. That risk needs its own ventilation and vapor-drive analysis per GANA/NGA guidance.

**Where does the interior film coefficient value come from?**

8 W/m²K is a commonly used interior air film coefficient in this type of steady-state check, but actual values can vary with air movement near the glass (e.g. from HVAC diffusers or blinds). Use a project-specific value if one has been established.

## Related calculators

- [Dew Point and Relative Humidity Calculator (with the Coating Surface Check)](https://craftquantities.com/calculators/materials-quantities/dew-point-calculator/)
- [Blast-Resistant Fenestration Rating Checker](https://craftquantities.com/calculators/materials-quantities/blast-glazing-rating-checker/)
- [Window Heat Loss Savings Calculator](https://craftquantities.com/calculators/insulation-efficiency/window-heat-loss-savings-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/curtain-wall-condensation-checker` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/curtain-wall-condensation-checker` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `curtain-wall-condensation-checker`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/curtain-wall-condensation-checker.json

---
Source: https://craftquantities.com/calculators/materials-quantities/curtain-wall-condensation-checker/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.