# Cleanroom HEPA Airflow & Face Velocity Calculator

> Calculate the required supply airflow and HEPA filter face velocity for a cleanroom, based on a target air-changes-per-hour rate by ISO class.

Page: https://craftquantities.com/calculators/materials-quantities/cleanroom-hepa-airflow-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-06, 2 published test vectors.

Required supply airflow: 3,330 CFM for Cleanroom volume 2000 ft³, the page's opening figures; on the metric page, 56.63 m³ gives 1,570 L/s. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Cleanroom volume | `roomVolumeFt3` | 56.6337 m³ | 2000 ft³ | l, gal, m3, ft3, yd3; range 0.1–1415840 L |
| Target Air Changes per Hour (ACH) | `airChangesPerHour` | 100 | 100 | range 10–500 |
| Total HEPA filter face area | `filterFaceArea` | 3.71612 m² | 40 sq ft | m2, ft2, mm2, in2; range 0.01–46.4515 m² |

- **Cleanroom volume**: The cleanroom's total enclosed volume.
- **Target Air Changes per Hour (ACH)**: How many times the room's full air volume is supplied per hour.
- **Total HEPA filter face area**: The combined open face area of all HEPA supply filters in the ceiling grid.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Required supply airflow** | 1,570 L/s |
| HEPA filter face velocity | 0.42 m/s |

### US customary

| Result | Value |
|---|---|
| **Required supply airflow** | 3,330 CFM |
| HEPA filter face velocity | 83.33 ft/min |

- Confidence: medium.

## How it is worked out

The ACH-by-ISO-class ranges are industry design guidance (IEST-RP-CC012.3), not an ISO 14644-1 requirement — ISO 14644-1 itself only sets particle-concentration limits, not airflow rates. Final design ACH depends on process particle generation, occupancy, and equipment heat load, and should be verified by the project's cleanroom design engineer. ISO 5 spaces are often designed as unidirectional/laminar flow at a target face velocity instead of a pure ACH value.

The working the page shows, in order: HEPA filter face velocity; then required supply airflow.

The method, derived in full:

- [Containment, Capture and Process Airflow](https://craftquantities.com/methodology/containment-and-process-airflow/): Why a leaky asbestos enclosure needs more air rather than less, why an island cooker hood needs far more than a wall one, and why a powered attic fan can pull conditioned air out of the house it is cooling.

What this calculation does not cover:

- This is total supply air, most of which is recirculated, and it says nothing about the outside air that holds the room positive against everything around it. The pressure cascade a cleanroom lives on — on the order of 5 to 15 Pa per classification step — is set by leakage through doors, pass-throughs and the envelope plus whatever process exhaust is drawn off, and a room supplied at exactly this rate with no offset loses its differential the first time a door swings.
- Air changes are a design input, not the acceptance result. The room is signed off on particle counts, and those depend on where the low-wall returns sit, how cleanly the air sweeps past benches and equipment, and how the space is gowned and operated — a room can hit this CFM exactly and still fail its classification because the supply short-circuits straight back to the ceiling.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Required airflow (CFM) = Room Volume (ft³) × Air Changes per Hour ÷ 60; Face Velocity (ft/min) = Airflow ÷ HEPA Filter Face Area. Typical ACH design ranges by ISO 14644-1 cleanliness class come from secondary design guidance (IEST-RP-CC012.3 'Considerations in Cleanroom Design' and established industry practice, NOT from ISO 14644-1 itself, which sets only particle-concentration limits): roughly ISO 8 → 10-30 ACH, ISO 7 → 30-65 ACH, ISO 6 → 80-150 ACH, ISO 5 → 200-480 ACH (ISO 5 is often instead designed as unidirectional/laminar flow at ~40-80 fpm face velocity rather than a pure ACH target).

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**How is the required cleanroom airflow calculated?**

Required airflow (CFM) equals the room's volume in cubic feet multiplied by the target air changes per hour (ACH), divided by 60 minutes — the same room-volume-times-ACH method used for general ventilation, applied here to cleanroom HEPA supply.

**Where do the typical ACH ranges by ISO class come from?**

They come from secondary design guidance such as IEST-RP-CC012.3 and established industry practice — not from ISO 14644-1 itself, which only sets particle-concentration limits and does not specify airflow rates. Roughly: ISO 8 → 10-30 ACH, ISO 7 → 30-65 ACH, ISO 6 → 80-150 ACH, ISO 5 → 200-480 ACH.

**Why does the result also show a face velocity?**

Face velocity (airflow ÷ total HEPA filter face area) confirms the filter bank size is adequate for the required airflow. ISO 5 spaces are often instead designed directly as unidirectional/laminar flow at a target face velocity (roughly 40-80 ft/min) rather than a pure ACH target, so final design ACH and face velocity should always be verified by the project's cleanroom design engineer.

## Related calculators

- [HEPA Filter Bank Pressure Drop Estimator](https://craftquantities.com/calculators/materials-quantities/hepa-filter-pressure-drop-calculator/)
- [Air Changes Per Hour (ACH50) Calculator](https://craftquantities.com/calculators/insulation-efficiency/air-changes-per-hour-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/cleanroom-hepa-airflow-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/cleanroom-hepa-airflow-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `cleanroom-hepa-airflow-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/cleanroom-hepa-airflow-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/cleanroom-hepa-airflow-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.