# U-Value to R-Value Calculator

> Convert a U-value from a specification or datasheet into the R-value used on insulation labelling.

Page: https://craftquantities.com/calculators/insulation-efficiency/u-value-to-r-value-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Equivalent R-value: 20 hr·ft²·°F/BTU for U-value 0.05, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| U-value (BTU/hr·ft²·°F) | `uValue` | 0.05 | 0.05 | range 0.001–5 |

- **U-value (BTU/hr·ft²·°F)**: The assembly's thermal transmittance, as specified.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Equivalent R-value** | 20 hr·ft²·°F/BTU |

### US customary

| Result | Value |
|---|---|
| **Equivalent R-value** | 20 hr·ft²·°F/BTU |

## How it is worked out

R = 1 ÷ U, the exact inverse relationship. The result is the whole assembly's resistance — subtract the other layers before choosing an insulation thickness.

The method, derived in full:

- [Unit Conversion, Exactness and Rounding](https://craftquantities.com/methodology/unit-conversion-and-rounding/): Why most conversion factors carry no uncertainty at all, which ones hide a material assumption, and why converting a measurement can never make it more precise than it was.

What this calculation does not cover:

- The conversion is arithmetic and takes the U-value at face value. It does not check that you have the right figure for the element: a window's whole-unit U-factor, its centre-of-glass value and its frame value are three different numbers, and only the whole-unit one describes what the opening actually loses.
- The field is imperial only, and the site's metric/imperial toggle does not convert it. A W/m2K figure typed in unchanged returns the metric resistance in m2K/W, which is about a fifth of the imperial R the result is labelled as. Divide a metric U-value by 5.678 before entering it.
- Thermal bridging is not in the number. A U-value quoted for a clear-wall build-up excludes studs, joists, rim boards, lintels and junctions, so the R returned describes the insulated bay rather than the whole element.
- This is not a code compliance check. It does not test the figure against any energy code's prescriptive U-factor or R-value tables, and it does not perform the area-weighted or trade-off calculation a submission needs.
- Steady-state conduction only: no air leakage, no thermal mass, no moisture. Insulation that is compressed, wind-washed or damp delivers less than its rated R, and a reciprocal cannot show that.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- R = 1 / U, the reciprocal of thermal transmittance
- Imperial U (BTU/hr-ft2-F) and metric U (W/m2K) differ by a factor of about 5.678

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**My specification is in W/m²K. Can I use it here?**

Not directly — that is the metric U-value and is about 5.678 times the imperial figure, so divide by 5.678 before entering it. Enter it raw and the R-value comes out roughly five times too LOW, not too high: a 0.18 W/m²K wall reads 5.6 instead of its true imperial R-31.5, making a well-insulated assembly look barely insulated at all. The error is pessimistic, which is why it tends to be noticed — but it is still wrong by a factor of 5.678.

**Does the resulting R-value match the insulation I need to buy?**

Not on its own. The converted figure is the whole assembly's resistance, and the insulation only has to make up the difference between that and what the other layers already provide. Subtract the existing layers before specifying a product.

**Why do regulations specify U rather than R?**

Because a maximum U-value sets a performance ceiling on the finished assembly regardless of how it is built up, which is what a regulator wants. R-value labelling describes a single product, which is what a manufacturer wants.

## Related calculators

- [R-Value to U-Value Calculator](https://craftquantities.com/calculators/insulation-efficiency/r-value-to-u-value-calculator/)
- [R-Value Calculator](https://craftquantities.com/calculators/insulation-efficiency/r-value-calculator/)
- [Continuous Insulation Thermal Bridging Calculator (Z-Furring)](https://craftquantities.com/calculators/materials-quantities/ci-thermal-bridging-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/u-value-to-r-value-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/u-value-to-r-value-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `u-value-to-r-value-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/u-value-to-r-value-calculator.json

---
Source: https://craftquantities.com/calculators/insulation-efficiency/u-value-to-r-value-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.