# Watts, Amps and kVA Calculator (Any Voltage, AC or DC)

> Convert watts to amps, amps to watts, or kVA to amps at any voltage — DC, single-phase or three-phase AC, with the power factor you enter.

Page: https://craftquantities.com/calculators/electrical/watts-amps-kva-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-10-05, 15 published test vectors.

Current or power: 30 A for Power 7200 and Power factor 1, the page's opening figures. Source: WEG Rolled Steel General Purpose 1-phase Motors, performance data (AutomationDirect catalogue page tMTR-54).

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Supply | `supply` | AC (mains) | AC (mains) | `ac`, `dc` |
| Phases | `phase` | Single phase | Single phase | `single`, `three` |
| Voltage | `voltage` | 240 V (North American dryer, range, EV charger or heat pump circuit) | 240 V (North American dryer, range, EV charger or heat pump circuit) | `12`, `24`, `48`, `120`, `208`, `230`, `240`, `277`, `400`, `415`, `480`, `other` |
| Voltage you are working at (V) | `customVoltage` | 220 | 220 | range 1–1500 |
| What you know | `known` | The power in watts — find the amps | The power in watts — find the amps | `watts`, `amps`, `kva` |
| Power (W) | `watts` | 7200 | 7200 | range 0–2000000 |
| Current (A) | `amps` | 32 | 32 | range 0–10000 |
| Apparent power (kVA) | `kva` | 10 | 10 | range 0–100000 |
| Power factor | `powerFactor` | 1 | 1 | range 0.2–1 |

- **Supply**: Alternating current from the mains or a generator, or direct current from a battery, a solar array or a DC bus.
- **Phases**: Single phase for houses and most appliances; three phase for larger commercial and industrial loads.
- **Voltage**: The supply's nominal voltage — for three phase, the voltage between two lines.
- **Voltage you are working at (V)**: Any voltage the quick picks do not list, in volts.
- **What you know**: The figure on the nameplate, the datasheet or the meter: watts, amps, or kVA.
- **Power (W)**: The real power in watts, from the rating plate or a data sheet.
- **Current (A)**: The current in amps: the nameplate's running current or a clamp-meter reading.
- **Apparent power (kVA)**: The kVA rating of a generator, transformer, UPS or supply.
- **Power factor**: 1 for heaters, kettles and incandescent lamps; lower for motors and inductive loads.

`phase` applies only when `supply` is `ac`.
`customVoltage` applies only when `voltage` is `other`.
`watts` applies only when `known` is `watts`.
`amps` applies only when `known` is `amps`.
`kva` applies only when `known` is `kva`.
`powerFactor` applies only when `supply` is `ac`.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Current or power** | 30 A |
| Apparent power | 7.2 kVA |
| Reactive power | 0 kvar |
| Voltage used | 240 V |
| Power factor used | 1 |

### US customary

| Result | Value |
|---|---|
| **Current or power** | 30 A |
| Apparent power | 7.2 kVA |
| Reactive power | 0 kvar |
| Voltage used | 240 V |
| Power factor used | 1 |

## How it is worked out

Single-phase AC: apparent power is volts times amps, and real power is that times the power factor. At a power factor of 1 the two are the same; below 1 the supply carries more current than the watts alone suggest.

The working the page shows, in order: Apparent power; Reactive power; Voltage used; Power factor used; then current or power.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- These are the defining relationships between volts, amps, watts and volt-amperes, and nothing else. The page does not size a conductor, a breaker, a fuse or a plug, and it applies no continuous-load allowance, diversity or derating; those are decided against the wiring rules where the work is done, by the person who signs for it.
- The voltage is the nominal one you chose. A real supply sits somewhere inside a tolerance band and sags along a loaded circuit; a constant-power load such as a motor drive or a charger draws proportionally more current as the voltage falls, so the current at a weak point of a long run is higher than the nominal answer.
- Three phase assumes a balanced load: the same current in each line. An unbalanced load puts current in the neutral and the line currents stop being interchangeable, so one figure no longer describes the circuit; work each phase as a single-phase load at the line-to-neutral voltage instead.
- The power factor entered is taken as the true power factor. Variable-speed drives, LED drivers and switch-mode supplies draw distorted current, and a meter that reports only the displacement factor flatters the answer; on those loads the nameplate's current or VA figure is the safer starting point.
- Running current only. Motors, compressors and transformers draw several times their running current for the first moments after switching on, and that inrush, not this figure, is what a protective device's type and a generator's size have to allow for.
- A heat pump's or an air conditioner's circuit is built to the minimum circuit ampacity and maximum overcurrent protection printed on its nameplate, not to a current worked back from its wattage; the same holds for any appliance whose installation instructions name a circuit.
- A motor's rating is the power at its shaft, not the power it draws, so a rating entered here as watts understates the current: a 1 hp single-phase motor entered at its rating with a power factor of 0.85 reads 3.8 A on 230 V, where WEG lists its own 1 hp motors at 5.06 and 6.8 A. The single-phase and three-phase motor pages divide by the motor's efficiency as well as its power factor.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-10-05):

- Definitions of real, apparent and reactive power: DC P = V × I; single-phase S = V × I and P = V × I × PF; three-phase S = √3 × V(line-to-line) × I and P = √3 × V × I × PF for a balanced load; Q = S × √(1 − PF²)
- Balanced three-phase systems: the line-to-line voltage is √3 times the line-to-neutral voltage (phases 120° apart), so three loads at V/√3 each draw √3 × V × I in total
- WEG Rolled Steel General Purpose 1-phase Motors, performance data (AutomationDirect catalogue page tMTR-54): the four-pole motors from 1/4 to 1 hp at full-load power factors of 0.59 to 0.68; the 1 hp motors listed at 6.8 A (1,745 rpm, 71.0%, 0.68) and 5.06 A (3,500 rpm, 70.0%, 0.92) on 230 V <https://cdn.automationdirect.com/static/specs/weg1phmotor.pdf>
- WEG W22 Single-Phase Electric Motor, Commercial Catalogue, European Market (Cod. 50069268, Rev. 00, 01/2017), page 5: motors with start and run capacitors, 0.18 to 9.2 kW, at full-load power factors of 0.75 to 0.99 <https://static.weg.net/medias/downloadcenter/h52/h99/WEG-w22-single-phase-european-market-50069268-brochure-english-web.pdf>

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**How many amps does a 240 V dryer, EV charger or heat pump draw?**

Divide its watts by 240. A dryer element rated 5,600 W draws 23.3 A; a Level 2 charger set to 48 A is 48 × 240 = 11,520 W, which is the figure the site's EV charger worked example carries into the service load. A heat pump is the exception to doing it this way round: its circuit is built to the minimum circuit ampacity and the maximum overcurrent protection on its nameplate, which already allow for the compressor and fans together, so read those rather than working back from a wattage.

**Why is three-phase current lower for the same power?**

Because the load is shared between three line conductors and the line-to-line voltage carries a √3 factor. Take 10 kVA at 400 V: it is 25 A on a single-phase circuit at 400 V, but 14.4 A in each line of a three-phase supply at 400 V line to line. Entering the line-to-neutral voltage — 230 or 277 V — with three phase selected is the commonest slip, and it overstates the current by about three quarters.

**Do I need the power factor?**

Only to move between watts and amps or kVA on AC. For heaters, kettles, ovens and incandescent lamps it is 1 and can be left there. For motors, compressors and older electronics it is lower, and the current is higher than the watts suggest by the reciprocal of the power factor — 37.5 A rather than 30 A for 7,200 W at 240 V and a power factor of 0.8. A motor's hp or kW rating is not those watts, though: it is the output at the shaft, and the motor pages divide by its efficiency too. Going from kVA to amps needs no power factor at all.

**Which voltage should I use: nominal or what my meter reads?**

Nominal, for anything being compared with a rating — equipment, breakers and cables are all rated against nominal voltage. A measured figure is useful for explaining why a clamp reading disagrees with the arithmetic by a few percent: real supplies sit inside a tolerance band either side of nominal, and a heater draws a little more current on a high supply while a charger or a motor drive draws a little more on a low one.

**Why are there separate 120 V and 230 V pages?**

They answer the two most common searches in one step each, with nothing to choose. This page is for every other case: 240 V, the three-phase voltages, DC, a power factor below 1, or a voltage none of the pages list. At 120 V or 230 V with a power factor of 1 the answers agree exactly.

## Related calculators

- [Watts to Amps Calculator (120 V)](https://craftquantities.com/calculators/electrical/watts-to-amps-120v-calculator/)
- [Watts to Amps Calculator (230 V)](https://craftquantities.com/calculators/electrical/watts-to-amps-230v-calculator/)
- [Three-Phase Power Calculator](https://craftquantities.com/calculators/electrical/three-phase-power-calculator/)
- [kVA to kW Calculator](https://craftquantities.com/calculators/electrical/kva-to-kw-calculator/)
- [Single-Phase Motor Full-Load Current Calculator (Amps from hp or kW)](https://craftquantities.com/calculators/electrical/single-phase-motor-full-load-current-calculator/)
- [Three-Phase Motor Full-Load Amperage Calculator](https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/watts-amps-kva-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/watts-amps-kva-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `watts-amps-kva-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/watts-amps-kva-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/watts-amps-kva-calculator/