# Watts to Amps Calculator (230 V)

> Convert appliance wattage into current on a 230 V supply for fuse, breaker and cable selection.

Page: https://craftquantities.com/calculators/electrical/watts-to-amps-230v-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Current draw: 13 A for Power 3000, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Power (W) | `watts` | 3000 | 3000 | range 0–30000 |

- **Power (W)**: The appliance's rated power in watts.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Current draw** | 13 A |
| Conversion factor applied | 0 A per W |

### US customary

| Result | Value |
|---|---|
| **Current draw** | 13 A |
| Conversion factor applied | 0 A per W |

## How it is worked out

I = P ÷ V at 230 V single phase. Check the result against the circuit's protective device rating and, on long runs, against voltage drop.

The working the page shows, in order: Conversion factor applied; then current draw.

The method, derived in full:

- [Unit Conversion, Exactness and Rounding](https://craftquantities.com/methodology/unit-conversion-and-rounding/): Why most conversion factors carry no uncertainty at all, which ones hide a material assumption, and why converting a measurement can never make it more precise than it was.

What this calculation does not cover:

- The division assumes the watt figure is also the volt-amp figure — a power factor of 1. Motors, compressors, transformers and switched-mode electronics draw more current than this, by the reciprocal of their power factor. Where the rating plate gives a VA figure as well as watts, divide the VA figure instead.
- The answer is the current at a nominal 230 V. Real supplies sit inside a tolerance band and often measure closer to 240 V, and nothing here models voltage drop along the run — which is usually what decides conductor size on a long circuit, not the current figure itself.
- Single phase only. A three-phase load's line current involves the line voltage and a root-three term, so pushing a three-phase wattage through this produces a number that has no relationship to the circuit.
- This is a conversion, not a load calculation and not a circuit design. It applies no diversity, no continuous-load derating, and none of the correction factors — grouping, ambient temperature, insulation, installation method — that set a cable's real current-carrying capacity, and it takes no account of what is already connected to the circuit. Protective device and conductor selection, earth fault loop impedance and disconnection times are work for a qualified electrician against the wiring rules that apply where you are.
- Starting current is excluded. A motor or compressor can pull several times its running current while it comes up to speed, which bears on the type and curve of the protective device rather than on the steady-state figure given here.

A professional must decide:

- This is a conversion, not a load calculation and not a circuit design. It applies no diversity, no continuous-load derating, and none of the correction factors — grouping, ambient temperature, insulation, installation method — that set a cable's real current-carrying capacity, and it takes no account of what is already connected to the circuit.
- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- I = P / V, rearranged from P = V x I
- UK plug fuses are manufactured in 3 A, 5 A and 13 A ratings (BS 1362)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Which plug fuse should I fit?**

The smallest standard rating at or above the appliance current draw. BS 1362 fuses come in 3 A, 5 A and 13 A, and the fuse protects the FLEX rather than the appliance, so fitting 13 A to everything leaves a thin lead unprotected until a much larger fault develops. A 500 W appliance draws 2.2 A at 230 V and takes a 3 A fuse. The rough trade boundary is around 700 W, which is worth doing the arithmetic on rather than guessing: 700 W is 3.04 A, just over a 3 A fuse, which is why appliances near that figure are commonly fused at 13 A with a suitably rated flex.

**Why is my shower on such a large cable?**

Because electric showers are among the biggest single-phase loads in a house. A 9 kW shower draws roughly 39 A at 230 V, which needs its own circuit, a substantial conductor and an appropriately rated device — it is not something to add to an existing ring.

**Does cable length affect this?**

Not the current, but it does affect whether the cable is adequate. Voltage drop accumulates over distance, and a long run may need a larger conductor than the current alone would suggest in order to keep the drop within limits.

## Related calculators

- [Amps to Watts Calculator (230 V)](https://craftquantities.com/calculators/electrical/amps-to-watts-230v-calculator/)
- [Watts, Amps and kVA Calculator (Any Voltage, AC or DC)](https://craftquantities.com/calculators/electrical/watts-amps-kva-calculator/)
- [Watts to Amps Calculator (120 V)](https://craftquantities.com/calculators/electrical/watts-to-amps-120v-calculator/)
- [Amperage to Wire Gauge Calculator](https://craftquantities.com/calculators/electrical/amperage-to-wire-gauge-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/watts-to-amps-230v-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/watts-to-amps-230v-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `watts-to-amps-230v-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/watts-to-amps-230v-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/watts-to-amps-230v-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.