# Feeder Conductor Ampacity Derating Calculator

> Calculate a conductor's derated ampacity after applying ambient temperature and conductor-count correction factors.

Page: https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Derated conductor ampacity: 91.5 A for Base Conductor Ampacity 130, Ambient Temperature Correction Factor (Per NEC 310.15(B)) 0.88 and Conductor Count Adjustment Factor (Per NEC Table 310.15(C)(1)) 0.8, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Base Conductor Ampacity (A, from NEC Table 310.16) | `baseAmpacity` | 130 | 130 | range 10–500 |
| Ambient Temperature Correction Factor (Per NEC 310.15(B)) | `tempCorrectionFactor` | 0.88 | 0.88 | range 0.5–1.3 |
| Conductor Count Adjustment Factor (Per NEC Table 310.15(C)(1)) | `conductorCountFactor` | 0.8 | 0.8 | range 0.35–1 |

- **Base Conductor Ampacity (A, from NEC Table 310.16)**: The conductor's tabulated ampacity before any correction or adjustment factors are applied.
- **Ambient Temperature Correction Factor (Per NEC 310.15(B))**: The multiplier for the ambient temperature the conductor will actually operate in, from the applicable NEC temperature correction table.
- **Conductor Count Adjustment Factor (Per NEC Table 310.15(C)(1))**: The multiplier for the number of current-carrying conductors bundled together in the same raceway or cable.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Derated conductor ampacity** | 91.5 A |

### US customary

| Result | Value |
|---|---|
| **Derated conductor ampacity** | 91.5 A |

- Confidence: medium.

## How it is worked out

Verify both correction factors directly against the current NEC tables for your specific ambient temperature and number of current-carrying conductors — this calculator applies factors you supply, it does not look them up for you.

The method, derived in full:

- [Voltage Drop and Conductor Sizing](https://craftquantities.com/methodology/voltage-drop-and-conductor-sizing/): Why the run length doubles, why a 12 V circuit suffers a hundred times the percentage loss of a 120 V one, and why ampacity answers a different question entirely.

What this calculation does not cover:

- Derating and terminations are two separate ceilings and the lower one governs. NEC 110.14(C) holds the conductor to the 60°C or 75°C column for whatever the breaker and lugs are listed at, so a run derated down from the 90°C column can still not be used above its 75°C table value — the number this page returns may legitimately be higher than the ampacity you are allowed to claim.
- The adjustment factor you type depends on a conductor count this page cannot verify. Equipment grounding conductors and the neutral of a balanced circuit are not current-carrying, while the neutral of a three-phase, four-wire wye feeding significant nonlinear load is — reclassifying one conductor can drop you a whole band in Table 310.15(C)(1). The adjustment also does not apply at all through a nipple of 24 in (610 mm) or less.
- A derated ampacity proves nothing by itself. It still has to cover the load it serves at 125 percent of the continuous portion, sit correctly with the overcurrent device protecting it, and survive a voltage drop check over the length of the run. This page stops one step before all three.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Derated ampacity = base conductor ampacity × ambient temperature correction factor × conductor bundling/count adjustment factor, per NEC 310.15(B) temperature correction tables and NEC Table 310.15(C)(1) adjustment factors for more than 3 current-carrying conductors in a raceway

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does a conductor need to be derated below its table ampacity?**

The NEC's base ampacity tables (like Table 310.16) assume a specific ambient temperature and a limited number of current-carrying conductors. When the actual ambient temperature is higher, or more current-carrying conductors are bundled together in the same raceway or cable, both effects reduce the conductor's heat dissipation, so NEC 310.15(B) and Table 310.15(C)(1) require applying correction and adjustment factors to find the safe derated ampacity.

**Where do I get the correction and adjustment factor values?**

The ambient temperature correction factor comes from the NEC 310.15(B) temperature correction table for your conductor's insulation rating and the expected ambient temperature. The conductor count adjustment factor comes from NEC Table 310.15(C)(1), based on the number of current-carrying conductors in the same raceway, cable, or earth. This calculator applies the factors you enter — it does not look them up for you.

**Can I apply both factors at once?**

Yes — when both elevated ambient temperature and conductor bundling apply to the same run, NEC 310.15 requires applying both correction factors together (multiplying the base ampacity by each), exactly as this calculator does.

## Related calculators

- [Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)](https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/)
- [Conduit Fill Calculator](https://craftquantities.com/calculators/electrical/conduit-fill-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/conductor-ampacity-derating-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/conductor-ampacity-derating-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `conductor-ampacity-derating-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/conductor-ampacity-derating-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/