# Collar Tie Wind Uplift Tension Calculator

> Estimate tension force in a roof collar tie from wind uplift pressure and tributary area.

Page: https://craftquantities.com/calculators/materials-quantities/collar-tie-uplift-tension-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-06, 2 published test vectors.

Collar tie tension force: 2.69 kips for Wind Uplift Pressure 31.33 psf and Tributary Roof Area per Tie 86 sq ft, the page's opening figures; on the metric page, 1.5 kPa and 8 m² give 12 kN. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Wind Uplift Pressure | `upliftPressure` | 1.5 kPa | 31.3282 psf | pa, kpa, mpa, psi, psf, in_wc; range 200–5000 Pa |
| Tributary Roof Area per Tie | `tributaryArea` | 8 m² | 86 sq ft | m2, ft2, mm2, in2; range 0.01–40 m² |
| Number of Ties Sharing This Load | `numberOfTies` | 1 | 1 | range 1–4 |

- **Wind Uplift Pressure**: The design wind uplift pressure acting on the roof.
- **Tributary Roof Area per Tie**: The roof area whose uplift load is carried by this collar tie.
- **Number of Ties Sharing This Load**: How many collar ties share the tributary area's uplift load.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Collar tie tension force** | 12 kN |

### US customary

| Result | Value |
|---|---|
| **Collar tie tension force** | 2.69 kips |

- Confidence: medium.

## How it is worked out

Simplified tributary-area estimate — a full load path/connection analysis by a structural engineer is recommended for critical uplift connections.

The method, derived in full:

- [Snow, Uplift and the Roof's Load Path](https://craftquantities.com/methodology/roof-loads-and-the-load-path/): Why a warm sheltered roof carries more snow than an exposed cold one, why building next to an existing low roof can overload it without touching it, and why a collar tie and a rafter tie are not the same member.

What this calculation does not cover:

- One uplift pressure is applied to every tie on the roof. Component-and-cladding pressures are not uniform: the ridge, eaves, hips and corner zones carry substantially more than the field of the roof, often half again or double, so the ties nearest those edges see more than this figure and the ones in the middle see less.
- The result is gross uplift with nothing set against it. The roof's own weight resists lifting and the wind combination credits part of it — 0.6 dead against 0.6 wind in allowable stress design — so tension taken straight from a pressure overstates the net force. It can also understate it: if the pressure entered is external only, internal pressure in a partially enclosed or breached building pushes up from underneath and adds to it.
- The force lands in the tie, but the tie is not what fails. Collar ties come apart at their nails, so this figure has to be converted into a fastener count using the lateral design value for that nail in that species and member thickness, with end and edge distance enough to develop it — three nails in a 2x4 is a habit rather than a capacity.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Simplified tributary-area method: tie tension = uplift pressure × tributary roof area ÷ number of ties sharing that tributary area

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does wind create tension in a collar tie?**

Wind uplift pressure tends to lift the roof rafters upward and outward; the collar tie resists this by developing tension force, transferring the uplift load down through its connections at each rafter.

**How is the tributary area determined?**

It's the portion of roof area whose uplift load is carried by this specific collar tie — generally the tie spacing multiplied by the horizontal distance the tie's connection influences on the roof.

**Is this a full structural design check?**

No — it's a simplified tributary-area estimate only. Critical uplift connections should be verified with a full load path and connection analysis by a structural engineer.

## Related calculators

- [Ground-to-Roof Snow Load Calculator](https://craftquantities.com/calculators/materials-quantities/roof-snow-load-calculator/)
- [King Post Truss Member Length Calculator](https://craftquantities.com/calculators/materials-quantities/king-post-truss-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/collar-tie-uplift-tension-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/collar-tie-uplift-tension-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `collar-tie-uplift-tension-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/collar-tie-uplift-tension-calculator.json

---