# Three-Phase Power Calculator

> Calculate real power (kW) for a three-phase electrical load from voltage, current, and power factor.

Page: https://craftquantities.com/calculators/electrical/three-phase-power-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Real power: 35.3 kW for Line Voltage 480, Current 50 and Power Factor 0.85, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Line Voltage (V) | `voltage` | 480 | 480 | range 100–1000 |
| Current (A) | `currentAmps` | 50 | 50 | range 1–1000 |
| Power Factor | `powerFactor` | 0.85 | 0.85 | range 0.5–1 |

- **Line Voltage (V)**: The line-to-line voltage of the three-phase system.
- **Current (A)**: The current draw per phase, in amps.
- **Power Factor**: The load's power factor — 1.0 is purely resistive, motors are typically lower.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Real power** | 35.3 kW |
| Apparent power | 41.57 kVA |

### US customary

| Result | Value |
|---|---|
| **Real power** | 35.3 kW |
| Apparent power | 41.57 kVA |

## How it is worked out

The working the page shows, in order: Apparent power; then real power.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- BALANCED loads only. The square root of three assumes the three phases carry equal current; an unbalanced load puts current in the neutral and the phase currents stop being interchangeable, so a single measured current no longer describes the system.
- The power factor entered has to be the TRUE power factor, not the displacement factor alone. Variable-speed drives, LED drivers and switched-mode supplies draw harmonic current that adds to the apparent power without adding real power, and a meter reporting only displacement will flatter the answer.
- Sizing conductors and protection from this figure means going through current, not kilowatts: ampacity, voltage drop, the protective device and any derating for grouping or ambient temperature are separate calculations, and the kW here is an input to none of them directly.
- Motor loads draw far more than their running current at start-up — several times, depending on the starting method — and it is the starting condition that sizes the protection and stresses the supply.
- Harmonic current also loads the neutral in a way the phase figures do not show. On a three-phase supply with many single-phase electronic loads, the triplen harmonics add rather than cancel in the neutral, which is why a neutral sized to match the phases can still run hot.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- Standard three-phase power formula: P = sqrt(3) x V x I x power factor

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does three-phase power use sqrt(3) instead of just multiplying voltage by current?**

In a three-phase system, the three phases are offset by 120°, so their combined power isn't a simple sum — the sqrt(3) factor (approximately 1.732) accounts for this phase relationship in the standard line-to-line voltage power formula.

**What's the difference between kW and kVA?**

kVA is apparent power (voltage x current, ignoring phase angle), and kW is real power, the actual usable power after accounting for power factor, so kW is always less than or equal to kVA. Equipment ratings sometimes use one or the other depending on the context.

**Where would I use this calculation?**

Common uses include sizing generators, transformers, or panels for three-phase equipment like large HVAC units, industrial motors, or commercial pump systems.

## Related calculators

- [Watts, Amps and kVA Calculator (Any Voltage, AC or DC)](https://craftquantities.com/calculators/electrical/watts-amps-kva-calculator/)
- [Transformer Sizing Calculator](https://craftquantities.com/calculators/electrical/transformer-sizing-calculator/)
- [Electrical Circuit Load Calculator](https://craftquantities.com/calculators/electrical/electrical-load-calculator/)
- [Three-Phase Motor Full-Load Amperage Calculator](https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/three-phase-power-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/three-phase-power-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `three-phase-power-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/three-phase-power-calculator.json

---