# Blower Door CFM50 Target Calculator

> Find the target CFM50 blower door reading needed to hit a specific ACH50 airtightness goal.

Page: https://craftquantities.com/calculators/insulation-efficiency/blower-door-cfm-target-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Target CFM50: 432 CFM50 (target maximum) for Conditioned Floor Area 1080 sq ft and Average Ceiling Height 8 ft, the page's opening figures; on the metric page, 100 m² and 2.4 m give 424 CFM50 (target maximum). Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Conditioned Floor Area | `floorArea` | 100 m² | 1080 sq ft | m2, ft2, mm2, in2; range 0.01–1000 m² |
| Average Ceiling Height | `ceilingHeight` | 2.4 m | 8 ft | mm, cm, m, in, ft, yd; range 0.01–6 m |
| Target ACH50 | `targetAch50` | 3 | 3 | range 0.5–15 |

- **Conditioned Floor Area**: The total conditioned (heated/cooled) floor area of the building.
- **Average Ceiling Height**: The average ceiling height across the conditioned space.
- **Target ACH50**: Your airtightness goal, e.g. from an energy code requirement or certification program.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Target CFM50** | 424 CFM50 (target maximum) |
| Building volume | 240 m³ |

### US customary

| Result | Value |
|---|---|
| **Target CFM50** | 432 CFM50 (target maximum) |
| Building volume | 8,640 ft³ |

## How it is worked out

Your actual blower door test result should come in at or below this target — this is the inverse of the Air Changes Per Hour Calculator, useful for setting a goal before construction or air sealing work rather than evaluating a completed test.

The working the page shows, in order: Building volume; then target CFM50.

The method, derived in full:

- [Airtightness, Infiltration and Moisture](https://craftquantities.com/methodology/airtightness-and-infiltration/): Why a blower-door result is not an air change rate, why a leak at the top of a house matters far more than the same leak halfway up, and why sealing without ventilating moves the problem rather than solving it.

What this calculation does not cover:

- Building volume here is nothing more than floor area multiplied by average ceiling height. That ignores the thickness of intermediate floor assemblies, flattens stairwells and double-height spaces into an average, and omits any conditioned basement or attic whose area you did not enter. The target moves in direct proportion to the volume, so a volume measured ten per cent differently from the tester's gives a CFM50 limit ten per cent different — agree the volume basis with whoever will run the test before you build to this number.
- Nothing here defines the tested envelope: whether an attached garage, an unheated basement, a conditioned crawl space or a plant room sits inside or outside it. That single decision changes both the volume in the denominator and the leakage the fan has to move. Two people can test the same building to two different ACH50 figures purely by drawing the boundary in two different places.
- ACH50 normalises leakage against volume. UK and much European testing, and some North American programmes, instead specify air permeability or leakage per unit of envelope area. This page never asks for envelope area, so a target handed to you in those terms cannot be met by hitting this CFM50 figure.
- The number assumes a properly conducted test at 50 Pa. It carries no correction for wind, stack effect or baseline pressure, no averaging of a depressurisation result against a pressurisation one, and no allowance for how the building is prepared — which trickle vents, flues, extract fans and drain traps get sealed and which are left as found. Those are the usual reasons two tests of the same building disagree.
- This is a target airflow, not a ventilation or combustion-air check. A building tightened towards a low ACH50 needs mechanical ventilation sized and commissioned for it, and any open-flued or naturally aspirated appliance inside the envelope needs its own combustion air and spillage assessment. Hitting this figure says nothing about either, and those are the parts that carry a safety consequence.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- Standard blower door formula rearranged: target CFM50 = (target ACH50 x building volume in cubic feet) / 60

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**When would I use this instead of the Air Changes Per Hour Calculator?**

Use this one before construction or an air-sealing project, to know what CFM50 result you're aiming for. Use the Air Changes Per Hour Calculator afterward, once you have an actual blower door test result, to see what ACH50 you achieved.

**Is hitting the target guaranteed by good workmanship alone?**

No: careful air sealing — caulk, foam, taped sheathing seams, sealed penetrations — is the main driver, but the actual result depends on many construction details. Most builders targeting an aggressive ACH50 use a blower door test mid-construction to catch and fix leaks before drywall closes up the walls.

**Does a lower target always cost more to achieve?**

Generally yes, especially at the tightest levels (well under 1 ACH50) which require deliberate air-sealing details throughout construction — but many of the basic measures that get a home to a moderate target (3-5 ACH50) are low-cost, common-sense sealing practices.

## Related calculators

- [Air Changes Per Hour (ACH50) Calculator](https://craftquantities.com/calculators/insulation-efficiency/air-changes-per-hour-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/blower-door-cfm-target-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/blower-door-cfm-target-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `blower-door-cfm-target-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/blower-door-cfm-target-calculator.json

---
Source: https://craftquantities.com/calculators/insulation-efficiency/blower-door-cfm-target-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.