# Hydronic Air/Dirt Separator Sizing Calculator

> Calculate the minimum connection size for a hydronic air/dirt separator at the system's design flow rate.

Page: https://craftquantities.com/calculators/materials-quantities/air-dirt-separator-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-06, 2 published test vectors.

Minimum connection diameter: 5.73 in for Maximum Velocity for Effective Separation 0.98 ft/s, the page's opening figures; on the metric page, 0.3 m/s gives 146 mm. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| System Flow Rate | `systemFlowRate` | 300 L/min | 79 gal/min | lpm, lps, gpm; range 20–3000 L/min |
| Maximum Velocity for Effective Separation | `maxVelocity` | 0.3 m/s | 0.984252 ft/s | ms, fpm, fps; range 0.1–0.6 m/s |

- **System Flow Rate**: The hydronic system's design flow rate through the separator.
- **Maximum Velocity for Effective Separation**: The maximum velocity through the separator's connection for effective air and dirt removal — commonly around 0.3 m/s (about 1 ft/s).

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Minimum connection diameter** | 146 mm |

### US customary

| Result | Value |
|---|---|
| **Minimum connection diameter** | 5.73 in |

- Confidence: medium.

## How it is worked out

Effective air/dirt separation requires low velocity at the separator itself — confirm the manufacturer's rated maximum velocity and connection size for your specific separator model rather than assuming a generic value.

The method, derived in full:

- [Flow, Velocity and Sizing a Duct or Pipe](https://craftquantities.com/methodology/flow-velocity-and-duct-or-pipe-sizing/): Why sizing a conduit is really choosing a velocity — capped above by noise and wear, held up from below by settlement — and then solving for the area.

What this calculation does not cover:

- Position beats size here. Air leaves solution where the water is hottest and the pressure lowest — on most systems the boiler or chiller outlet, upstream of the circulator. Put the same separator on the cool return and it sees air still dissolved and passes it straight through. No connection diameter compensates for the wrong location; the low velocity sized here only earns its keep once the bubbles actually exist.
- This is a connection diameter, not a pressure drop. Every separator adds head to the circuit — the vessel, the coalescing medium inside it, and the expansion and contraction at each end — and none of that comes back from a velocity formula. A pump selected on pipe friction alone can land short of its duty point once the separator, the strainer and the dirt the separator will eventually be holding are all counted in.
- The dirt half is a different problem from the air half. What blocks a modern condensing boiler's heat exchanger is magnetite — fine ferrous sludge that a gravity pocket catches poorly and a magnet catches well — and no velocity calculation tells you whether you need the magnetic version. Nor does it size the dirt pocket or set how often it is flushed: a separator that is never blown down is a reservoir, not a filter.

## Sources

As the calculator cites them (sources checked 2026-09-06):

- Minimum connection diameter = √(4×system flow rate ÷ (π×maximum velocity)), sizing the separator's pipe connection to keep flow velocity low enough (commonly under ~0.3-0.6 m/s) for effective air and particulate separation

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does an air/dirt separator need such a low design velocity compared to regular pipe?**

Air and dirt separators work by giving entrained air bubbles time to rise and particulates time to settle out of the flow stream — that only happens effectively at low velocity, commonly around 0.3 m/s, far below the velocities typically allowed in ordinary hydronic piping.

**Is the connection size the same as the rest of the system's pipe size?**

Not necessarily — because the separator needs a much lower velocity than the main piping, its connection is often sized larger than the adjoining pipe to slow the flow down as it passes through the unit.

**Should I use the manufacturer's rated size instead of this calculation?**

Yes — this is a general velocity-based estimate. Confirm the actual rated maximum velocity and connection size for your specific separator model against the manufacturer's data before final selection.

## Related calculators

- [Hydronic Closed-Loop Expansion Tank Sizing Calculator](https://craftquantities.com/calculators/materials-quantities/hydronic-expansion-tank-calculator/)
- [Hydronic Circulator Pump Head Loss Calculator](https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/air-dirt-separator-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/air-dirt-separator-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `air-dirt-separator-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/air-dirt-separator-calculator.json

---
Source: https://craftquantities.com/calculators/materials-quantities/air-dirt-separator-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.