# Corrugated Metal Decking Span Deflection Checker

> Check corrugated steel deck deflection against a code limit, using your deck's own effective moment of inertia.

Page: https://craftquantities.com/calculators/materials-quantities/corrugated-decking-deflection-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-05, 2 published test vectors.

Calculated deflection: 0.0332 in for Uniform Load per Meter of Width 3000 and Effective Moment of Inertia I 20, the page's opening figures, to compare with the limit shown with it; a comparison, not a check. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Uniform Load per Meter of Width (N/m) | `udl` | 3000 | 3000 | range 100–30000 |
| Span | `span` | 3 m | 10 ft | mm, cm, m, in, ft, yd; range 0.01–8 m |
| Effective Moment of Inertia I (×10⁶ mm⁴ per m width) | `momentOfInertia` | 20 | 20 | range 0.1–500 |
| Deflection Limit | `deflectionLimitRatio` | L/240 | L/240 | `180`, `240`, `360` |

- **Uniform Load per Meter of Width (N/m)**: The uniformly distributed load per meter of deck width.
- **Span**: The deck's clear span between supports.
- **Effective Moment of Inertia I (×10⁶ mm⁴ per m width)**: The deck's effective moment of inertia per meter of width, from the manufacturer's or SDI's span table.
- **Deflection Limit**: The applicable code deflection limit, as a fraction of the span.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Calculated deflection** | 0.791 mm |
| Allowable limit | 12.5 mm |

### US customary

| Result | Value |
|---|---|
| **Calculated deflection** | 0.0332 in |
| Allowable limit | 0.5 in |

- Confidence: medium.
- The figure is compared against a limit; that is a check of the number, not an approval.

## How it is worked out

The deflection this deck works out to is below the deflection limit for the span entered shown with it — you entered it from the limit ratio you chose. The effective moment of inertia has to come from the deck manufacturer's or the SDI's own span table for this exact profile and gauge, not from a computed section property. Being under one limit is not a design. Nothing else is checked here — not the other limit states, not the connections, not the member the load arrives from.

The working the page shows, in order: Allowable limit; then calculated deflection.

The method, derived in full:

- [Deflection, Creep and Vibration: What Governs a Span](https://craftquantities.com/methodology/deflection-and-vibration/): Why doubling a span multiplies its deflection by sixteen, why a stronger grade of steel does nothing for it, and why a floor that passes every deflection check can still be unacceptable to walk on.

What this calculation does not cover:

- The check is deflection alone. Nothing here tests bending capacity, shear, or web crippling where the sheet bears on a narrow support flange, and published deck span tables are frequently governed by crippling or flexure rather than by sag, so a profile can clear this ratio and still fail the check that actually sets its allowable span.
- The 5wL⁴/384EI expression is the single simply supported span, pinned at both ends. A deck sheet lapped continuously over two or three supports deflects only about 40 to 55 per cent as much under the same span and load, so deflection for a continuous layout is overstated here, while cantilevered edge overhangs, unequal adjacent spans and sheets that stop mid-bay are not represented at all.
- The limit you select is applied to whatever load you typed, and the page does not link the two. Codes commonly pair the tighter ratio with live load acting alone and the looser one with the full service load, so entering dead plus live and choosing L/360 tests a combination no code asks for. Only ratio limits are offered, so an absolute cap on deflection, of the kind imposed on composite deck under wet concrete, cannot be checked here at all.
- The effective moment of inertia is treated as one fixed number. For cold-formed decking it is stress-dependent, because the wide compression flange buckles locally and only part of its width stays effective, and composite deck tables publish separate values for the bare sheet under wet concrete and for the finished composite slab. E is likewise fixed at 200,000 MPa (29,000 ksi), so steel at elevated temperature and the long-term creep and shrinkage movement of a concrete topping are outside this.
- The result is the deck's sag between its own two supports, not the movement a floor or ceiling actually sees. The joists or beams carrying the deck deflect as well and the two add at any point below, and where that combined sag collects rainwater or wet concrete the added weight deepens it further, a feedback loop this single-pass calculation does not iterate.

## Sources

As the calculator cites them (sources checked 2026-09-05):

- Steel Deck Institute Floor/Roof Deck Design Manuals: Δ = 5wL⁴/(384EI) applied per unit width, with E = 200,000 MPa; effective moment of inertia (I) is profile- and gauge-specific and must come from the deck manufacturer's or SDI's own span table — it cannot be derived from a general formula

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Where do I get the effective moment of inertia for my deck?**

From the manufacturer's or the Steel Deck Institute's (SDI) span table for your exact deck profile and gauge — effective moment of inertia for corrugated decking depends on the specific corrugation geometry and cannot be derived from a general formula.

**Why is the modulus of elasticity fixed at 200,000 MPa?**

200,000 MPa (200 GPa) is the standard modulus of elasticity for structural steel, so it is fixed rather than entered by the user for this calculator.

**What's the difference between the L/180 and L/360 limits?**

L/360 is a tighter limit typically applied where finishes or ceilings below are sensitive to movement, while L/180 is a looser limit sometimes permitted for roof decks without such finishes — confirm which limit applies under your project's governing code.

## Related calculators

- [Glulam Beam Deflection Checker](https://craftquantities.com/calculators/materials-quantities/glulam-beam-deflection-calculator/)
- [Roof/Floor Deflection Limit Calculator](https://craftquantities.com/calculators/materials-quantities/roof-deflection-limit-calculator/)
- [Steel Deck Support Beam Spacing Calculator](https://craftquantities.com/calculators/materials-quantities/steel-deck-support-spacing-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/corrugated-decking-deflection-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/corrugated-decking-deflection-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `corrugated-decking-deflection-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/corrugated-decking-deflection-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/corrugated-decking-deflection-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.