# Surface Temperature Factor (fRsi) Calculator (BS EN ISO 13788, BRE IP 1/06)

> The surface temperature factor fRsi, from a U-value or a surface temperature, beside the critical factor BRE IP 1/06 sets for the building type.

Page: https://craftquantities.com/calculators/insulation-efficiency/surface-temperature-factor-frsi-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-09-22, 8 published test vectors.

Temperature factor fRsi: 0.925 ratio for U-Value of the Element 0.05 BTU/(hr·ft²·°F), Internal Surface Resistance Rsi 1.42 hr·ft²·°F/BTU and Internal Temperature 68 °F, the page's opening figures; on the metric page, 0.3 W/m²K, 0.25 m²K/W and 20 °C give 0.925 ratio. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| What You Know About the Surface | `method` | A plane element's U-value | A plane element's U-value | `u-value`, `temperatures` |
| U-Value of the Element | `uValue` | 0.3 W/m²K | 0.0528331 BTU/(hr·ft²·°F) | w_m2k, btu_h_ft2_f; range 0.05–7 W/m²K |
| Internal Surface Resistance Rsi | `rsi` | 0.25 m²K/W | 1.41957 hr·ft²·°F/BTU | m2k_w, h_ft2_f_btu; range 0.04–1 m²K/W |
| Internal Temperature | `insideTemp` | 20 °C | 68 °F | c, f, k; range 5–35 °C |
| External Temperature | `outsideTemp` | 0 °C | 32 °F | c, f, k; range -30–25 °C |
| Internal Surface Temperature | `surfaceTemp` | 15 °C | 59 °F | c, f, k; range -30–35 °C |
| Building Type (for the Critical Factor) | `buildingType` | Dwellings, residential buildings and schools | Dwellings, residential buildings and schools | `storage`, `office`, `dwelling`, `sports-kitchen`, `pool-laundry` |

- **What You Know About the Surface**: A flat wall or roof away from junctions follows from its U-value; a junction needs a surface temperature from a model or a measurement.
- **U-Value of the Element**: The element's thermal transmittance, surface resistances included.
- **Internal Surface Resistance Rsi**: The surface film the factor is worked with — larger than the one used for heat loss, on purpose.
- **Internal Temperature**: The room's temperature — strictly the operative temperature, the mean of the air and the surrounding surfaces.
- **External Temperature**: The outdoor air temperature for the day or month being assessed.
- **Internal Surface Temperature**: The coldest point of the surface, read on site or taken from a thermal model.
- **Building Type (for the Critical Factor)**: BRE IP 1/06 sets a critical factor by the humidity the building's use generates.

`uValue` applies only when `method` is `u-value`.
`rsi` applies only when `method` is `u-value`.
`surfaceTemp` applies only when `method` is `temperatures`.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Temperature factor fRsi** | 0.925 ratio |
| Surface temperature at these air temperatures | 18.5 °C |
| Critical factor for this building type (BRE IP 1/06) | 0.75 |
| Surface temperature the critical factor corresponds to | 15 °C |

### US customary

| Result | Value |
|---|---|
| **Temperature factor fRsi** | 0.925 ratio |
| Surface temperature at these air temperatures | 65.3 °F |
| Critical factor for this building type (BRE IP 1/06) | 0.75 |
| Surface temperature the critical factor corresponds to | 59 °F |

## How it is worked out

For a plane element the factor is 1 − U × Rsi, whatever the weather: the temperatures only place the surface temperature on the day. The factor is at or above the 0.75 BRE IP 1/06 gives for dwellings, residential buildings and schools.

The working the page shows, in order: Surface temperature at these air temperatures; Critical factor for this building type (BRE IP 1/06); Surface temperature the critical factor corresponds to; then temperature factor fRsi.

The method, derived in full:

- [Thermal Resistance in Series](https://craftquantities.com/methodology/thermal-resistance-in-series/): Why R-values add but U-values do not, and why the assembly you build never performs like the assembly you specified.

What this calculation does not cover:

- From a U-value the factor holds for a plane element only. Junctions, lintels, window reveals and corners conduct in two or three dimensions and need a model to BS EN ISO 10211, or a measured surface temperature.
- The critical factors are BRE's, derived for the internal humidity each building type is expected to generate; a building used more humidly than its type needs its own assessment to BS EN ISO 13788.
- The factor is about the surface: it says nothing about condensation between the layers of the construction, which BS EN ISO 13788's interstitial method assesses separately.

## Sources

As the calculator cites them (sources checked 2026-09-22):

- BS EN ISO 13788:2012, 3.1.2: fRsi = (θsi − θe) ÷ (θi − θe), calculated with an internal surface resistance Rsi; for a plane element fRsi = 1 − U × Rsi
- BS EN ISO 13788:2012, 4.4.1: Rsi = 0.25 m²K/W for condensation or mould growth on opaque surfaces, representing corners, furniture, curtains or suspended ceilings; for windows and doors the values of Table 2 (0.10 up, 0.13 horizontal, 0.17 down)
- BRE Information Paper IP 1/06, Assessing the effects of thermal bridging at junctions and around openings — critical temperature factors: storage 0.30; offices and retail 0.50; dwellings, residential buildings and schools 0.75; sports halls, kitchens and canteens 0.80; swimming pools, laundries and breweries 0.90

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why use a factor rather than the surface temperature itself?**

Because a surface temperature is only true for the pair of air temperatures it was worked out at, while the factor is a property of the construction. A detail with a factor of 0.75 sits three quarters of the way from the outdoor temperature to the indoor one whatever the weather, so one number describes it on every day of the winter.

**Why is the internal surface resistance 0.25 and not 0.13?**

Because BS EN ISO 13788 assesses mould and condensation on opaque surfaces with a larger film to represent the still air behind furniture and curtains and in corners, where surfaces are coldest. For windows and doors it keeps the ordinary values — 0.13 m²K/W (0.74 hr·ft²·°F/BTU) with horizontal heat flow.

**What does the critical factor mean?**

It is the lowest factor at which the surface stays warm enough to keep its humidity below the level mould needs, for the internal humidity BRE assumed for that type of building. BRE IP 1/06 gives 0.75 for dwellings, residential buildings and schools, less for drier buildings and more for wetter ones.

**Can I find the factor from a thermal camera?**

Yes, with care: read the coldest point of the surface and the room and outdoor temperatures at the same time, on a cold day with a steady difference across the wall. The factor from those three figures describes the detail as it is built, which is what a diagnosis of damp needs.

## Related calculators

- [Curtain Wall Spandrel Condensation Risk Checker](https://craftquantities.com/calculators/materials-quantities/curtain-wall-condensation-checker/)
- [Vapor Barrier Dew-Point Condensation Risk Calculator](https://craftquantities.com/calculators/materials-quantities/vapor-barrier-dewpoint-calculator/)
- [Thermal Bridge Heat Loss Calculator (ψ and χ Values)](https://craftquantities.com/calculators/insulation-efficiency/thermal-bridge-heat-loss-calculator/)
- [Insulation Thickness for a Target U-Value Calculator (BS EN ISO 6946)](https://craftquantities.com/calculators/insulation-efficiency/insulation-thickness-target-u-value-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/surface-temperature-factor-frsi-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/surface-temperature-factor-frsi-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `surface-temperature-factor-frsi-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/surface-temperature-factor-frsi-calculator.json

---
Source: https://craftquantities.com/calculators/insulation-efficiency/surface-temperature-factor-frsi-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.