# Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)

> How much voltage a copper or aluminum run loses over distance — 14 AWG to 1,000 kcmil, single or three phase — against the 3% and 5% the NEC suggests.

Page: https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.0, sources checked 2026-10-05, 25 published test vectors.

Voltage drop: 1.94 V for One-Way Wire Run Length 49 ft, the page's opening figures; on the metric page, 15 m gives 1.94 V. Source: IAEI Magazine, "Voltage Drop Formulas" (March/April 2017).

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Conductor metal | `material` | Copper (uncoated) | Copper (uncoated) | `copper`, `aluminum` |
| Conductor size (AWG or kcmil) | `wireGauge` | 12 AWG | 12 AWG | `14`, `12`, `10`, `8`, `6`, `4`, `3`, `2`, `1`, `1/0`, `2/0`, `3/0`, `4/0`, `250`, `300`, `350`, `400`, `500`, `600`, `750`, `1000` |
| Circuit | `phase` | Single phase (or DC), out and back | Single phase (or DC), out and back | `single`, `three` |
| One-Way Wire Run Length | `oneWayLength` | 15 m | 49 ft | mm, cm, m, in, ft, yd; range 0.01–600 m |
| Current Draw | `currentAmps` | 10 | 10 | range 0.5–2000 |
| Circuit Voltage | `circuitVoltage` | 120 V | 120 V | `120`, `208`, `240`, `277`, `480`, `other` |
| Voltage you are working at (V) | `customVoltage` | 600 | 600 | range 6–1000 |

- **Conductor metal**: Copper, or aluminum — the metal printed on the jacket (CU or AL).
- **Conductor size (AWG or kcmil)**: The size printed on the jacket: an AWG number up to 4/0, then kcmil.
- **Circuit**: Single phase — including a 240 V circuit and DC — or a balanced three-phase circuit.
- **One-Way Wire Run Length**: The distance from the panel to the load, one direction only.
- **Current Draw**: The expected current draw of the load in amps.
- **Circuit Voltage**: The nominal circuit voltage — line to line for three phase.
- **Voltage you are working at (V)**: Any nominal voltage the list does not carry.

`customVoltage` applies only when `circuitVoltage` is `other`.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Voltage drop** | 1.94 V |
| Voltage drop | 1.62 % |
| Voltage at the load | 118.06 V |
| K constant, Ω·cmil per ft | 12.9 |
| Conductor area, circular mils | 6,530 |

### US customary

| Result | Value |
|---|---|
| **Voltage drop** | 1.94 V |
| Voltage drop | 1.61 % |
| Voltage at the load | 118.06 V |
| K constant, Ω·cmil per ft | 12.9 |
| Conductor area, circular mils | 6,530 |

## How it is worked out

The working the page shows, in order: Voltage drop; Voltage at the load; K constant, Ω·cmil per ft; Conductor area, circular mils; then voltage drop.

The method, derived in full:

- [Voltage Drop and Conductor Sizing](https://craftquantities.com/methodology/voltage-drop-and-conductor-sizing/): Why the run length doubles, why a 12 V circuit suffers a hundred times the percentage loss of a 120 V one, and why ampacity answers a different question entirely.

What this calculation does not cover:

- VOLTAGE DROP IS NOT AMPACITY, and the two are different questions with different answers. A conductor can stay inside the 3% suggestion and still be too small to carry the current without overheating, and it can be thermally adequate and still drop too much over a long run. Both checks have to be made, and only one of them is made here.
- The K constants are DC resistance at 75 °C (167 °F) for uncoated copper and for aluminum, the basis of NEC Chapter 9 Table 8. The table's size-by-size resistances differ from the single constant by a percent or so either way, and the table is not reproduced here. A conductor running cooler drops a little less and one at a 90 °C (194 °F) rating a little more; tinned (coated) copper has its own, slightly higher resistance.
- Treats the circuit as resistive, which is close for lighting, heating and most branch circuits. On a large AC feeder, and above all one in steel conduit feeding an inductive load, the conductor's reactance adds to the drop and the power factor matters; Table 9 of the same chapter carries the AC figures and is not reproduced here.
- Three phase assumes a balanced load and gives the drop between lines. A single-phase load taken from one line to neutral of a three-phase supply is a single-phase circuit: choose single phase and the line-to-neutral voltage.
- Aluminum conductors need terminations and devices listed for them; the code does not let dissimilar metals be joined except in a device listed for the purpose. Nothing here checks a termination, a lug or a splice.
- The 3% and 5% figures are suggestions in the code's informational notes rather than requirements, though a local amendment, an equipment maker's instructions or a specification can make a tighter figure binding.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-10-05):

- Standard single-phase voltage drop formula: Vdrop = (2 x K x one-way length in ft x amps) / circular mils, K=12.9 for copper
- NEC recommends keeping voltage drop to 3% or less for branch circuits (and 5% total including feeders) for reasonable efficiency, though it is a recommendation, not a hard code violation
- IAEI Magazine, "Voltage Drop Formulas" (March/April 2017): K is a conductor's resistance per foot times its area in circular mils — the resistance of a conductor one circular mil in area and one foot long — at 75 °C (167 °F), from NEC Chapter 9 Table 8: 1,000 kcmil uncoated copper at 0.0129 Ω per 1,000 ft (0.0423 Ω/km) gives 12.9, 1,000 kcmil aluminum at 0.0212 Ω per 1,000 ft (0.0696 Ω/km) gives 21.2, and every size in the table works out close to these; the single-phase multiplier 2 becomes 1.732 for three phase <https://iaeimagazine.org/electrical-fundamentals/voltage-drop-formulas/>
- EC&M, "Stumped by the Code? NEC Requirements for Conductor Material Types and Sizing Requirements" (Mike Holt, 9 February 2023, on the 2023 NEC): Section 310.3(A) sets the smallest conductors at 14 AWG for copper and 12 AWG for aluminum or copper-clad aluminum, except where the code permits otherwise <https://www.ecmweb.com/home/article/21259364/stumped-by-the-code-nec-requirements-for-conductor-material-types-and-sizing-requirements>

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does voltage drop matter?**

Excessive voltage drop wastes energy as heat in the wire and can cause motors to run hotter and less efficiently, dim lights, or trip sensitive electronics — the NEC recommends staying under 3% for branch circuits as a best practice.

**Is exceeding 3% a code violation?**

No — the NEC's voltage drop figures sit in informational notes, which explain rather than require, unlike breaker sizing. Exceeding them is still a real efficiency and equipment-longevity concern, and an equipment maker's instructions or a specification can make a tighter figure binding.

**What lowers voltage drop?**

A larger (lower-numbered) conductor or a shorter run lowers it, because both reduce the resistance the current has to push through. Which, if either, is the circuit designer's call, made with the ampacity, the overcurrent protection and the terminations in view.

**How much more does aluminum drop than copper?**

About 64% more at the same size, because its K is 21.2 against copper's 12.9. To drop the same voltage an aluminum conductor needs roughly 1.64 times the area: two sizes up for the small branch-circuit sizes from 14 to 6 AWG, where each size is two gauge numbers, and usually three for feeders and large conductors from 4 AWG up, where the sizes run closer together. That is why aluminum feeders look two or three sizes heavier than the copper they replace. The copper-to-aluminum page works the size on that basis.

**How is three phase different?**

The multiplier is 1.732 instead of 2, because in a balanced three-phase circuit the currents in the lines cancel in the neutral and the drop is measured between lines. The same conductor, length and current therefore drop about 13% less on a three-phase circuit — and the percentage is taken against the line-to-line voltage, 208 or 480 V, not 120 or 277 V.

## Related calculators

- [Cable Voltage Drop Calculator (mm², Copper or Aluminium)](https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/)
- [Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²)](https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/)
- [Electrical Circuit Load Calculator](https://craftquantities.com/calculators/electrical/electrical-load-calculator/)
- [Wire Gauge to Amperage Calculator](https://craftquantities.com/calculators/electrical/wire-gauge-to-amperage-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/wire-gauge-voltage-drop-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/wire-gauge-voltage-drop-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `wire-gauge-voltage-drop-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/wire-gauge-voltage-drop-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.