# Wire Gauge to Amperage Calculator

> Look up the NEC allowable ampacity of a copper conductor from its AWG size, at the 60, 75 and 90 °C (140, 167 and 194 °F) insulation ratings.

Page: https://craftquantities.com/calculators/electrical/wire-gauge-to-amperage-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.1, sources checked 2026-09-01, 4 published test vectors.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Conductor size | `awg` | 12 AWG | 12 AWG | `14`, `12`, `10`, `8`, `6`, `4`, `3`, `2`, `1`, `0` |

- **Conductor size**: The AWG size of the copper conductor, as printed on the jacket.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Allowable ampacity at 75 °C** | 25 A |
| 60 °C column | 20 A |
| 75 °C column | 25 A |
| 90 °C column | 30 A |
| Maximum overcurrent protection — NEC 240.4(D) | 20 A |

### US customary

| Result | Value |
|---|---|
| **Allowable ampacity at 75 °C** | 25 A |
| 60 °C column | 20 A |
| 75 °C column | 25 A |
| 90 °C column | 30 A |
| Maximum overcurrent protection — NEC 240.4(D) | 20 A |

## How it is worked out

NEC Table 310.16, copper, 75 °C column headline. Table value only — apply the adjustment and correction factors for conduit fill and ambient temperature, and never exceed the 240.4(D) cap on 14, 12 and 10 AWG.

The working the page shows, in order: 60 °C column; 75 °C column; 90 °C column; Maximum overcurrent protection — NEC 240.4(D); then allowable ampacity at 75 °C.

The method, derived in full:

- [Voltage Drop and Conductor Sizing](https://craftquantities.com/methodology/voltage-drop-and-conductor-sizing/): Why the run length doubles, why a 12 V circuit suffers a hundred times the percentage loss of a 120 V one, and why ampacity answers a different question entirely.

What this calculation does not cover:

- Copper only. Aluminium has its own column with materially lower values — using the copper figure on aluminium oversizes the protection, which is the dangerous direction.
- Assumes ambient 30 °C and not more than three current-carrying conductors in the raceway. Outside either condition, the table value must be derated — see the derating calculator.
- The temperature column that governs is the lowest rating in the whole path: conductor, terminations and equipment. Most breakers are listed at 75 °C and much residential equipment at 60 °C.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-01):

- NFPA 70 (NEC) Table 310.16 — Allowable Ampacities of Insulated Conductors, copper, 60/75/90 °C columns, ambient 30 °C, not more than three current-carrying conductors
- NEC 240.4(D) — small-conductor overcurrent limits: 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG copper

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is 12 AWG protected at 20 A when the table says 25 A?**

NEC 240.4(D) caps overcurrent protection for the small conductors regardless of the table: 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG. The table ampacity is what the conductor can carry; the cap is what you may protect it at. The lower of the two governs, and for these three sizes it is almost always the cap.

**Which temperature column applies to my circuit?**

The lowest rating in the whole path — conductor insulation, terminations and equipment. Most breakers and devices are listed at 75 °C, and much residential equipment at 60 °C, so a 90 °C cable is usually still limited to the 75 °C or 60 °C column. The 90 °C figure is generally used only as the starting point for derating.

**Does this figure change with conduit fill or ambient temperature?**

Yes, and often substantially. More than three current-carrying conductors in a raceway triggers an adjustment factor, and ambient above 30 °C triggers a correction factor. Both reduce the allowable ampacity, and both are applied to the table value rather than replacing it — see the derating calculator.

**Can I use this for aluminium?**

No. Aluminium carries materially less current for the same gauge — 12 AWG aluminium is 20 A at 75 °C against copper's 25 A — and it has its own column in Table 310.16. Using the copper figure on an aluminium conductor oversizes the protection, which is the dangerous direction.

**Why can I not enter 7 AWG or 9 AWG?**

Because Table 310.16 has no row for them. The table steps 14, 12, 10, 8, 6, 4, 3, 2, 1 and then into the 1/0 sizes, so it is not that odd numbers are skipped — 3 and 1 are both published — it is that 5, 7, 9, 11 and 13 are not. Those exist as manufactured wire but carry no tabulated ampacity here. An earlier version of this page accepted any number and had no answer for those sizes; offering only the published rows is the honest shape of the tool.

## Related calculators

- [Amperage to Wire Gauge Calculator](https://craftquantities.com/calculators/electrical/amperage-to-wire-gauge-calculator/)
- [Feeder Conductor Ampacity Derating Calculator](https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/)
- [Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)](https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/wire-gauge-to-amperage-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/wire-gauge-to-amperage-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `wire-gauge-to-amperage-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/wire-gauge-to-amperage-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/wire-gauge-to-amperage-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.