# Air Permeability (q50) and Test Flow Calculator

> Air permeability (q50) from an air tightness test's flow over the envelope area, or the fan flow a target needs, with the n50 air change rate.

Page: https://craftquantities.com/calculators/insulation-efficiency/air-permeability-q50-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-09-22, 3 published test vectors.

Air permeability q50: 0.274 CFM/ft² for Envelope Area 2690 sq ft, Internal Volume 8829 ft³ and Measured Flow at 50 Pa 735.72 CFM, the page's opening figures; on the metric page, 250 m², 250 m³ and 1250 m³/h give 5 m³/h·m². Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| What You Want | `mode` | The permeability a measured test flow gives | The permeability a measured test flow gives | `measured`, `target` |
| Envelope Area | `envelopeArea` | 250 m² | 2690 sq ft | m2, ft2, mm2, in2; range 1–500000 m² |
| Internal Volume | `volume` | 250 m³ | 8829 ft³ | l, gal, m3, ft3, yd3; range 1000–10000000000 L |
| Measured Flow at 50 Pa | `measuredFlow` | 1250 m³/h | 735.722 CFM | lps, m3h, lpm, cfm; range 1–50000000 L/s |
| Target Air Permeability | `targetQ50` | 5 m³/h·m² | 0.273403 CFM/ft² | m3_h_m2, cfm_ft2; range 0.1–50 m³/h·m² |
| Flow Exponent n From the Test (0 to skip) | `exponent` | 0 | 0 | range 0–1 |

- **What You Want**: Work a result from a test, or the flow a test rig has to reach for a target.
- **Envelope Area**: Every internal surface bounding the tested volume — walls, the underside of the roof, and the ground floor.
- **Internal Volume**: The volume inside the tested envelope, for the air change rate of the same test.
- **Measured Flow at 50 Pa**: The fan flow that held the building at 50 pascals, from the test report.
- **Target Air Permeability**: The permeability the building has to achieve, from the specification or the design.
- **Flow Exponent n From the Test (0 to skip)**: The exponent of the test's own multi-point fit, to carry the result to 75 Pa.

`measuredFlow` applies only when `mode` is `measured`.
`targetQ50` applies only when `mode` is `target`.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Air permeability q50** | 5 m³/h·m² |
| Measured flow at 50 Pa | 1,250 m³/h |
| The same flow in litres per second | 347.22 L/s |
| Air changes per hour at 50 Pa (n50) | 5 per hour |

### US customary

| Result | Value |
|---|---|
| **Air permeability q50** | 0.274 CFM/ft² |
| Measured flow at 50 Pa | 735.72 CFM |
| Air changes per hour at 50 Pa (n50) | 5 per hour |

## How it is worked out

Air permeability is the test flow divided by the envelope area; the air change rate divides the same flow by the volume. They are one test described two ways.

The working the page shows, in order: Measured flow at 50 Pa; The same flow in litres per second; Air changes per hour at 50 Pa (n50); then air permeability q50.

The method, derived in full:

- [Airtightness, Infiltration and Moisture](https://craftquantities.com/methodology/airtightness-and-infiltration/): Why a blower-door result is not an air change rate, why a leak at the top of a house matters far more than the same leak halfway up, and why sealing without ventilating moves the problem rather than solving it.

What this calculation does not cover:

- The envelope area is a take-off, and the published result moves in proportion to it. Agree the boundary — ground floor included, separate zones excluded — with whoever will accept the certificate.
- A result at 50 Pa (0.2 in. w.g.) is not a result at 75 Pa (0.3 in. w.g.) with a unit change. The 75 Pa figures appear only when the test's own flow exponent is entered.
- It is arithmetic on the test's figures; the measurement itself follows BS EN ISO 9972 under ATTMA TSL1 for dwellings or TSL2 for other buildings.

## Sources

As the calculator cites them (sources checked 2026-09-22):

- BS EN ISO 9972:2015, Thermal performance of buildings — Determination of air permeability of buildings — Fan pressurization method: air permeability = the flow at the reference pressure ÷ the envelope area; air change rate = the flow ÷ the internal volume
- ATTMA Technical Standards L1 (dwellings) and L2 (non-dwellings), the UK measurement standards behind Approved Document L submissions, at 50 Pa
- The power law of the fan pressurization method, Q = C × Δpⁿ, which carries a flow from one test pressure to another only with the exponent n from the test's own fit

The site's pages for the documents these name:

- [Approved Documents to the Building Regulations (England)](https://craftquantities.com/standards/uk-gov/uk-approved-documents/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does a warehouse look so airtight in air changes?**

Because a big box holds a great deal of volume for each square metre of skin, and leaks are in the skin. The guide's shed at a permeability of 5 is only about one air change per hour at 50 Pa — a figure that would be exceptional for a house and is ordinary here. The area-based figure does not flatter it.

**Can I convert a 50 Pa result to 75 Pa?**

Only with the test's own flow exponent, because leakage follows a power law whose exponent depends on the leaks. Enter it and the page carries the flow and the permeability to 75 Pa; without it the conversion would be a guess.

**Is the floor really part of the envelope?**

Yes. The envelope is every internal surface bounding the tested volume, the ground floor slab included, and leaving it out raises the reported permeability by the same proportion.

## Related calculators

- [Air Changes Per Hour (ACH50) Calculator](https://craftquantities.com/calculators/insulation-efficiency/air-changes-per-hour-calculator/)
- [Blower Door CFM50 Target Calculator](https://craftquantities.com/calculators/insulation-efficiency/blower-door-cfm-target-calculator/)
- [Stack Effect Pressure Calculator](https://craftquantities.com/calculators/plumbing-hvac/stack-effect-pressure-calculator/)
- [HVAC Thermal Load (U-Value) Calculator](https://craftquantities.com/calculators/plumbing-hvac/hvac-thermal-load-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/air-permeability-q50-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/air-permeability-q50-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `air-permeability-q50-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/air-permeability-q50-calculator.json

---
Source: https://craftquantities.com/calculators/insulation-efficiency/air-permeability-q50-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.