# ERV/HRV Sizing Calculator

> Estimate the required continuous ventilation rate (CFM or L/s) for a whole-house ERV or HRV, per the ASHRAE 62.2 formula.

Page: https://craftquantities.com/calculators/insulation-efficiency/erv-hrv-sizing-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Required continuous ventilation rate: 78.3 CFM (continuous) for Conditioned Floor Area 1610 sq ft, the page's opening figures; on the metric page, 150 m² gives 37 L/s. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Conditioned Floor Area | `houseArea` | 150 m² | 1610 sq ft | m2, ft2, mm2, in2; range 0.01–1000 m² |
| Number of Bedrooms | `occupants` | 3 | 3 | range 1–10 |

- **Conditioned Floor Area**: The total conditioned floor area of the home.
- **Number of Bedrooms**: ASHRAE 62.2 uses bedroom count as a proxy for expected occupancy.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Required continuous ventilation rate** | 37 L/s |
| House area | 150 m² |

### US customary

| Result | Value |
|---|---|
| **Required continuous ventilation rate** | 78.3 CFM (continuous) |
| House area | 1,610 sq ft |

## How it is worked out

This is the standard ASHRAE 62.2 formula for continuous whole-house mechanical ventilation — actual equipment selection should also account for your specific ERV/HRV unit's rated efficiency and any local code amendments to the base ASHRAE formula.

The working the page shows, in order: House area; then required continuous ventilation rate.

The method, derived in full:

- [Ventilation: Net Free Area, Air Change and the Openings That Deliver Them](https://craftquantities.com/methodology/ventilation-openings-and-air-change/): Why a wooden louvre delivers a quarter of the hole you cut and a metal one three-quarters, why intake and exhaust have to be balanced or the roof ventilates the house, and why doubling the pressure does not double the flow.

What this calculation does not cover:

- This is the whole-house rate only. ASHRAE 62.2 also requires local exhaust at kitchens and bathrooms, sized and ducted separately, and nothing here covers range hoods, bath fans or their duct runs.
- No infiltration credit and no envelope input. The figure is the total ventilation rate; current editions of the standard let a balanced system take credit for natural leakage, so the fan flow a leaky house actually needs can be lower than this. Nothing here reads a blower-door result or an air-tightness figure.
- This is a target flow, not an equipment selection. What a core actually delivers depends on external static pressure, duct length and fittings, filter loading, and how well supply and exhaust are balanced against each other, so a unit whose spec sheet lists this flow can fall well short once it is ducted. Commission with measured flows at the grilles.
- No climate adjustment. Defrost strategies that interrupt the supply side — recirculation, exhaust-only operation, or throttling the supply fan — cut the net fresh air delivered over a cold hour, while a preheater keeps outdoor air flowing continuously and pays for it in energy instead. The ERV-versus-HRV choice for humidity control is not modelled at all, and the number is the same in Miami and in Winnipeg.
- Bedroom count is the standard's occupancy proxy, not your occupancy or your pollutant load. A house run above the bedrooms-plus-one assumption, or one with an attached garage, unvented combustion or a workshop, needs more than this. Local codes and programs amend or replace the base ASHRAE rate, and this calculation does not check for that.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- ASHRAE 62.2 whole-house mechanical ventilation formula: required CFM = 0.03 x floor area (sq ft) + 7.5 x (number of bedrooms + 1)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does a tight, energy-efficient home need mechanical ventilation?**

Air-sealing and insulation improvements reduce the incidental fresh air that used to leak in through gaps — without deliberate mechanical ventilation, indoor air quality, humidity, and odor control can suffer in a very tight home.

**What's the difference between an ERV and an HRV?**

An ERV (energy recovery ventilator) transfers some humidity between the airstreams as well as heat, while an HRV (heat recovery ventilator) transfers heat only. Both recover heat from outgoing air to precondition incoming fresh air, saving energy, and the ERV is often preferred in humid climates or homes needing humidity control.

**Is this rate required to run continuously?**

ASHRAE 62.2 is designed as a continuous (24/7) ventilation rate, though some systems use intermittent operation at a higher rate to average out to the same total air exchange — check your specific system's control strategy.

## Related calculators

- [Air Changes Per Hour (ACH50) Calculator](https://craftquantities.com/calculators/insulation-efficiency/air-changes-per-hour-calculator/)
- [Blower Door CFM50 Target Calculator](https://craftquantities.com/calculators/insulation-efficiency/blower-door-cfm-target-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/erv-hrv-sizing-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/erv-hrv-sizing-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `erv-hrv-sizing-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/erv-hrv-sizing-calculator.json

---
Source: https://craftquantities.com/calculators/insulation-efficiency/erv-hrv-sizing-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.